Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

R

Every generator set is subjected to a comprehensive test


program which includes 50% load, 75% load, 100% load, 110%
load and the checking and proving of all control and safety shut-
down functions.
Equipped with two 12V high performance maintenance-free lead-
acid starting batteries, famous brand MCCB circuit breaker and
connecting with cables.
Equipped with 8 hours operation base fuel tank.
Each genset with operation manual and test report.
Designed to comply with ISO8528/GB2820.

Powered by Perkins engine and coupled with Stamford alternator.

Prime power 26kVA


Standby power 29 kVA
Rated speed 1500 RPM
Output frequency 50 Hz
Phase 3
Rated voltage 400 V
Engine model 404D-22G
Alternator model PI144E
Fuel consumption of 100% load 5.3 Litres/h
Fuel consumption of 75% load 4.0 Litres/h
Voltage regulation rate 1%
Length(L) mm 1620 Random voltage variation 1%
Width(W) mm 600 Frequency regulation rate 5%
Height(H) mm Random frequency variation 0.5%
1333
Weight kg 550 Prime Power:
Tank capacity L 90 This rating is for the supply of continuous electrical power
(at variable load). There is no limit on the annual hours of
operation and 10% overload power can be supplied for 1
hour in 12.
Standby power:
Environment temperature 50 This rating is for the supply of continuous electrical power
Relative humidity % 90 (at variable load) in the event of a utility power failure.
Altitude m 1000 No overload is permitted.
Rated voltage:
Available with customer requirements.

Page: 1/3
R

Engine model 404D-22G


Engine manufacturer Perkins
EU2007 (EU 97/68/EC Stage II)
Emissions statement
EPA Tier 4Final (EPA 40 CFR Part 1039 Tier 4)
Number of cylinders 4
Cylinder arrangement Vertical in-line
Cycle Four stroke
Aspiration Natural Aspiration
Bore Stroke (mm mm) 84 x 100
Displacement (Liter) 2.216
Compression Ratio 23.3:1
Prime power/speed (kW/RPM) 18.4/1500
Standby power/speed (kW/RPM) 20.3/1500
Speed governor Mechanical
Cooling system Forced Water Cooling Cycle
Total lubrication system capacity(L) 10.6
Coolant capacity L 7.0
Fuel consumption at 100% load (g/kWh) 237 (at 1500RPM)
Starter motor DC12V
Alternator AC12V

Alternator model PI144E


Alternator manufacturer Stamford
Exciter type Single bearing, Brushless, Self-excited
Rated output prime power 25 kVA
Rated speed 1500 RPM
Rated frequency 50 Hz
Phase 3
Rated voltage 400 V(Available with customer requirements)
Power factor 0.8
Voltage adjust range 5%
Voltage regulation NL-FL 1%
Insulation grade H
Protection grade IP23

Remark
Alternator option:
Other alternator manufacturer: Lisite, Leroy Somer, Marathon and Mecc Alte.

Page: 2/3
R

DEEPSEA COMAP HARSEN MONICON SMARTGEN

Page: 3/3