Storey Drift Limitation Check

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur

Storey Drift Limitation Check

Allowable
Story Load Combinations Direction ETABS Drift Storey Drift Check
Drift
Head Room Slab B01: 1.0 (DL+SIDL+LL) X 0.00003 0.1000 13 O.K.
Head Room Slab B02: 1.0 (DL+SIDL+WLX) X 0.00041 1.2875 13 O.K.
Head Room Slab B03: 1.0 (DL+SIDL-WLX) X 0.00037 1.1406 13 O.K.
Head Room Slab B04: 1.0 (DL+SIDL+WLY) X 0.00073 2.2688 13 O.K.
Head Room Slab B05: 1.0 (DL+SIDL-WLY) X 0.00068 2.1250 13 O.K.
Head Room Slab B06: 1.0 (DL+SIDL+ELX) X 0.00067 2.0906 13 O.K.
Head Room Slab B07: 1.0 (DL+SIDL-ELX) X 0.00062 1.9438 13 O.K.
Head Room Slab B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00065 2.0156 13 O.K.
Head Room Slab B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00059 1.8500 13 O.K.
Head Room Slab B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00071 2.2188 13 O.K.
Head Room Slab B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00066 2.0719 13 O.K.
Head Room Slab B17: 1.0 [DL+SIDL-(ELY-e)] X 0.00005 0.1500 13 O.K.
Head Room Slab B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00034 1.0563 13 O.K.
Head Room Slab B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00028 0.8875 13 O.K.
Head Room Slab B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00059 1.8406 13 O.K.
Head Room Slab B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00054 1.6750 13 O.K.
Head Room Slab B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00054 1.6969 13 O.K.
Head Room Slab B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00049 1.5281 13 O.K.
Head Room Slab B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00053 1.6438 13 O.K.
Head Room Slab B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00046 1.4500 13 O.K.
Head Room Slab B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00058 1.8000 13 O.K.
Head Room Slab B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00052 1.6313 13 O.K.
Head Room Slab B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) X 0.00005 0.1438 13 O.K.
Head Room Slab B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] X 0.00005 0.1469 13 O.K.
Terrace B01: 1.0 (DL+SIDL+LL) X 0.00001 0.0375 13 O.K.
Terrace B02: 1.0 (DL+SIDL+WLX) X 0.00022 0.6969 13 O.K.
Terrace B03: 1.0 (DL+SIDL-WLX) X 0.00020 0.6313 13 O.K.
Terrace B04: 1.0 (DL+SIDL+WLY) X 0.00039 1.2313 13 O.K.
Terrace B05: 1.0 (DL+SIDL-WLY) X 0.00037 1.1656 13 O.K.
Terrace B06: 1.0 (DL+SIDL+ELX) X 0.00075 2.3313 13 O.K.
Terrace B07: 1.0 (DL+SIDL-ELX) X 0.00073 2.2656 13 O.K.
Terrace B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00081 2.5156 13 O.K.
Terrace B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00078 2.4500 13 O.K.
Terrace B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00069 2.1469 13 O.K.
Terrace B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00067 2.0813 13 O.K.
Terrace B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00018 0.5656 13 O.K.
Terrace B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00016 0.4938 13 O.K.
Terrace B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00032 0.9969 13 O.K.
Terrace B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00030 0.9250 13 O.K.
Terrace B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00060 1.8750 13 O.K.
Terrace B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00058 1.8031 13 O.K.
Terrace B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00065 2.0219 13 O.K.
Terrace B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00062 1.9500 13 O.K.
Terrace B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00055 1.7281 13 O.K.
Terrace B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00053 1.6563 13 O.K.
Floor 03 B01: 1.0 (DL+SIDL+LL) X 0.00001 0.0188 13 O.K.
Floor 03 B02: 1.0 (DL+SIDL+WLX) X 0.00027 0.8531 13 O.K.
Floor 03 B03: 1.0 (DL+SIDL-WLX) X 0.00026 0.8188 13 O.K.
Floor 03 B04: 1.0 (DL+SIDL+WLY) X 0.00049 1.5313 13 O.K.
Floor 03 B05: 1.0 (DL+SIDL-WLY) X 0.00048 1.4969 13 O.K.
Floor 03 B06: 1.0 (DL+SIDL+ELX) X 0.00102 3.1781 13 O.K.
Floor 03 B07: 1.0 (DL+SIDL-ELX) X 0.00101 3.1438 13 O.K.
Floor 03 B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00111 3.4719 13 O.K.
Floor 03 B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00110 3.4375 13 O.K.
Floor 03 B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00092 2.8844 13 O.K.
Floor 03 B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00091 2.8500 13 O.K.
Floor 03 B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00022 0.6875 13 O.K.
Floor 03 B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00021 0.6500 13 O.K.
Floor 03 B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00039 1.2313 13 O.K.

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check

Floor 03 B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00038 1.1906 13 O.K.


Floor 03 B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00082 2.5469 13 O.K.
Floor 03 B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00080 2.5094 13 O.K.
Floor 03 B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00089 2.7813 13 O.K.
Floor 03 B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00088 2.7438 13 O.K.
Floor 03 B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00074 2.3125 13 O.K.
Floor 03 B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00073 2.2750 13 O.K.
Floor 02 B01: 1.0 (DL+SIDL+LL) X 0.00001 0.0188 13 O.K.
Floor 02 B02: 1.0 (DL+SIDL+WLX) X 0.00033 1.0313 13 O.K.
Floor 02 B03: 1.0 (DL+SIDL-WLX) X 0.00032 0.9969 13 O.K.
Floor 02 B04: 1.0 (DL+SIDL+WLY) X 0.00059 1.8500 13 O.K.
Floor 02 B05: 1.0 (DL+SIDL-WLY) X 0.00058 1.8156 13 O.K.
Floor 02 B06: 1.0 (DL+SIDL+ELX) X 0.00117 3.6469 13 O.K.
Floor 02 B07: 1.0 (DL+SIDL-ELX) X 0.00116 3.6125 13 O.K.
Floor 02 B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00128 4.0031 13 O.K.
Floor 02 B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00127 3.9688 13 O.K.
Floor 02 B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00105 3.2906 13 O.K.
Floor 02 B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00104 3.2563 13 O.K.
Floor 02 B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00027 0.8313 13 O.K.
Floor 02 B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00025 0.7938 13 O.K.
Floor 02 B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00048 1.4875 13 O.K.
Floor 02 B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00046 1.4469 13 O.K.
Floor 02 B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00094 2.9219 13 O.K.
Floor 02 B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00092 2.8844 13 O.K.
Floor 02 B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00103 3.2063 13 O.K.
Floor 02 B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00101 3.1688 13 O.K.
Floor 02 B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00084 2.6375 13 O.K.
Floor 02 B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00083 2.6000 13 O.K.
Floor 01 B01: 1.0 (DL+SIDL+LL) X 0.00004 0.1250 13 O.K.
Floor 01 B02: 1.0 (DL+SIDL+WLX) X 0.00036 1.1188 13 O.K.
Floor 01 B03: 1.0 (DL+SIDL-WLX) X 0.00036 1.1281 13 O.K.
Floor 01 B04: 1.0 (DL+SIDL+WLY) X 0.00064 2.0125 13 O.K.
Floor 01 B05: 1.0 (DL+SIDL-WLY) X 0.00065 2.0250 13 O.K.
Floor 01 B06: 1.0 (DL+SIDL+ELX) X 0.00121 3.7875 13 O.K.
Floor 01 B07: 1.0 (DL+SIDL-ELX) X 0.00122 3.8000 13 O.K.
Floor 01 B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00132 4.1219 13 O.K.
Floor 01 B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00132 4.1344 13 O.K.
Floor 01 B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00111 3.4531 13 O.K.
Floor 01 B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00111 3.4656 13 O.K.
Floor 01 B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00028 0.8875 13 O.K.
Floor 01 B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00029 0.9031 13 O.K.
Floor 01 B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00051 1.6063 13 O.K.
Floor 01 B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00052 1.6188 13 O.K.
Floor 01 B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00097 3.0250 13 O.K.
Floor 01 B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00097 3.0406 13 O.K.
Floor 01 B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00105 3.2906 13 O.K.
Floor 01 B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00106 3.3063 13 O.K.
Floor 01 B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00088 2.7563 13 O.K.
Floor 01 B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00089 2.7719 13 O.K.
Ground Floor B01: 1.0 (DL+SIDL+LL) X 0.00008 0.2469 13 O.K.
Ground Floor B02: 1.0 (DL+SIDL+WLX) X 0.00020 0.6281 13 O.K.
Ground Floor B03: 1.0 (DL+SIDL-WLX) X 0.00026 0.7969 13 O.K.
Ground Floor B04: 1.0 (DL+SIDL+WLY) X 0.00034 1.0750 13 O.K.
Ground Floor B05: 1.0 (DL+SIDL-WLY) X 0.00041 1.2688 13 O.K.
Ground Floor B06: 1.0 (DL+SIDL+ELX) X 0.00062 1.9406 13 O.K.
Ground Floor B07: 1.0 (DL+SIDL-ELX) X 0.00070 2.1781 13 O.K.
Ground Floor B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00060 1.8781 13 O.K.
Ground Floor B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00068 2.1156 13 O.K.
Ground Floor B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00064 2.0031 13 O.K.
Ground Floor B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00072 2.2406 13 O.K.
Ground Floor B16: 1.0 [DL+SIDL+(ELY-e)] X 0.00016 0.4969 13 O.K.
Ground Floor B17: 1.0 [DL+SIDL-(ELY-e)] X 0.00018 0.5500 13 O.K.
Ground Floor B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00016 0.5125 13 O.K.
Ground Floor B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00023 0.7125 13 O.K.
Ground Floor B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00028 0.8719 13 O.K.
Ground Floor B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00035 1.0906 13 O.K.

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check

Ground Floor B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00050 1.5656 13 O.K.
Ground Floor B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00058 1.8156 13 O.K.
Ground Floor B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00048 1.5125 13 O.K.
Ground Floor B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00057 1.7656 13 O.K.
Ground Floor B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00052 1.6156 13 O.K.
Ground Floor B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00060 1.8656 13 O.K.
Ground Floor B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] X 0.00014 0.4281 13 O.K.
Ground Floor B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] X 0.00015 0.4531 13 O.K.
Head Room Slab B01: 1.0 (DL+SIDL+LL) Y 0.00007 0.2094 13 O.K.
Head Room Slab B02: 1.0 (DL+SIDL+WLX) Y 0.00006 0.1781 13 O.K.
Head Room Slab B03: 1.0 (DL+SIDL-WLX) Y 0.00006 0.1750 13 O.K.
Head Room Slab B12: 1.0 (DL+SIDL+ELY) Y 0.00046 1.4438 13 O.K.
Head Room Slab B13: 1.0 (DL+SIDL-ELY) Y 0.00036 1.1375 13 O.K.
Head Room Slab B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00047 1.4750 13 O.K.
Head Room Slab B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00037 1.1688 13 O.K.
Head Room Slab B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00046 1.4406 13 O.K.
Head Room Slab B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00036 1.1250 13 O.K.
Head Room Slab B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) Y 0.00007 0.2125 13 O.K.
Head Room Slab B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) Y 0.00007 0.2125 13 O.K.
Head Room Slab B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) Y 0.00007 0.2313 13 O.K.
Head Room Slab B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) Y 0.00007 0.2250 13 O.K.
Head Room Slab B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) Y 0.00007 0.2156 13 O.K.
Head Room Slab B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) Y 0.00007 0.2188 13 O.K.
Head Room Slab B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] Y 0.00007 0.2031 13 O.K.
Head Room Slab B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] Y 0.00007 0.2031 13 O.K.
Head Room Slab B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] Y 0.00008 0.2469 13 O.K.
Head Room Slab B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] Y 0.00008 0.2438 13 O.K.
Head Room Slab B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00039 1.2281 13 O.K.
Head Room Slab B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00027 0.8406 13 O.K.
Head Room Slab B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00040 1.2500 13 O.K.
Head Room Slab B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00028 0.8625 13 O.K.
Head Room Slab B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00039 1.2250 13 O.K.
Head Room Slab B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00027 0.8281 13 O.K.
Terrace B01: 1.0 (DL+SIDL+LL) Y 0.00002 0.0563 13 O.K.
Terrace B12: 1.0 (DL+SIDL+ELY) Y 0.00054 1.6813 13 O.K.
Terrace B13: 1.0 (DL+SIDL-ELY) Y 0.00052 1.6125 13 O.K.
Terrace B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00066 2.0594 13 O.K.
Terrace B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00064 2.0094 13 O.K.
Terrace B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00067 2.0813 13 O.K.
Terrace B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00064 1.9969 13 O.K.
Terrace B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00044 1.3656 13 O.K.
Terrace B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00041 1.2781 13 O.K.
Terrace B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00053 1.6594 13 O.K.
Terrace B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00051 1.5938 13 O.K.
Terrace B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00054 1.6844 13 O.K.
Terrace B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00051 1.5781 13 O.K.
Floor 03 B01: 1.0 (DL+SIDL+LL) Y 0.00002 0.0469 13 O.K.
Floor 03 B12: 1.0 (DL+SIDL+ELY) Y 0.00072 2.2469 13 O.K.
Floor 03 B13: 1.0 (DL+SIDL-ELY) Y 0.00070 2.1906 13 O.K.
Floor 03 B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00090 2.8250 13 O.K.
Floor 03 B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00091 2.8281 13 O.K.
Floor 03 B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00092 2.8875 13 O.K.
Floor 03 B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00090 2.8094 13 O.K.
Floor 03 B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00058 1.8125 13 O.K.
Floor 03 B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00056 1.7500 13 O.K.
Floor 03 B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00072 2.2594 13 O.K.
Floor 03 B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00072 2.2625 13 O.K.
Floor 03 B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00074 2.3250 13 O.K.
Floor 03 B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00071 2.2313 13 O.K.
Floor 02 B01: 1.0 (DL+SIDL+LL) Y 0.00001 0.0375 13 O.K.
Floor 02 B12: 1.0 (DL+SIDL+ELY) Y 0.00079 2.4750 13 O.K.
Floor 02 B13: 1.0 (DL+SIDL-ELY) Y 0.00079 2.4531 13 O.K.
Floor 02 B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00101 3.1688 13 O.K.
Floor 02 B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00103 3.2313 13 O.K.
Floor 02 B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00104 3.2531 13 O.K.
Floor 02 B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00103 3.2219 13 O.K.

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check

Floor 02 B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00064 1.9844 13 O.K.


Floor 02 B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00063 1.9750 13 O.K.
Floor 02 B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00081 2.5250 13 O.K.
Floor 02 B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00083 2.5969 13 O.K.
Floor 02 B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00084 2.6094 13 O.K.
Floor 02 B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00082 2.5719 13 O.K.
Floor 01 B01: 1.0 (DL+SIDL+LL) Y 0.00003 0.0875 13 O.K.
Floor 01 B02: 1.0 (DL+SIDL+WLX) Y 0.00010 0.3094 13 O.K.
Floor 01 B12: 1.0 (DL+SIDL+ELY) Y 0.00088 2.7594 13 O.K.
Floor 01 B13: 1.0 (DL+SIDL-ELY) Y 0.00090 2.8156 13 O.K.
Floor 01 B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00105 3.2688 13 O.K.
Floor 01 B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00109 3.4125 13 O.K.
Floor 01 B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00113 3.5188 13 O.K.
Floor 01 B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00114 3.5750 13 O.K.
Floor 01 B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) Y 0.00009 0.2750 13 O.K.
Floor 01 B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) Y 0.00014 0.4281 13 O.K.
Floor 01 B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00070 2.2000 13 O.K.
Floor 01 B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00072 2.2625 13 O.K.
Floor 01 B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00083 2.5906 13 O.K.
Floor 01 B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00088 2.7563 13 O.K.
Floor 01 B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00090 2.8094 13 O.K.
Floor 01 B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00092 2.8719 13 O.K.
Ground Floor B01: 1.0 (DL+SIDL+LL) Y 0.00004 0.1313 13 O.K.
Ground Floor B02: 1.0 (DL+SIDL+WLX) Y 0.00004 0.1313 13 O.K.
Ground Floor B04: 1.0 (DL+SIDL+WLY) Y 0.00006 0.2000 13 O.K.
Ground Floor B12: 1.0 (DL+SIDL+ELY) Y 0.00069 2.1625 13 O.K.
Ground Floor B13: 1.0 (DL+SIDL-ELY) Y 0.00069 2.1531 13 O.K.
Ground Floor B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00071 2.2125 13 O.K.
Ground Floor B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00071 2.2031 13 O.K.
Ground Floor B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00068 2.1125 13 O.K.
Ground Floor B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00067 2.1031 13 O.K.
Ground Floor B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) Y 0.00005 0.1438 13 O.K.
Ground Floor B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) Y 0.00004 0.1094 13 O.K.
Ground Floor B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) Y 0.00006 0.1750 13 O.K.
Ground Floor B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] Y 0.00013 0.4156 13 O.K.
Ground Floor B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00056 1.7375 13 O.K.
Ground Floor B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00055 1.7156 13 O.K.
Ground Floor B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00057 1.7781 13 O.K.
Ground Floor B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00056 1.7531 13 O.K.
Ground Floor B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00054 1.6969 13 O.K.
Ground Floor B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00054 1.6750 13 O.K.

Note:
Storey Drift is nothing but relative displacement between floors above and/or below
the storey under consideration. Storey drift in any story shall not exceed 0.004 times the storey
height, under the action of design base shear VB with no load factor that is, partial safety factor
for all loads taken as 1.0 which is nothing but service load combinations. The check is given

Calculations:
in Clause 7.11.1 of IS 1893 (Part-1): 2016.
as per Indian Standard 1893:2016 Clasue 7.11.1.1 Storey Drift Limitation
Storey Drift in any storey shall not exceed 0.004 times the storey height
Drift shown in ETABS is as Storey Drift / Floor Height
where, Height between slabs is 3.25 m i.e., 3250 mm
Allowable Drift = 0.004 × Storey Height = 0.004 × 3250 = 13 mm
hence, here Storey Drift for all storey is not exceeding 0.004 times the storey height for all Service Load Combinations
⸫ Check for Storey Drift Limitation is O.K.

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Torsional Irregularity Check

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur

Torsional Irregularity Check

Story Load Case Direction Maximum Average Ratio Check


mm mm
Head Room Slab ELX X 14.866 13.81 1.076 O.K.
Terrace ELX X 13.94 12.298 1.133 O.K.
Floor 03 ELX X 11.549 10.106 1.143 O.K.
Floor 02 ELX X 8.261 7.237 1.142 O.K.
Floor 01 ELX X 4.487 4.014 1.118 O.K.
Head Room Slab ELX+e X 15.593 13.702 1.138 O.K.
Terrace ELX+e X 15.201 12.524 1.214 O.K.
Floor 03 ELX+e X 12.619 10.3 1.225 O.K.
Floor 02 ELX+e X 9.026 7.375 1.224 O.K.
Floor 01 ELX+e X 4.882 4.081 1.196 O.K.
Head Room Slab ELX-e X 14.138 13.917 1.016 O.K.
Terrace ELX-e X 12.679 12.071 1.05 O.K.
Floor 03 ELX-e X 10.48 9.911 1.057 O.K.
Floor 02 ELX-e X 7.496 7.099 1.056 O.K.
Floor 01 ELX-e X 4.093 3.947 1.037 O.K.
Head Room Slab ELY Y 11.06 11.054 1.001 O.K.
Terrace ELY Y 9.872 9.725 1.015 O.K.
Floor 03 ELY Y 8.166 8.022 1.018 O.K.
Floor 02 ELY Y 5.87 5.736 1.023 O.K.
Floor 01 ELY Y 3.313 3.197 1.036 O.K.
Head Room Slab ELY+e Y 11.461 11.046 1.038 O.K.
Terrace ELY+e Y 12.343 9.712 1.271 O.K.
Floor 03 ELY+e Y 10.228 8.009 1.277 O.K.
Floor 02 ELY+e Y 7.289 5.725 1.273 O.K.
Floor 01 ELY+e Y 3.962 3.187 1.243 O.K.
Head Room Slab ELY-e Y 11.488 11.061 1.039 O.K.
Terrace ELY-e Y 12.662 9.738 1.3 O.K.
Floor 03 ELY-e Y 10.543 8.034 1.312 O.K.
Floor 02 ELY-e Y 7.581 5.748 1.319 O.K.
Floor 01 ELY-e Y 4.213 3.207 1.314 O.K.

Notes:
The designer should review the structural arrangement of the structural elements to
ensure that the code requirements against building irregularity will be satisfied. Building
Irregularity checks are depending on the code that we are using, although there are similarities.
The most common checks under a building irregularity are the torsional irregularity check
which will be tackled by applying check as per IS 1893: 2016 (Part-1) Clause 7.1 and Table
No. 5. The code states that the ratio of maximum horizontal displacement at one end minimum
horizontal displacement at another end should not exceed 1.5

as per IS 1893:2016 Clause 7.1 Table 5 Torsional Irregularity


Building is Torsionally Irregular when, Maximum Displacement / Minimum Displacement > 1.5
hence, our all ratios are with in acceptable limit i.e. all the Ratios are less than 1.5
which is as per Indian Standard 1893:2016 Clause 7.1 Table 5
⸫ Check for Torsional Irregularity is O.K.

Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur


Lateral Sway Check

Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur

Lateral Sway Check

Story Load Case Direction Max. Displacemnet H/500 Check


mm mm
Head Room Slab WLX X 4.834 35 O.K.
Head Room Slab WLY Y 5.946 35 O.K.
Terrace WLX X 3.94 28.5 O.K.
Terrace WLY Y 4.497 28.5 O.K.

Note:
This is Design check given by IS 456: 2000 in Clause 20.5; this check is regarding the deflection at top storey with respect to the height of
the structure where the clause states that under transient wind load the lateral sway at top should not exceed H/500, where H is the total height of
the building. Hence for Wind Load Check the Story Displacement for Top of the Structure

Calculations:
as per Indian Standard 456:2000 Clause 20.5 Lateral Sway at Top should not exceed H/500
here, H is the total height of building i.e; 17.5 meter at Head Room Slab Level ⸫ H = 17500 milimeter
& 14.25 meter at Head Room Slab Level ⸫ H = 14250 milimeter
⸫ for Top of Head Room Slab, H/500 = 17500/500 = 35 mm & for Terrace Level H/500= 14250/500 = 28.5
hence, here Lateral Sway at Top for Wind Load is within Acceptable Limits which is as per IS 456:200 Clause 20.5
⸫ Check for Lateral Sway is O.K.