Professional Documents
Culture Documents
Limodor: Ventilation According To DIN 18017-3
Limodor: Ventilation According To DIN 18017-3
com
contents
LIMODOR
2 LIMODOR
contents
DIN 18017-3
1 Area of application, planned minimum exhaust air volume flow
1.1 Area of application 1.3 Planned minimum exhaust air volume flow
DIN 18017-3 applies to ventilation systems with fans for Ventilation systems for the ventilation of bathrooms (with /
the ventilation of bathrooms and toilet rooms without without toilet) can optionally, depending on the design and
outside windows in apartments and similar lounge areas, mode of operation, for the following planned
e.g. residential units in hotels. Other rooms within Minimum exhaust air volume flows [q V] be laid out:
apartments, Table 1.3
e.g. kitchens or storage rooms can also be ventilated
using systems in accordance with this standard. 40 m³ / h The volume flow must be continuously removed
will. 1)
2) The volume flow may be reduced to a daily average of 15 m³ / h during times of low air
DIN 18017-3 assumes that an outside air flow demand (eg at night). This does not apply to kitchens and kitchenettes. Intermittent
corresponding to the exhaust air volume flow can flow operation with a maximum fan downtime of 1 hour is permitted.
into the exhaust air rooms via the leaks (infiltration) in the
3) With normal use of a bathroom (e.g. without additional laundry drying) or a toilet
building envelope and / or outside air outlets via the room, the exhaust air volume flow may be reduced to 0 m³ / h during times of low air
apartment / common rooms. demand if the building meets a thermal insulation standard of at least the
requirements of the 1995 Thermal Insulation Ordinance or better. Each time the
ventilation unit is switched off, a further 15 m³ of air must be discharged.
LIMODOR 3
contents
DIN 18017-3
2 Disturbance pressure in single-pipe ventilation systems
2.1 Influence of disturbance pressure 2.3 Disturbance pressure in individual ventilation systems
The exhaust air volume flows must not change by more Evidence must be provided that the planned volume
than ± 15% compared to the planned volume flows due flows only change within the permissible limits as a
to wind and thermal lift. result of back pressures.
In the case of ventilation systems with a common main
line, the mutual influence of the ventilation devices must
When planning a system, it is to be expected that the also be taken into account.
differences in static pressures between the ventilated Proof is necessary to ensure a sufficient cross-section of
rooms and the outside of the outlet openings the main line.
(interference pressures) will increase or decrease by 40
Pa. If the exhaust air is not routed perpendicularly, the The change in volume flow as a result of back pressures
disturbance pressure is 60 Pa. can be checked with sufficient accuracy using the
characteristic curve of a single complete ventilation device
with connection line. The characteristic curve of the
complete ventilation unit, including its connection line to
the main line, must be applied. The pressure drop in the
common main line when operating a device is neglected.
Picture 2.3
Exhaust air volume flow
perpendicular to the roof,
Disturbance pressure = 40 Pa 1
Picture 2.1.1
pd
Exhaust air volume flow
not perpendicular,
Disturbance pressure = 60 Pa
2 Vd
p
V Vf
1 Total pressure characteristic of the ventilation unit including the
connection line
2 Total pressure characteristic of the system,
Vf Volume flow of the ventilation device blowing out freely from the
connection line
Picture 2.1.2
4th LIMODOR
contents
DIN 18017-3
3 Flow rate deviation with a common main line
3.1 Calculation of the static pressure drop 3.2 Volume flow reductions with simultaneous
operation of single-pipe ventilation units
The reduction in volume flow at the lowest
ventilation unit can be determined with sufficient The reduction in volume flow through simultaneous
accuracy using an equation by calculating the static operation of all ventilation units is greatest at the
pressure drop in the main line when all units are in lowest ventilation unit.
operation and the same characteristic curve of one
ventilation unit. The relevant total volume flow V v, m total when operating all
devices is less than the sum of
If the reduction in volume flow is within the permissible Volume flows of the ventilation units blowing out freely.
range, the main line is sufficiently large. The reduction factor is around 0.93. The relevant total
volume flow is:
Equation 3.2
The static pressure loss Δp s [ Pa] in the main line from
the connection of the lowest ventilation unit V v, m total = 0.93 • n 2 • V f
up to the mouth can be calculated with sufficient
n2 Number of connected ventilation units
accuracy using the following equation:
Vf Volume flow of the ventilation unit blowing out freely from the connection
Equation 3.1 line in m 3 / H
R. A. Pressure drop per m in the discharge line with the relevant total volume flow in
Pa / m
1
n1 Number of floors
l S. Length of the main line between 2 device connections in m Length of
l A. the discharge line in m
p there dynamic pressure in the discharge line at the relevant total volume flow in Pa ps
For diagrams for determining This can be used for p s Disturbance pressure difference
the pipe cross-section, see planning and design V s Volume flow reduction at the lowest ventilation unit with the same
timely operation of all ventilation devices
section - Dimensioning free software
Vf Volume flow of the ventilation device blowing out freely from the
from L do gsle iteration en-. program Limodor- connection line
professional
demands are made.
9 9
Number of floors
8th 8th
7th 7th
5 5
LI M. OT
44 97 1
4th 4th
31 - 9
G m
bra
0) 79
&
9(
C. O.
3 3
4
: +
LIIM
L. MOODDOORR.
K
ax
G
•F
Lü
0
ft
U.
h49
N
4t
gs
Media library
9
te
1-
2 2
ch
1 1
Pipe-
100 125 140 160 Pipe-
nominal nominal
expanse expanse
LIMODOR 5
contents
DIN 18017-3
4 Post-flow of outside air
unit can also be determined on the basis of DIN 1946-6 The number of necessary outer wall air passages
be telt. Details on this can be found in the standard. let ( n in the building envelope can be determined using
ALD)
2) Table 4.5) Minimum free area A ÜLD of overflow air outlets (ÜLD) 1)
Permissible limit value according to EnEV 2007, (n 50 < 3.0 1 / h)
Usable area 1) in m² 30 50 70 90 110 130 150 170 190 65
Overflow air volume flow
1-storey NE with shaft 22 36 50 79 93 108 122 136 70 85 101 40 50 60 70 80 90 100 100 125 150
q v, ÜLD in m³ / h
1-storey NE without shaft 23 39 54 116 131 147 80 97 115 133
Free area A ÜLD in cm² 175 200 225 250
multi-storey NE 27 44 62 150 168
1) Calculation according to DIN 1946-6
1) Area of the usage unit in m², according to DIN EN 12831
2) Basis of the calculation according to DIN
1946-6: for category A50- n = 1.0 1 / h The design differential pressure must not exceed
for category B - n = 1.550 1 / h 1.5 Pa. For doors without a circumferential seal, an area
differential pressure 8 Pa of 25 cm² is taken into account. If there is no
Room height (medium) 2.5 m single- information from the manufacturer, the free cross-
storey NE, with shaft f effective, comp = 0.65
section of the ÜLD should be at least 150 cm² up to an
single storey NE, without shaft f effective, comp = 0.70
multi-storey NE f effective, comp = 0.80
exhaust air volume flow of max. 60 m³ / h.
6th LIMODOR
contents
DIN 18017-3
5 Requirements for the common exhaust duct
Exhaust air ducts must be tight and stable and in cold The ventilation systems must be constructed and
zone areas (e.g. in unheated basements, attics) operated in such a way that odors and dust cannot be
designed or thermally insulated in such a way that transferred to other user units. If rooms other than
condensate damage cannot occur. Ventilation lines bathrooms and toilets are connected to a ventilation
made of, for example, folded spiral ducts must be system, the transmission of odors and dust to other
protected from aggressive materials such as mortar or rooms must be prevented.
plaster.
An exhaust duct consists of: A non-return valve must be installed in or after each
- the connection lines for the fans and ventilation unit before the connection and main lines are
- the common exhaust air line (main line). connected.
possibly.
A sufficient number of cleaning openings with tight
Warmth- closures must be made in the exhaust air lines so that the
insulation exhaust air lines can be easily cleaned. Screw-in cleaning
The main line must be
caps are not permitted. Cleaning openings are not
straight and perpendicular
necessary if the exhaust air lines can be cleaned from the
and must have a constant
exhaust air openings.
cross-section.
Because of the overpressure in the lines, they must also The roof hood is part of the exhaust pipe and should not
be tight against overpressure. create any additional resistance. Otherwise, the pressure
loss must be taken into account when dimensioning the
It is recommended to use an “air bag” at the lower end of common exhaust air line.
the main line to collect any condensate. A connection to
the drainage system is not necessary.
LIMODOR 7th
contents
DIN 18017-3
6 Fan requirements
The fan curve may only have one working point up to In the case of ventilation systems with exhaust air lines
pressures equal to the planned working pressure plus that deviate from the requirements for the common main
double the disturbance pressure. line (e.g. no vertical design), the exhaust air volume flows
of the fans can be measured.
Picture 6.1
The fans can have several switching levels. At least one 6.5 Leak tightness / function of the non-return valve
switching stage must meet the requirements of the Blow-out
support
minimum exhaust air volume flow according to Table Our spring-loaded
1.3. It must be possible to see whether the fans are in Non-return valves achieve leaks
operation. below 1 l / h on average. The
Fans with only one switching stage are only permitted if requirement of DIN 18017-3
the requirements for meeting the minimum exhaust air with 10 l / h (= 0.01 m³ / h) is far Return
impact
volume flow are met. below. flap
Picture 6.5
The exhaust air must be discharged from the room to be The tightness of the back
ventilated as close as possible to the ceiling. The flap flap is fulfilled by all ventilation devices and in
every installation position (exhaust nozzle on top, side,
rear and bottom).
6.3 Fan for several rooms
In addition to preventing the transmission of odor and
Other rooms in an apartment must not be ventilated dust when the system is at a standstill, the non-return
using the same fan that is used to ventilate the valve also fulfills the requirement criteria for preventing
bathroom and toilet. cold smoke transmission.
8th LIMODOR
contents
DIN 18017-3
7 Ventilation concept, maintenance, kitchenettes
Ventilation systems according to DIN 18017-3 are Other rooms within apartments, e.g. kitchenettes, can
intended for the ventilation of individual rooms. They also be ventilated via ventilation ducts (designed in
can also take over the ventilation of living rooms and accordance with DIN 18017-3). The planned minimum
lounges, if the relevant requirements are met. Details exhaust air volume flow for this type of room is given in
on dimensioning and execution are contained in DIN Table 1.3, information on the dimensioning of the
1946-6. required supply air is given under point 4 (Post-flow of
outside air).
The combination of ventilation of living and common
rooms in connection with the design principles of DIN A kitchenette is always part of a living room.
18017-3 must be agreed with the client. Kitchenettes are permitted if they can be ventilated
independently. This means that a ventilation device
must always be provided if the niche itself is not directly
7.2 Handover / acceptance of a ventilation system assigned a window (see Figure 7.4.1a).
Compliance with the requirements for a ventilation Figure 7.4.1a) Example of an arrangement of a kitchenette
system according to DIN 18017-3 Sections 3 and 4
must be proven and documented by on-site
acceptance.
The acceptance or parts of the acceptance may be Ventilation unit
waived if the suitability is proven in another way. provide
The maintenance of our ventilation devices usually only An internal kitchen can be locked with a door.
includes the replacement of the filters. With regular Volume flow information can be found in the
filter maintenance according to the specifications “Building Regulations Guideline for Ventilation in
in the maintenance and care instructions, the check of Internal Rooms”. When planning ventilation
the non-return valve can be dispensed with. systems, it must be ensured that the air flowing in
must be fed directly into the room.
LIMODOR 9
contents
DIN 18017-3
8 Air / acoustical design of outside air outlets
8.1 Ventilation design of outside air outlets 8.3 Acoustic design of outside air outlets (ALD)
(ALD)
Using equation 4.4 and table 4.5, the required number of The specified requirements for the sound insulation of
outer wall air outlets can be determined. The following is the outer wall and the outer window must not be
a calculation example of a 1-storey user unit (with shaft) impaired by the combination of the supply air device and
without a room-air-dependent fireplace. window.
Exhaust air volume flow, usable : 60 m³ / h The basis for calculating the resulting sound
living space as planned : 70 m² reduction index can be found in DIN 4109,
Living room height (medium) : 2.5 m Supplement 1.
Airtightness value n 50 the NE : 1.5 1 / h (according to EnEV 2007)
Outer wall air outlet design : ALD 100 series When comparing the components (wall / window,
: 8 Pa
pressure difference wall / supply air device), the resulting sound reduction
n ALD = [ q v - q v, inf, act ] / q v, ALD index R 'for the two components is calculated using
thew, R,following equation:
n ALD = [ 60 m³ / h - 33 m³ / h] / 26 m³ / hn res
Equation 8.3
ALD = 1.04 1 piece R. w, R, 1- R. w, R, 2
S.
Figure 8.1) V olumen current characteristic Se rie ALD R' = R ' w, R, 1 - 10lg 1+ 2 10 10 - 1 dB
w, R, res
S. total
8th
Sample calculation
6th
R ' w, R, W = 50 dB (wall) R ' w, R, W = 50 dB (wall)
4th R ' w, R, F = 35 dB (window) = R ' w, R, ALD = 19 dB (ALD)
S. F. 1.5 m² (window) = 10 S. ALD = 0.0180 m² (ALD) =
2
a S. total m² S. total 10 m²
5 10 15th 20th 25th 30th 35
Regulating plate
Volume flow [m³ / h] R ' w, R, res, W / F = 42.5 dB R ' w, R, res, W / ALD = 44.9 dB
8.2 Requirements for outside air outlets In connection with the wall, the ALD has a sound
reduction index that is approx. 2.4 dB (44.9 - 42.5 dB)
DIN 18017-3 does not contain any requirements for the better than the wall / window component.
ALDs. When arranging an ALD in the building envelope,
the following points must be observed in addition to the
statutory provisions (e.g. Energy Saving Ordinance): The resulting sound reduction index of an ALD can be
displayed using graphics.
- The facade composed of ALD / external wall may
comply with the DIN 4109 series of standards Figure 8.2) Example diagram of the resulting sound reduction index
10 LIMODOR
contents
C.
The permitted sound pressure level specifications of DIN A.
4109, Table 4, always refer to rooms in need of
protection in other people's homes. No requirements are
Apartment separating ceiling
specified within your own living area!
D.
Rooms in need of protection are lounges, such as
e.g. living rooms (including floorboards) or bedrooms /
children's rooms in the unfamiliar unit. In these
“protected rooms”, the sound pressure level of other Ventilation unit
building services systems (ventilation systems) must not
exceed 30 dB (A) or 35 dB (A) for continuous noises
E. in operation
For compliance with the sound levels, the following A) Protected living area of the unfamiliar unit, max.permissible
sound pressure level = 30 (35) dB (A)
factors must be taken into account during the planning
phase or the execution of the trades: B) Difference in shaft level
- Floor plan arrangement of the apartments (building acoustics C) Required airborne sound insulation R ' w the apartment
favorable / unfavorable) separating ceiling / shaft wall according to DIN 4109, table 3
- Mass per unit area of the shaft wall (solid / D / E) no requirements (own living area)
lightweight wall)
Figure 9.1.2) Test setup for a shaft level difference measurement
- Airborne sound insulation apartment separating ceiling / wall
= Loudspeaker = Microphone
LIMODOR 11
contents
10.1 General Figure 10.1.1) Installation of ventilation units in the protection area
1 and 2 for showers with a bathtub
The scope of VDE 0100-701 applies to the
installation of electrical systems in rooms that are
used for bathing and / or showering by people.
cm
10.2 Protection areas / classifications Area 0
Area 1
In the case of shower trays or bathtubs, the area is
limited by the edge of the bathtub and the vertical
wall surfaces above the shower or bathtub (see Fig.
1).
Area 1 for showers without The tub is the
225 cm
cylindrical space with a radius of 120 cm from the
center of the fixed water outlet on the wall or
ceiling (see Fig. 2). Area 1 is 225 cm high. r = 120 cm
Area 1
Area 2
(only for shower or bath tubs) Note: Area 0 not set; Area 2 is not applicable
12th LIMODOR
contents
11.1 General according to DIN 18017-3 With visible approval by the DIBt, the shut-off devices
can be used as a building product in the sense of all state
If the ventilation systems are set up according to the building regulations.
requirements of DIN 18017-3, those in the “Model The shut-off devices are given the suffix
Directive on Fire Protection Requirements for Ventilation “-18017” (e.g. K90-18017) after the fire resistance
Systems (M-LüAR)”, Section 7 - “Special provisions for period achieved.
ventilation systems according to DIN 18017-3” apply
Requirements. Details on the use / installation of shut-off devices or
the ventilation system can be found in the building
inspectorate approval. The approval can contain, for
11.2 Legal requirements and regulations for example, the following information:
preventive fire protection in residential
construction - Product description / drawings
- Requirements for the shaft wall / cladding
Legal requirements for preventive fire protection in - Permissible cable cross-sections of the ventilation system
ventilation systems can be found in the following - Installation positions of the shut-off device
regulations / rules: - Maintenance instructions / inspection intervals
- State building regulations; Implementing Ordinance Shut-off devices in accordance with DIN 18017, together
- technical building regulations with the components of a ventilation system, prevent fire
- Building supervision guidelines on fire protection and smoke from spreading when floors are on top of
requirements for ventilation systems each other.
- Ventilation system guidelines (M-LüAR) They are not permitted to prevent fire spreading
within a floor, e.g. bridging an apartment partition
The following statement applies in principle: wall.
“Ventilation systems or installation shafts must be The ventilation devices / shut-off devices can be used in
operationally safe and fire-proof. Ventilation ducts residential buildings, e.g. bathrooms, toilets, ... and in
may be passed through fire-resistant walls or "non-residential buildings", e.g. tea kitchens in offices,
ceilings if fire and smoke cannot be transmitted. " can be used.
3
Figure 11.2) Sectional view of a
LIMODOR shut-off device
When fire protection measures are to be observed series compact-K 2
5
depends on the height of the building. Depending on
6th 1
the federal state, the “building height” is interpreted 4th
differently. As a rule, requirements are placed on the
7th
fire resistance period of installation / ventilation shafts
1 = damper spring, tensioned 2
or ventilation devices / shut-off devices from a height of
= damper blade, stainless steel
6 - 7 m up to the upper floor of the top floor. 3 = fusible link release trigger
direction
4 = non-return valve of the 8th
Ventilation device
5 = end position safety device
11.3 General requirements for shut-off devices
Damper blade
according to DIN 18017 6 = exhaust socket, stainless steel
7 = fire protection jacket 8 =
For shut-off devices according to DIN 18017, compared housing box compact
to fire dampers according to DIN 4102, special
provisions apply with regard to fire testing and system
design.
Approval guidelines and test regulations are laid down LIMODOR ventilation units have a non-return flap (item 4)
by the German Institute for Building Technology (DIBt). that prevents smoke (cold smoke) from being transmitted
By issuing a construction to other user / residential units!
LIMODOR 13
contents
11.4 Fire protection solutions with ventilation The cross-section of the air-carrying (non-combustible)
devices in / outside of classified ventilation / main line must not exceed 1000 cm² = NW 355 mm. The
installation shafts shut-off devices can also be used directly in or on
ventilation shafts without internal ducting.
In the case of ventilation systems for toilets or
bathrooms, shut-off devices with a fire protection
jacket around the installation box, in conjunction with Picture 11.4.3) Wall sleeve
a height offset (H), ensure fire protection. In the event (e.g. aluminum flexible pipe)
Main line Thanks to its simple fire protection solution, the compact-
H = 150 mm K-AP fan series is particularly suitable for renovating old
buildings or for converting thermal lift ventilation. Due to
Direction of flow
With shut-off devices for kitchens or kitchenettes, or with 11.5 Ceiling bulkhead fire protection solutions with
systems in combination with toilets and bathrooms, an ventilation devices in / outside of ventilation /
additional "active shut-off" (e.g. spring-loaded metal flap installation shafts
with fusible link release)
Limodor ceiling bulkheads enable the use of
lock the box. unclassified manhole or pre-wall cladding. The principle
of fire sealing in the ceiling or in the floor and in
Picture 11.4.2)
connection with our ventilation devices prevents the
Ceiling grouting Connection pipe (aluminum flexible pipe) transmission of fire and smoke within the ventilation
system in the event of a fire.
Main line
"Active shut-off Picture 11.4.4)
contraption"
Ceiling grouting Ceiling bulkhead
Kickback
flap
Built-in box Main line
compact-K Connecting pipe
(Aluminum flexible pipe)
14th LIMODOR
contents
Single-pipe ventilation devices must not impair the proper Joint operation requires a safety device or a technical
operation of room air-dependent combustion systems. system measure that ensures that the ventilation system
The requirements for the installation and the supply of or a "quickly switched-off fireplace" may not go into
combustion air to fireplaces are summarized in the state operation or will not continue to be operated if there is a
firing regulations. dangerous negative pressure in the installation room
during the operation of a conventional room air-
dependent fireplace the fire
According to the building inspectorate approval, fans
may be installed and operated in user units with open- site can arise. Safety devices for joint operation
air-dependent fireplaces if the exhaust gas routing is require a general building inspectorate usability
monitored by special safety devices that also switch off
the fans when triggered. proof. In the event of a malfunction, the safety device
must either act on the ventilation system or release a
sufficiently large opening to the outside (controllable
It must be ensured that the operation of the fan does ALD).
not generate a negative pressure greater than 4 Pa in
the user unit. This must be taken into account when In the case of alternating operation, it must be proven
dimensioning and designing the outer wall outlets. in conjunction with the safety device that the fan is or
will be switched off when the fireplace is in operation.
LIMODOR 15th
contents
LIMODOR
LIMOT GmbH & Co. KG
ventilation technology
Lower Wart 13-15
D-97980 Bad Mergentheim
Tel .: (0 79 31) 94 49-0 Fax:
(0 79 31) 94 49-71 e-mail:
info@limot.de
http://www.limot.de Subject to technical and content changes