Professional Documents
Culture Documents
EGP3-03.02 Instrumentation, Control Valve Stations and Instrument Air
EGP3-03.02 Instrumentation, Control Valve Stations and Instrument Air
: EGP3-00-SP-032-605-001
Notes
i.) Revisions numbers shall be A, B, C, etc. up through the issue for Invitation to Bid.
iii.) Revisions after the issue for Invitation to Bid shall be 1, 2, 3, etc. Any revisions made after
Revision 0 shall be denoted by a vertical line in the left hand margin against the revised text.
iv.) A brief description of the key changes made in each revision shall be included on this page.
PAGE
1.1 Scope 5
1.2 Definitions 5
2.0 REFERENCES 6
3.3 Strainers 7
3.5 Rotameters 8
4.2 Piping 11
5.2 Material 14
5.4 Arrangement 14
5.5 Supports 15
5.9 Fabrication 15
1.1 Scope
This specification, in addition to the "Piping - Valves, Material and Service
Classification Specification 3.00," covers the minimum technical requirements
for the design, manufacture, and testing of instrument and control valve
stations.
1.2 Definitions
Definitions used in this specification are as follows:
c. Control valve stations include the required piping, block valves, bypass
valves, drains, and necessary supports required for installation of the
following types of proportioning control valves.
● Diaphragm-operated
● Motor-operated
● Piston-operated
● Hand-operated
The following documents are hereby referenced and are considered part of this
specification:
b. Connections and block valve inlets shall be at least 3/4-inch pipe size except
that connections to orifice flanges may be 1/2-inch pipe size.
● Mounted between (900mm) and (1700mm) above the level of the deck
c. Meter piping shall be installed so that air in the line will be purged
automatically and so that any condensate will drain into the meter run.
3.3 Strainers
a. Y-type strainers shall be installed upstream of all positive displacement
meters.
d. Strainers for turbine meters shall pass no particles larger than one half
the distance between the tip of the rotor and the bore of the meter.
3.4.1 Valves
3.5 Rotameters
a. Rotameters shall be mounted in locations that are as free of vibration as
possible.
● Gas service
● If backflow is possible
d. Floats for internal level control instruments shall be mounted so that the
bottom of the float is at least 3 inches (76mm) off the bottom in horizontal
vessels and 18 inches (457mm) off the bottom in vertical vessels.
3.6.1 Connections
3.6.2 Standpipes
d. Stations shall be supported on the operating platform with base ells and
other similar items.
e. If a bypass for manual control is provided for a control valve station, the
controlled-variable indicator shall be readable from the station.
f. A drain valve shall be located on the piping between each block valve
and the control valve or instrument in liquid or vapor service if the control
valve is failed closed. For failed open control valves a drain shall be
placed on the upstream side only.
g. Sufficient flexibility shall be built into the control valve station to permit
replacement of the valve without damage to gaskets. For this reason, an
elbow located in a removable spool installed between a block valve and
a control valve is required see Figure 1.
4.2 Piping
a. Piping shall be self-supporting when the control valve or instrument is
removed for maintenance.
b. Equipment shall not have block and bypass valves if the following
conditions apply:
c. The capacity of bypass lines and bypass valves shall be at least equal to
the calculated or required liquid sizing coefficient (Cv) of the control
valve, but not greater than twice the Cv of the control valve.
d. The minimum size for block and bypass valves is presented in Table 1.
f. Bypass valves shall be of the globe for bypass valves larger than 4 inch,
company may approve use of gate valves.
● If the valve requires bottom access, valves 4 inches or larger in size shall be
located a minimum of (600mm) above the deck or operating platform.
5.2 Material
Instrument air piping materials shall comply with the requirements of piping
material classification A15.
3/4 10
1 25
1 1/2 80
2 150
e. The minimum size for supply lines to individual instruments shall be 1/2-
inch pipe.
f. Instrument piping from the shutoff valve to the instrument normally shall
be 3/8-inch outside diameter (OD) tubing. The tubing for large
pneumatic actuators shall be 1/2-inch OD.
5.4 Arrangement
a. Instrument tubing or piping shall be run overhead in raceways, on pipe
racks, or otherwise supported in order to provide a neat, plumb, level,
vibration-free installation. Routing of the instrument air piping shall be
approved in writing by the Company.
e. Low points in the main header and the subheaders shall be supplied with
3/4-inch valves. Valve end connections shall be threaded and shall have
plugs.
5.5 Supports
See EGP3-03-04 (13.0) piping layout, support and flexibility for support criteria.
As a minimum, supports shall be provided at (6m) 20-foot intervals.
c. If a single takeoff from the main supply header serves more than one
instrument, each line to the individual instruments shall have a separate
ball valve.
b. Each air line takeoff on the header shall be isolated with ball valves.
c. Instrument supply lines shall terminate with shutoff valves located not
more than (900mm) 36 inches from the instrument.
5.9 Fabrication
a. Pipe shall be fabricated so that no butt welds are in direct contact with
January, 2004 Specification No. EGP3-03.02 Page 15 of 20
structural steel pipe supports.
a. Block and bypass valves shall be tagged with the valve specification number
from the applicable piping class specification.
d. The instrument air piping system shall be identified by a blue color-coded label
in accordance with ANSI A13.1, Scheme for the Identification of piping Systems.
Line Size
1/2 3/4 1 1-1/2 2 3 4 6 8 10 12
Valve Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp Blk Byp
C
o 1-1/2 1-1/2
n 1/2 1/2 1/2 3/4 3/4 1 1 -- -- -- -- -- -- -- -- -- -- -- -- -- --
t
r 1-1/2 1-1/2
o 3/4 -- -- 3/4 3/4 1 1 2 2 -- -- -- -- -- -- -- -- -- -- -- --
l
1-1/2 1-1/2
1 -- -- -- -- 1 1 2 2 2 2 -- -- -- -- -- -- -- -- -- --
V
a 1-1/2 1-1/2
l 1-1/2 -- -- -- -- -- -- 2 2 2 2 3 3 -- -- -- -- -- -- -- --
v
e
2 -- -- -- -- -- -- -- -- 2 2 3 2 3 3 4 4 -- -- -- -- -- --
S
I
z 3 -- -- -- -- -- -- -- -- -- -- 3 3 4 3 4 4 6 6 -- -- -- --
e
4 -- -- -- -- -- -- -- -- -- -- -- -- 4 4 6 4 6 6 8 8 -- --
6 -- -- -- -- -- -- -- -- -- -- -- -- -- -- 6 6 8 6 8 8 10 10
8 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 8 8 10 8 10 10
10 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 10 10 12 10
12 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 12 12