Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Record agreed variations below (or attach copy of certificate with list of variations):
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
DESIGN MODULE
Specified standards applied:
Has the correct NSI/BAFE certificate been
NSI Reg
A1 issued within one month of completion of the N/A Yes No A5.1.4
system?
5.2
A2 BS 5839 Category of system specified: 8.2(a)
Category M/L
IQ at least 24 hours
Category P
IQ period of unoccupation + 24 hours up to 72
hours
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
DOCUMENTATION
Are there satisfactory commissioning 39.2(c)
B1 N/A Yes No
records?
Have BS 5839 certificates for design,
B2 installation, commissioning & acceptance Yes No 41.2(a)(b)
been issued? (as applicable)
B3 Is there a record of agreed variations? N/A Yes No 40.2(e)
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
Comments:
INSTALLATION
C1 Are cables of a suitable type? N/A Yes No 26.2(b)(d)(e)
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
CIRCUIT DESIGN
Does the area per loop satisfy the
E1 specified standards (addressable systems N/A Yes No 12.2.2(d)
only)?
Is there adequate short circuit isolation 12.2.2(c)
E2 N/A Yes No
(addressable systems only)?
Is there adequate tolerance to open circuit 12.2.2(c)
E3 N/A Yes No
faults?
Are there at least two sounder circuits (or 12.2.2(j)
E4 N/A Yes No 16.2.1(3i)
a suitable ring circuit with isolators)?
Are circuits monitored adequately?
E5 (e.g. are the correct indications given during Yes No 12.2.1
fault conditions?)
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
Comments:
ZONING
F1 Is the detection/alarm zoning adequate? Yes No 13/14
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
AUTOMATIC DETECTORS
Are the areas in which automatic fire
H1 detection is provided, sufficient for the N/A Yes No 8.2
category of system?
Are the types of detector used 21.2
H2 Yes No
appropriate?
H3 Is detector spacing appropriate? Yes No 22.3
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
P2)?
22.2(d)
H7 voids >800mm? N/A Yes No 22.3(g)
BS5839-1: 2017?
Are the detectors mounted within the 22.3(e)
H18 Yes No
appropriate limits below the ceiling?
Are remote indicator lamps provided where 13.2.5
H19 N/A Yes No
required?
If BS 6266 is specified, are the specific
H20 recommendations for detector type, N/A Yes No BS 6266
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
Comments:
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
Comments:
required)?
K5 Is internal workmanship satisfactory? Yes No
Are batteries for standby power supplies of a 25.4(b)
K6 Yes No
suitable type?
Are batteries marked with date of installation
K7 and can dates be read without disturbing the Yes No 25.4(c)
batteries?
Have the quiescent & alarm currents been 39.2(c21)
K8 Yes No
verified at commissioning?
Have the quiescent & alarm currents been 39.2(c21)
K9 N/A Yes No
verified for additional PSUs?
Is the battery capacity, as installed, 25.4(e)
K10 N/A Yes No
adequate?
Is the wiring to any separate power supply
K11 equipment/battery enclosures of a suitable N/A Yes No 26.2(b)
type?
Are the connections to power supply 12.2.2(l)
K12 N/A Yes No
equipment in separate housings duplicated?
Are PSU/batteries in separate enclosures 12.2.2(l)
K13 N/A Yes No
from the CIE fused at the remote end?
Do batteries connected in parallel give the 12.2.1(d)
K14 N/A Yes No
correct fault indications?
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
Comments:
ANCILLARY SERVICES
Confirm that power is not supplied from
M1 the fire alarm system in the quiescent N/A Yes No 9.2(d)
state?
WORKMANSHIP
Good Satisfactory
What is the standard of workmanship?
Unsatisfactory Poor
Comments:
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)
FSF 350.7
October, 2017
© NSI 2017
Fire detection & fire alarm systems BS 5839-1:2017 compliance checklist
Relevant standard
& clause
(where applicable)