Professional Documents
Culture Documents
TRF 39905 Test Report
TRF 39905 Test Report
I. EQUIPMENT DETAILS
Make : SHILCHAR TECHNOLOGIES LTD.
Type of cooling : ONAN
Rating : 2700 KVA
HV Volts : 33 kV
LV Volts : 0.380 kV
Frequency : 50Hz
Vector Group : Dyn11
HV rated Current : 47.24 A
LV rated Current : 4102.22 A
Sl. no. : 399/05
Month /Mfg. year : 2021
II. LOCATION & FEEDER NAME : IR-1 / INCOMING-OG STAND ALONE FEEDER
1
DETAILS IR in 60 sec (MΩ) P.I
LV-1 to Earth 750 1.04
2
Applied Volts (V)
1U2V = 1U2W R and r Shorted Condition
OK
4.83= 4.83
1V2W = 1V2V
OK
415 = 415
X. FUNCTIONAL CHECK
For main tank
OTI- Alarm
1 OK
Trip
WTI- Alarm
2 OK
Trip
3 PRV –trip OK
4 DGPT Alarm & trip OK
3
4