PVSYST V6.

53 19/08/21 Page 1/3

Grid-Connected System: Simulation parameters

Project : Viewing PT. Nikawatex 500 kWp


Geographical Site PT. Nikawa Country Indonesia
Situation Latitude 6.37° N Longitude 107.32° E
Time defined as Legal Time Time zone UT+7 Altitude 20 m
Albedo 0.20
Meteo data: PT. Nikawa Meteonorm 7.1 (1971-1980), Sat=100% - Synthetic

Simulation variant : New simulation variant


Simulation date 19/08/21 11h12

Simulation parameters
Collector Plane Orientation Tilt 30° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings

PV Array Characteristics
PV module Si-mono Model SP350-72M
Custom parameters definition Manufacturer Adyasolar
Number of PV modules In series 18 modules In parallel 80 strings
Total number of PV modules Nb. modules 1440 Unit Nom. Power 350 Wp
Array global power Nominal (STC) 504 kWp At operating cond. 485 kWp (50°C)
Array operating characteristics (50°C) U mpp 608 V I mpp 798 A
Total area Module area 2808 m²

Inverter Model SG50CX


Custom parameters definition Manufacturer Sungrow
Characteristics Operating Voltage 550-800 V Unit Nom. Power 50 kWac
Inverter pack Nb. of inverters 10 units Total Power 500 kWac

PV Array loss factors


Thermal Loss factor Uc (const) 29.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 13 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction 3.0 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Incidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Param. 0.05

User's needs : Unlimited load (grid)

PVsyst Licensed to PT Adyawinsa Electrical and Power (Indonesia)


PVSYST V6.53 19/08/21 Page 2/3

Grid-Connected System: Main results


Project : Viewing PT. Nikawatex 500 kWp
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation tilt 30° azimuth 0°
PV modules Model SP350-72M Pnom 350 Wp
PV Array Nb. of modules 1440 Pnom total 504 kWp
Inverter Model SG50CX Pnom 50.0 kW ac
Inverter pack Nb. of units 10.0 Pnom total 500 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 754.3 MWh/year Specific prod. 1497 kWh/kWp/year
Performance Ratio PR 88.39 %

Normalized productions (per installed kWp): Nominal power 504 kWp Performance Ratio PR
7 1.0
PR : Performance Ratio (Yf / Yr) : 0.884
Lc : Collection Loss (PV-array losses) 0.48 kWh/kWp/day
Ls : System Loss (inverter, ...) 0.06 kWh/kWp/day
Yf : Produced useful energy (inverter output) 4.1 kWh/kWp/day
6
0.8
Normalized Energy [kWh/kWp/day]

5
Performance Ratio PR

0.6
4

3
0.4

0.2
1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

New simulation variant


Balances and main results

GlobHor DiffHor T Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh
January 132.1 73.33 25.50 146.3 142.3 66.76 65.72 0.891
February 146.9 72.98 25.89 155.4 151.0 70.69 69.63 0.889
March 182.8 77.55 26.90 176.7 171.2 79.82 78.63 0.883
April 191.2 69.17 28.11 164.6 158.5 73.79 72.69 0.876
May 173.2 76.89 28.57 135.1 129.1 60.59 59.67 0.876
June 150.0 74.78 27.88 113.8 108.6 51.28 50.47 0.880
July 151.8 75.06 28.11 116.6 111.3 52.51 51.67 0.879
August 163.9 83.32 28.06 137.7 132.4 62.14 61.20 0.881
September 149.1 85.53 27.48 138.4 133.6 62.72 61.77 0.886
October 153.0 78.74 27.42 154.4 149.7 69.78 68.74 0.884
November 125.7 76.08 26.86 137.2 133.2 62.42 61.48 0.889
December 108.5 76.32 26.36 117.0 113.4 53.51 52.66 0.893
Year 1828.1 919.74 27.27 1693.2 1634.2 765.99 754.33 0.884

Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T Amb Ambient Temperature E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Licensed to PT Adyawinsa Electrical and Power (Indonesia)


PVSYST V6.53 19/08/21 Page 3/3

Grid-Connected System: Loss diagram


Project : Viewing PT. Nikawatex 500 kWp
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation tilt 30° azimuth 0°
PV modules Model SP350-72M Pnom 350 Wp
PV Array Nb. of modules 1440 Pnom total 504 kWp
Inverter Model SG50CX Pnom 50.0 kW ac
Inverter pack Nb. of units 10.0 Pnom total 500 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1828 kWh/m² Horizontal global irradiation

-7.4% Global incident in coll. plane


-3.5% IAM factor on global

1634 kWh/m² * 2808 m² coll. Effective irradiance on collectors


efficiency at STC = 19.00% PV conversion

872 MWh Array nominal energy (at STC effic.)


-0.8% PV loss due to irradiance level

-7.0% PV loss due to temperature

-3.0% Module quality loss


-1.0% Module array mismatch loss
-0.9% Ohmic wiring loss
766 MWh Array virtual energy at MPP

-1.5% Inverter Loss during operation (efficiency)


0.0% Inverter Loss over nominal inv. power
0.0% Inverter Loss due to power threshold
0.0% Inverter Loss over nominal inv. voltage
0.0% Inverter Loss due to voltage threshold
754 MWh Available Energy at Inverter Output

754 MWh Energy injected into grid

PVsyst Licensed to PT Adyawinsa Electrical and Power (Indonesia)