LOAD SCHEDULE / CABLE SIZING / VOLTAGE DR

PROJECT: DAVAO CITY BY PASS CONSTRUCTION PROJECT/ PAC


PANEL NAME: PP-A (SECOND FLOOR)-AC VOLTAGE SYSTE
LOCATI0N: ENGINEER'S OFFICE AND
LIVING QUARTERS ENCLOSU

System
CKT. NO. LOAD DESCRIPTION VA QTY Ø Voltage
(V)
1 1.0 HP, 230V, WACU 966 1 1 230
2 1.0 HP, 230V, WACU 966 1 1 230
3 1.0 HP, 230V, WACU 966 1 1 230
4 1.0 HP, 230V, WACU 966 1 1 230
5 1.0 HP, 230V, WACU 966 1 1 230
6 1.0 HP, 230V, WACU 966 1 1 230
7 1.0 HP, 230V, WACU 966 1 1 230
8 1.0 HP, 230V, WACU 966 1 1 230
9 1.0 HP, 230V, WACU 966 1 1 230
10 1.0 HP, 230V, WACU 966 1 1 230
11 1.0 HP, 230V, WACU 966 1 1 230
12 1.0 HP, 230V, WACU 966 1 1 230
13 1.0 HP, 230V, WACU 966 1 1 230
14 1.0 HP, 230V, WACU 966 1 1 230
15 1.0 HP, 230V, WACU 966 1 1 230
16 1.0 HP, 230V, WACU 966 1 1 230
17 1.0 HP, 230V, WACU 966 1 1 230
18 1.0 HP, 230V, WACU 966 1 1 230
19 1.0 HP, 230V, WACU 966 1 1 230
20 1.0 HP, 230V, WACU 966 1 1 230
TOTAL

Page 1 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
COMPUTATION:

FULL LOAD CURRENT:


= 19.32 X 1000 84 A
1.000 230
FLC = 84 + 0,25 (4.2) = 85.0 85.05 A

CB RATING: = 20 +4.2(19) = 99.80 A

USE: 100 AT /100AF, 2P

CABLE SIZE AMPACITY:


(1.25)4.2 +(19)(4.2) = 85.05 A
SEE ARTICLE 3.10 . CONDUCTORS FOR GENERAL WIRING TABL
85.05 < 101.2 A
USE: 3-30 mm² THW

VOLTAGE DROP CALCULATION:


VD = 35.6 70 85.05
1000 SET/S 30
VD = 4.24

%V = 4.24
230
%V = 3.07 REQUIRES BIGGER SIZE OF CONDUC
USE: 50 mm² TW
FOR SERVICE WIRE:
USE: 2- 50 mm² TW (FIRE PROOF)
FOR GROUND WIRE:
SEE ARTICLE 2.50 . MINIMUM SIZE OF EQUIPMENT GROUND TA
USE: 2- 8.0 mm² TW
FOR CONDUIT SIZING:
SEE APPENDIX C, TABLE C.4 PEC 1, 2017 PAGE 985
USE: 65mmØ IMC

Page 2 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 3 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
TAGE DROP

JECT/ PACKAGE I-2


AGE SYSTEM : 230
230V,
V,1-PHASE
1-PHASE
WIRE : 2W + G
ENCLOSURE : NEMA 1 WITH GROUND TERMINAL

LOAD
RATING
DISTRIBUTION, KVA CIRCUIT BREAKER SIZE
% Full Load
kVA AB Pole MCB Rating AT
Multiplier Current
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
0.966 1.75 2 4.20 7.35 20
19.32
19.32 kVA
100 %
19.32 kVA
84 A

Page 4 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
RING TABLE 3.10.2.6 PEC 1, 2017 PAGE 174

F CONDUCTOR

GROUND TABLE 2.50.6.13, PEC 1, 2017 PAGE 124

Page 5 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 6 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
GROUND WIRE CONDUIT
AT AF mm² Type mmØ Type
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC

MAIN PROTECTION:
MAIN FEEDER SIZE: 1

Page 7 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 8 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 9 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
CABLE AMPACITY
SERVICE W
Full Load
PF DF K L CV %
Current Rating
Multiplier
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5
1 1 35.6 100 4.20 1000 1.25 7.5

100 AT 100 AF MCB


sets - 2 x 50.0 mm² THHN
8.0 mm² TW in 65 MMØ IMC

Page 10 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 11 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 12 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
System
SERVICE WIRE PERMITTED VD VOLTAGE DRO
Voltage Allowable
Voltage
Number mm² Type % Voltage
Drop
Drop
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42
3.5 TW 230 3% 6.9 3.42

Page 13 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 14 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
Page 15 file:///conversion/tmp/activity_task_scratch/538398071.xlsx
VOLTAGE DROP REMARKS
e(V) %V
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK
1.49% OK