Power System
Parameters
Out-of-Step Blocking
Protection Apoliatian amples | AMIS
‘ut-of-Step Logic Application Examples
Table 1.32 lists the power system parameters.
Table 132 Positive-Sequence Impedances (Secondary)
ine impedances
tua 8.00.0.287.8" secondary (ZIMAG Q ZZIAN
‘Zone 2 Phase Distance Reach
zee 9.60 secondary
Source $ impedances
ths 880.288" secondary
Source R impedances:
Zan 352.0. 48" secondary
Nominal fequeney am) eon,
‘omizal cute som) 5 A secondary
Line Length 100 miles
‘This example demonstrates setting OSB function. Use this logic to
discriminate between power swings and faults to prevent unwanted distance
clement trips. This application example assumes that you have sot the phase-
to-phase mho distance element Zone 2 reach, First, enable the OOS logic.
‘Next. calculate the impedance reach settings for Zones 6 and 7 (RARS, RIR7,
XIT6, and X1T7), and then calculate OSBD (out-of-step block time delay)
‘Al of the OOS settings appear in Table 1.33 a
example,
Table 1.34 atthe end of this
Enable 00S Logic
NOTE: thereiay astorstiay
{alelates and aides setings when
You set EADVS toh and EOOST tO,
Thiet dalte mere stings
Date Coce 201601
‘Access Group settings to enable the out-of:step logic.
Eos = ¥ Outof-Step (¥.N)
You do not need to enable the Advanced Settings for this application example
EADVS = W Advanced Settings (¥, N)
Out-of Step Tripping
Disable the OST logic for this particular application example
£00ST:-W Out-of-Step Tripping (N, I, 0)
Phase Distance Element Blocking
‘OSB logic blocks phase distance protection during a swing when the
measured postive-sequence impedance enters the operating characteristics of
the phase distance elements (see Zone 1 and Zone 2 in Figure 1.29). In
practice, it is not necessary to block al zones. In this application example, the
‘OSB logic blocks zones that generate instantaneous tripping. The OSB logic
blocks instantaneous Zone 1 and Zone 2 (Zone 2 is patt ofthe
ccomumunications-assisted tipping scheme).
‘The OSB logic typically supervises forward-looking Zones 1 and 2 because
the operation time of these two zones is ordinarily shorter than the time period
‘during which the impedance of a power swing resides in these protection
zones. For example, ifthe period of a swing is 1.5 seconds, OSB logic should
supervise instantaneous Zone 1 and communications-assisted Zone 2.
During a power swing, the relay typically does not block overreaching zones
‘of protection that provide time-delayed tipping. Do not block reverse-looking
‘Zone 3 when this zone serves as a starting element for the DCB (directional
Acplications Handbook SEL-A2-4 5 RelayALMA | Protection Applicaton Example
Out-of-tep Logie Application Examples
‘comparison blocking) scheme or when this zone provides current reversal
‘guard for the POT (permissive overreaching transfer tripping) scheme. For
‘example if the OSB logic inhibits the DCB blocking signal during swings that
pass behind the local relay over-tipping can occur atthe remote terminal. Ifa
power swing enters both the local reverse-looking Zone 3 and the remote
‘overreaching Zone 2, high-speed tipping occurs atthe remote terminal
because OSB logic removes the local Zone 3 element DCB scheme block
‘Set the relay to block Zone 1 and Zone 2.
(00581:=¥ Block Zone I (¥. N)
00582 =¥ Block Zone 2 (¥, N)
00883 -=W Block Zone 3 (Y, N)
n
Rr
2 Tele 0-Y inipum
Load
Impedance
ar Cexport)
rr
Figure 1.29 00S Characteristie Settings Parameters
Zone 6 and Zone 7 Impedance Settings
‘The OOS logic uses two zones of concenttic polygons, outer Zone 7 and inner
Zone 6 (see Figure 1.29). The relay uses Zone 6 and Zone 7 for OOS logic
timing to differeniate between power swings and faults. The relay measures a
traveling positive-sequence impedance locus (Z,) in Zone 6 and Zone 7 when
4 power swing or fault occurs. Two factors affect the Zone 6 and Zone 7
impedance stings:
> The outermost overreaching zone of phase distance protection
that you want to block,
> The load impedance that the relay measures during maximum
load (minimum load impedance locus)
SeL-2h4,-$ Relay Applications Hendbook Date Code 201601"NOTE: thie sttnge anieroony
provides meron there
Eeecewretner 9 aut oF Dower
Date Coce 201601
Protection Application Examples
tep Logie Application Examples
Setinner Zone 6 (X1T6, RIR6, X1B6, and RLS) to encompass the outermost
zone of phase distance protection that you have selected for out-of step
blocking. Set Zone 7 so thatthe closest minimum load impedance locus is
‘outside the Zone 7 characteristic for all loading conditions
Resistance Blinders
“Zone 2is the outermost characteristic for this particular example. Include a
safety margin (20 percent for this example).
RIR6 = 12+ —_2MP__
> sia(ZIANG)
12+ 9.609
2+ sin(87.6°)
=5779 ation 1.69
where:
‘Z2MP = Zone 2 mho phase distance element reach (see
Table 1.32),
RR6:=5.77 Zone 6 Resistance—Right (0,05-70 Qsecondary)
Set Zone 7 outer resistance blinders according to maximum load, In other
‘words, set the Zone 7 outer right-hand resistance blinder just inside the
corresponding minimum export load impedance locus (maximum load locus)
‘The maximum load current is 2.41 A secondary, determined from load studies
‘The corresponding line-to-neutral voltage during maximum load at Station $
4s 61.44 V secondary.
Tuga = 241A
Vin = 6144
Determine the minimum load impedance thatthe relay measures:
Z,
Equation 170
‘Assume that the maximum load angle is 445° . Use trigonometry to calculate
RIR7, which is the distance from the origin tothe right-hand resistance
blinder along line OP, the c side of the right triangle (see Figure 1.30). The
resistance blinders are parallel othe ine characteristic impedance Zi, fr
Which the angle is seting Z1ANG,
cos(A) = £
Wea Equation 171
where
A= 45° + (90°-ZZ1ANG)
b= Zaina
= setting RIRT
ications Handbook SEL-A2-4 5 RelayALMG | Protection Applicaton Examples
Out-of-tep Logie Application Examples
fun) oad Impedance
Figure 1.30 calculating Setting RIR7
Rearrange Equation 1.71 and multiply by a safety factor of 90 percent to
caleulate RAR.
RIRT = 0.9 Zc cag) * 608(A)
0.9* Z cain)? C0814" + (90° -Z1ANG)]
0.9+ 2549+ cos[45* + (90° ~ 87.6" )]
0.9+ 25.49+ cos(47.4*)
= 1553.0 Equation 172
ART =15.53 Zone 7 Resistance—Right (0.05-70 (2secondary)
Reactance Lines
Zone 6 inner reactance lines XIT@ and X1B6 should completely encompass
the outermost zone of phase distance protection that you want to block from
‘tipping during a power swing. Include a safety margin (20 percent)
XIT6 = 1.2 Z2MP
12+ 9.60.
52.9 Equation 173
where:
‘Z2MP = Zone 2:mho phase distance element reach
XiT6== 1152 Zone 6 Reactance—Top (0.05-96 secondary)
SeL-2h4,-$ Relay ations Hendbook Date Code 201601"Protection Apoliatian ramples | AIT
‘ut-of-Step Logic Application Examples
‘The distance between Zones 6 and 7 top reactance lines should equal the
distance between Zones 6 and 7 right-hand resistance blinders.
NOTE! the vue
A117 mute a xi?
me X176-+ (RIRI-RIRG)
11.52 Q+ (15.53 2-5.76 9
= 21299 Equation 174
NIT =2129 Zone 7 Reactance—Top (0.05-96 Qsecondary)
Out-of-Step Block Time Delay
‘When the Z impedance locus intially moves inside Zone 7, the relay starts
the OSBD (out-of step block time delay) timer. The Z, impedance trajectory
is shown in Figure 1.31 forthe case of [4|= [Ea| (isthe voltage at Node A
and Eis the voltage at Node B). The OSBD timer detects slow swings. Ifthe
OSBD timer expires before the Z, trajectory enters Zone 6, the relay detects a
power swing blocking condition.
i
Minimum Load
Inpadance
Figure 1.31 Swing Trajectory to Determine the OSBD Setting
Use Equation 1.75 through Equation 1.78 to calculate the OSBD setting
‘These equations are derived from the impedance trajectory shown in
Figure 1-31. Line section AB isthe transfer impedance, Z; The horizontal
dashed line represents the trajectory of the power swing perpendicular to line
section AB. The trajectory passes through the midpoint of line section AB.
si *Zie
Equation 175
where:
2 = transfer impedance
Zls = positive-sequence source impedance
Zi, = positive-sequence impedance for Line 1
Zl = positive-sequence remote impedance
Date Coce 201601 Acplications Handbook SEL-A2-4 5 Relay[AA | Protcton applet
amples
Out-of-tep Logie Application Examples
SeL-2h4,-$ Relay
al
= 2+ aan] 3
RRS
2
77a
8 2288° ——
2+ atan|
1209° Equation 1.76
Ang R’
2
1533
— ——
2+ atanl
= 66.4" Equation 177
Atypical stable swing frequency is f jyp = 5 Hz. Use this value in
Equation 1.78 find setting OSBD.
(Ang_R6~Ang_R7)* fyom
OsBD = cycles
SBD 7 vel
cycle” fair
658°) + 601 0 eg
360" SS He %
eyeh
82 cycles Equation 178
where
J som = nominal power system frequency (Hl)
5 ap = maximum slip frequency (Hi)
‘The OSBD timer settings are in increments of 0.125 cycle; round up to the
nearest valid relay setting.
0580 = 1.875 Out-of-Step Block Time Delay (0.500-8000 cycles)
Latch Out-of-Step Blocking
“The SEL.-£21 automatically resets the OSB logic if this logic asserts for more
than two seconds while the positive-sequence impedance locus is inside
Zone 7. During an unstable power swing, the relay also resets the OSB logic
‘ach time the swing impedance exits Zone 7. You can latch on the OSB
function during an unstable power swing to continue blocking the distance
«lements if the power swing impedance locus moves outside of Zone 7 and
before it comes back inside Zone 7 on its next swing cycle. Iflatched, the
‘OSB logic resets one second after the power system stops the out-of-step,
Latching the OSB gives you an advantage in tat the relay can successfully
block uncontrolled distance element operations if a fault occurs when the
unstable swing impedance is outside of Zone 7. Relay elements detect internal
faults that occur during a power swing and take the appropriate action
(unblock),
OssiTCH = ¥ Latch Out-o
Step Blocking CY, N)
Applications Hendbook Date Code 201601"Date Coce 201601
Protection Application Examples
‘ut-of-Step Logic Application Examples
Out-of-Step Unblocking
‘The relay disables out-of-step blocking automatically when a fault occurs
during a power swing. Therefore, the distance protection successfully detects
all fall types and tips the circuit breaker(s) during internal faults
Out-of-Step Unblocking During Three-Phase Faults. ‘he trajectories
‘of a three-phase fault and a power swing appear the same to phase distance
clements because both a three-phase fault and a power swing consist of
positive-sequence quantities only (Vj and I,). Therefore, if a power swing
evolves into an internal three-phase fault, typical OSB logic cannot detect the
‘occurence of the balanced fault, The SEL-421 includes an additional set of
inner blinders to provide proper detection of the internal three-phase fault (see
Figure 1.32). Wthe positive-sequence impedance resides between these
blinders for a specific duration, OSB logic unblocks. The relay calculates this
duration (UBOSBD) each time the power swing enters Zone 7. A short timer
setting is adequate for fast swings, but the relay needs a longer timer setting
for slow power swings. For example, ifthe positive-sequence impedance
passes gradually between the two inner blinders during a slow swing, a short
timer setting would cause unwanted tripping
"
THY cone 2
ete Right
3 Binder
Acplications Handbook SEL-A2-4 5 Relay‘A120 | Protection aplication Exempl
Out-of-tep Logie Application Examples
SeL-2h4,-$ Relay
‘The UBOSBD timer length is the expected duration ofthe power swing within
the inner blinders. The relay bases the calculation on the actual time required
for the swing to traverse from Zone 7 to Zone 6, before entering the inner
blinders. I the swing remains inside the inner blinders for a period greater
than UBOSBD, an unblock signal asserts
‘You can increase the adaptive UBOSBD timer calculation in multiples of
setting UBOSBE. If UBOSBF is a multiplier of one, the relay calculates the
‘expected time to traverse across the inner blinders based on the rate at which
the swing moved from Zone 7 to Zone 6. Similarly, if UBOSBF is a multiplier
of four, the relay multiplies UBOSBD by fou,
Out-of-Step Unblocking During Unbalanced Faults. The SEL-421
tueals Zone 1 phase and ground distance elements differently than phase
distance elements of other zones
Operation of either of two negative-sequence directional elements, 67QUBF
(forward-looking), or 67QUBR (reverse-looking), defeats the OSB logic and
"unblocks the phase distance elements (except the Zone 1 elements) when an
unbalanced fault occurs following a power swing. Therefore, the phase
distance protection operates in the POT scheme and high-speed clears the
‘unbalanced fault ifitis an internal one. The time-delayed elements of
associated zones also start timing to initiate backup protection functions. The
67QUBF element unblocks forward-looking zones and 67QUBR unblocks
reverse-looking zones.
‘The relay supervises the 67QUBF and 67QUBR clements with negative-
sequence pickup setting 50QUBP. When you set the 50QUBP pickup level to
other than OFF, the level of negative sequence current exceeds the SOQUBP
Setting threshold, andthe relay has made a valid directional decision
(52 elements), the relay asset either the 67QUBE or the 67QUBR dlectional
clement after time delay setting UBD. In this manner the relay removes out-
‘of-tep blocking for phase distance elements other than Zone 1 elements
during unbalanced faults
‘The SOQUBP setting is an advanced setting and must be coordinated with the
distance protection for the protected line, Setting UBD is also an advanced
setting: set the UBD timer to coordinate clearing times with protection
‘external to the protected ine,
For out-of-step unblocking on unbalanced faults you must do the following:
Step 1, Set EADVS := ¥ to enable advanced settings.
Step 2. Set the negative sequence unblocking element pickup with
setting SOQUBP (Negative-Sequence Current Supervision)
Coordinate with line distance protection,
Step 3. Set the unblock delay timer UBD (Negative-Sequence Current
Unblock Delay)
Coordinate clearing times with other protection
fa power swing center is on the line under protection, the Zone 1 distance
elements at one or both terminals may operate if the OSB is removed. For
‘example. during an unstable swing, if an external A-phase ground fault occurs
beyond the remote terminal R in Figure 1.28, the A-phase ground distance
elements at both terminals operate correctly; that is, A-phase distance element
picks up in Zone 2 atthe S terminal, and in reverse Zone 3 at the R terminal,
However, all Zone 1 phase and ground distance elements at both terminals
‘ay also operate ifthe swing center is within the Zone 1 reach and a negative-
Applications Hendbook Date Code 201601"Protection Apoliatian ramples | A121
‘ut-of-Step Logic Application Examples
sequence overcurrent element removes the OSB. The undesirable operations
‘of Zone 1 clements may trip all three phases at both terminals for an external
Acphase fault
‘The SEL-421 uses a directional negative-sequence element (6791T) to
supervise the out-of-step blocking of Zone 1 distance elements. 67Q1T is
independent from 67QUBF and 67QUBR, which are used to defeat the OSB
for distance elements other than Zone 1 elements, This separation gives you a
choice to control the Zone 1 element operations during an unstable swing
situation.
For those applications that allow the relay to operate for any internal and
‘external faulls on a system during a power swing, set the 67Q1T element
similar to the 67QUBF element:
S001? same value as of SOQUBP Level 1 Pickup (OFF. 0.25-100 Amps
sec.)
‘67010 ~ same value as of UBD Level 1 Time Delay (0.000-16000 cycles)
s10HIC =1 Level 1 Torque Control (SELocic Equation)
For those applications that requite the relay only trip for internal faults during
power swing, disable the 67QIT element by setting 50QIP to OFF or E50Q
=N. This way, the Zone 1 distance elements are always blocked by the OSB
logic. The relay relies on Zone 2 overreaching elements together with the
POTT scheme to make high-speed trips for internal faults.
Example Completed
This completes the application example that describes setting the SEL-421 for
cout-of-step blocking. Analyze your particular power system to determine the
appropriate setings for your application,
Relay Settings
Table 1.33 lists the settings that the relay automatically calculates and hides
when you sot EADVS to N and EOOST to N.
‘Table 133 Automatically Calculated/Hidden Settings
‘setting Default Setting
XIBT | Zone TReactance—Baviom 0050-96 secondary) | XUBT = -XITT
XIB6 | Zone 6 Reatance Bottom (0.05 19-86 secondary) | XIBE = -XITS
RIL7 | Zone 7 Resistance —Left -0.05 to-70 Qsecondary) | RII? = -RIR7
RILs | Zone 6 Resistance —Left (0.05 to 70 secondary) | RIL = -RIRE
OSTD | OutoF Step Trp Delay (0500-8000 cycles) 0.500
SoABCP | Posiive-Sequence Curent Supervision SOABCP 0.2 Ion
(00-100 A secondary)
SOQUBP | Negative-Sequence Curent Supervision our
(OFF, 050-100 A secondary)
usp | Negative-Sequence Current Unblock Delay 0.500
(0.300-120 eyees)
uBosBF | Outof Step Angle Unblock Rate (1-10) 4
Table 1.34 and Table 1.35 list the protective relay settings available in this
example.
Date Coce 201601 ications Handbook SEL-A2-4 5 Relay‘A122 | Protection Application Examples
Out-of-tep Logie Application Examples
Table 134. Relay Configuration (Group)
Setting Description Entry
OOS ‘Ourof Step VVEW) Y
EADVS Advanced Settings (YN) N
Table 135 Out-of-Step Tripping/Blocking
‘Setting _| Description Entry
‘O0sBI | Block Zonet WN) Y
osne | Block Zone 2(¥, N) y
oosns | Block Zone 2 (¥, ) N
OSBD | Ou-of Step Block Time Delay (0500-8000 cyeles) 1875
OspETCH | Latch Oucof-Sep Blocking (Y, N) y
Oost | Out-ofStep Tipping (W. 1.0) N
xIT? Zone 7 Reacance—Top (0.05 to 96M secondary) 2129
XITS Zone 6 Reactance—Top (0.05 to 96 secondary) 1182
RIRT Zone 7 Resistance—Right (0.05 to T0 secondary) 1353
RIRe Zone § Resistance —Right (0,05 to 70 secondary) sm
xIBy Zone 7 Reactance—Battom (-0.05%0-96 Aecondary) | -21.29,
XIB6 Zone 6 Reactance—Bottom (-0.05 (0-96 Qsecondary) | -11.52
RALy Zone 7 Resistance—Leh (-0.05 to -70 Gsecondary) “15.58
RILS “one Resistance —Let (-0.05 to -70 Asecondary) “3
SOABCP | Positive-Sequence Current Supervision 1.00
(.00-100 A secondary)
SOQUEP | Negative-Sequence Curent Supervision oF
(OFF, 050-100 A secondary)
usp [Negative-Sequence Current Unblock Delay 0.00
(0300-120 eyeles)
UBOSBF | Ou-ofStep Angle Unblock Rate (1-10) 4
soqiP | Level Pickup (OFF, 025-100 Amps sec) oF
67Q1D__| Level 1 Time Delay (0.000-16000 cycles) 0.000
67Q1Tc _| Level 1 Torque Contol (SELOGIe Equation) 1
Out-of-Step Tripping ‘This example demonstrates how to set the OST (out-of-stp tripping) function,
Use OST logic to detect an unstable power swing and trip the local terminal.
‘With OST logic, you can spit the power system at predetermined locations
after an OST condition occurs.
“The Zone 6 and Zone 7 settings for the OST logic depend on the positive
sequence impedance (Z,) trajectory of the power swing (see Figure 1.33). Set
inner Zone 6 at the point along the trajectory where the power system cannot
regain stability. Set Zone 7 so thatthe impedance because of maximum load
conditions is outside the Zone 7 characteristic for all loading conditions.
SeL-2h4,-$ Relay ations Hendbook Date Code 201601"Protection Appliation Examples | A123
‘ut-of-Step Logic Application Examples
NOTE: this setting phiesophy
Droid: ne moss ene ortho a
Sccceireterin poner
= = imum Load
impecence
Figure 1.33. OST Characteristics
‘To conligure the OOS logic for out-of-step tripping, enable the OOS logic.
‘Next, calculate the impedance reach settings for Zones 6 and 7 (RIRS, RIRT,
XIT6, and X1T7), and then calculate OSTD (out-of sep tip delay) and
‘OSBD (out-of-step block time delay). All of the OOS settings appear in
Table 1,37 and Table 1.38.
Enable 00S Logic
Access Group seltings to enable the out-of-step logic.
£005: ¥ Outof-Step (¥, N)
OTE: ravens thesetings | You do not need to enable the Advanced Settings for this application example
[hanlaes wen oust! EADVSUON EADVS = Advanced Settings (¥, N)
Date Coce 201601
Out-of-Step Tripping
‘When the positive-sequence impedance locus enters Zone 7, both OOS logic
timers (OSBD and OSTD) start (see Figure /.33). If OSTD expires before
‘OSBD and Zone 6 asserts, the relay declares an out-of step tipping condition.
able the relay to trip when Zone 6 drops out (Trip-On-the-Way-Out) See
Out-of Step Tripping and Blocking for OSTD and OSBD caleulations.
[00ST:=0 Out-of-Step Tripping (N, 1, 0)
where:
able out-of sep tripping (Trip-On-the-Way-In)
0 = Enable out-of-sep tripping (Thip-On-the-Way-Out)
N= Disable out-of step tripping
Phase Distance Element Blocking
Enable the OSB function to prevent tripping when the positive-sequence
impedance locus enters the Zone 1 and Zone 2 distance protection
‘characteristics during an unstable power swing. Therefore, in this application
Acplications Handbook SEL-A2-4 5 Relay‘A124 | Protection pplication Examples
Out-of-tep Logie Application Examples
cxample, the relay trips after the Z, impedance locus exits Zone 6 (Zone 6