APOLLO PROTON THERAPY & CANCER CARE DOC NO: BSL/AHEL/ECL/FPS & FAS-001

HOSPITAL FORMAT REV. No. R00


CHECK SHEET FOR INSTALLATION OF FIRE PROTECTION & FIRE ALARM SYSTEM
Building Reference: Location:

Reference Drawing: Rev.:

S.NO. INSTALLATION CHECKS Approved Approved Ref


Remarks/Comments
make documents
01 Ensure fire exit and evacuation plans were displayed as per NFPA zone
-
requirement.
02 Ensure fire indicator alarm is installed at respective area as specified in
NOTIFIER
approved drawing and showing condition normal.
03 Ensure all manual call points are installed visibly. NOTIFIER/
HONEYWELL
04 Check automatic fire/smoke detector are working properly NOTIFIER/
HONEYWELL
05 Ensure that the occupants can hear the fire alarm sound. At least the sound
the level should be 15db higher to the minimum outside noise level/ 5db to -
the maximum outside noise level.
06 Ensure all fire extinguishers are placed in right zone as per NFPA Minimax /
instruction/as per approved drawing. Safex
07 Ensure Sprinkler control valves are working properly and also ensure all Tyco/ Viking /
zones are pressurized. Rapid Drop
08 Ensure Sprinkler system impairment program is in place.
-
09 Ensure proper access is provided for fire pipe lines access.
Jindal
10 Ensure self closing fire doors are working properly.

11 Ensure emergency light fittings and exit signs boards were displayed NOTIFIER/
properly. HONEYWELL
12 Ensure external Fire Hydrants unobstructed.
Neco
13 Ensure below and above detectors are installed as per Approved latest RCP
-
and as per NFPA std.
14 Ensure smoke detectors are installed in HVAC ducts as specified in drawing. NOTIFIER/
HONEYWELL
15 Ensure fire alarm loop system resistance is within the limit. NOTIFIER/
HONEYWELL
REMARK:

Prepared BSL QA/QC (BSL) MEP (L&T) QA/QC (L&T) AHEL

NAME
DATE

SIGNATURE