Technical Data Sheet for AvK-Alternators FM 7.

3-5

Date: 08/01/14 Customer: Bitte Interessent eingeben!


Project No.: AvK Reference: 1-203-0000032-1
Object data:
Site: Prime Mover:
Application: Stationary Power Plant Manufacturer:
Generator data:
Generator: DIG 140 k/4 L Poles: 4 Standards: IEC 60034
Rated power: 2500 kVA 2000 kWe 2072 kWm
Power factor: 0.80
Power at pf 1,0 2013 kVA 2013 kWe 2072 kWm
Rated voltage: 10 kV
Speed: 1500 1/min
Frequency: 50 Hz Voltage range / frequency range:
Rated current: 144.3 A Zone A according IEC 60034-1 (dU = +/-5%, df = +/-
2%)
Winding pitch: ca. 5/6
Insulation class: Stator: Class F Rotor: Class F Temperature rise: B
Ambient temperature: 40 ° C Environment: Standard environment
Site altitude: 1000 m
Enclosure: IP44 Filter: n.a.
Cooling: IC616 - Air-to-air heat exchanger-fan motor in outer circuit
Coolant: Ambient Air Temperature 40 ° C Temperature Air inlet 55 ° C
Coolant: generator:
Cooling air vol.: 3.5 m³/s Cooling water quantity: n/a
Moment of inertia (I): 185 kgm² Weight: 10300 Kg Losses (environment): 72 KW
Losses (cooling): n/a
Connections and regulators:
Wires: 4 terminals, starpoint connected in terminal box
Operation mode: Parallel with the grid and island mode
Regulators:
Voltage regulator: DECS 100
Electrical data: (acc. IEC)
Efficiencies: 110% 100% 75% 50% 25%
Power factor 0.8 96,35 96,53 96,06 94,92 92,79
Power factor 0.9 96,67 96,83 96,3 95,1 92,91
Power factor 1.0 96,98 97,13 96,54 95,27 93,02

Reactances and time constants


unsaturated saturated unsaturated saturated

xd 1.62 1.46 p.u. xq 0.81 0.79 p.u. Td0' 3.8 s Td0'' 0.06583 s
xd' 0.209 0.209 p.u. xq' 0.81 0.79 p.u. Td' 0.49 s Tq0' 0.8 s
xd'' 0.140 0.127 p.u. xq'' 0.139 0.139 p.u. Td'' 0.04 s Tq0'' 0.46619 s
x2 0.146 0.133 p.u. x0 0.042 0.038 p.u. Ta 0.08 s Tq' 0.8 s
x1s n.a. 0.076 p.u. Tq'' 0.08 s
Short circuit ratio saturated: 0.69 Zn 40.000 Ohm

Short circuit data:


Initial short circuit current (3-phase): Ik'' 1137 A
Max. peak current (3-phase): IS 2894 A
Sustained short circuit current: Ik 433 A Minimum 3 x rated current for
max.10 s
Initial short circuit torque: Mk2 162.9 kNm
Mk3 97.7 kNm
Max. faulty synchron moment: Mf 350.2 kNm
Rated kVA torque: MSN 15.92 kNm
Rated torque MN 12.74 kNm
Shaft torque MSh 13.20 kNm
Load application:
max. load application: 1794 kVA(corresponds to 71,77 % from 2500 kVA) Power: 2500 kVA
for Power factor 0.4 Power factor: 0.8
15% transient voltage drop transient voltage drop: -17.3 %
Remarks: