Excel Sheets For Analysis Checks
Excel Sheets For Analysis Checks
I highly encourage you to design the structures with your approach and understanding and always cross check the results manually.
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Allowable
Story Load Combinations Direction ETABS Drift Storey Drift Check
Drift
Head Room Slab B01: 1.0 (DL+SIDL+LL) X 0.00003 0.1000 13 O.K.
Head Room Slab B02: 1.0 (DL+SIDL+WLX) X 0.00041 1.2875 13 O.K.
Head Room Slab B03: 1.0 (DL+SIDL-WLX) X 0.00037 1.1406 13 O.K.
Head Room Slab B04: 1.0 (DL+SIDL+WLY) X 0.00073 2.2688 13 O.K.
Head Room Slab B05: 1.0 (DL+SIDL-WLY) X 0.00068 2.1250 13 O.K.
Head Room Slab B06: 1.0 (DL+SIDL+ELX) X 0.00067 2.0906 13 O.K.
Head Room Slab B07: 1.0 (DL+SIDL-ELX) X 0.00062 1.9438 13 O.K.
Head Room Slab B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00065 2.0156 13 O.K.
Head Room Slab B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00059 1.8500 13 O.K.
Head Room Slab B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00071 2.2188 13 O.K.
Head Room Slab B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00066 2.0719 13 O.K.
Head Room Slab B17: 1.0 [DL+SIDL-(ELY-e)] X 0.00005 0.1500 13 O.K.
Head Room Slab B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00034 1.0563 13 O.K.
Head Room Slab B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00028 0.8875 13 O.K.
Head Room Slab B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00059 1.8406 13 O.K.
Head Room Slab B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00054 1.6750 13 O.K.
Head Room Slab B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00054 1.6969 13 O.K.
Head Room Slab B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00049 1.5281 13 O.K.
Head Room Slab B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00053 1.6438 13 O.K.
Head Room Slab B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00046 1.4500 13 O.K.
Head Room Slab B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00058 1.8000 13 O.K.
Head Room Slab B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00052 1.6313 13 O.K.
Head Room Slab B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) X 0.00005 0.1438 13 O.K.
Head Room Slab B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] X 0.00005 0.1469 13 O.K.
Terrace B01: 1.0 (DL+SIDL+LL) X 0.00001 0.0375 13 O.K.
Terrace B02: 1.0 (DL+SIDL+WLX) X 0.00022 0.6969 13 O.K.
Terrace B03: 1.0 (DL+SIDL-WLX) X 0.00020 0.6313 13 O.K.
Terrace B04: 1.0 (DL+SIDL+WLY) X 0.00039 1.2313 13 O.K.
Terrace B05: 1.0 (DL+SIDL-WLY) X 0.00037 1.1656 13 O.K.
Terrace B06: 1.0 (DL+SIDL+ELX) X 0.00075 2.3313 13 O.K.
Terrace B07: 1.0 (DL+SIDL-ELX) X 0.00073 2.2656 13 O.K.
Terrace B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00081 2.5156 13 O.K.
Terrace B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00078 2.4500 13 O.K.
Terrace B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00069 2.1469 13 O.K.
Terrace B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00067 2.0813 13 O.K.
Terrace B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00018 0.5656 13 O.K.
Terrace B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00016 0.4938 13 O.K.
Terrace B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00032 0.9969 13 O.K.
Terrace B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) X 0.00030 0.9250 13 O.K.
Terrace B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00060 1.8750 13 O.K.
Terrace B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00058 1.8031 13 O.K.
Terrace B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00065 2.0219 13 O.K.
Terrace B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00062 1.9500 13 O.K.
Terrace B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00055 1.7281 13 O.K.
Terrace B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00053 1.6563 13 O.K.
Floor 03 B01: 1.0 (DL+SIDL+LL) X 0.00001 0.0188 13 O.K.
Floor 03 B02: 1.0 (DL+SIDL+WLX) X 0.00027 0.8531 13 O.K.
Floor 03 B03: 1.0 (DL+SIDL-WLX) X 0.00026 0.8188 13 O.K.
Floor 03 B04: 1.0 (DL+SIDL+WLY) X 0.00049 1.5313 13 O.K.
Floor 03 B05: 1.0 (DL+SIDL-WLY) X 0.00048 1.4969 13 O.K.
Floor 03 B06: 1.0 (DL+SIDL+ELX) X 0.00102 3.1781 13 O.K.
Floor 03 B07: 1.0 (DL+SIDL-ELX) X 0.00101 3.1438 13 O.K.
Floor 03 B08: 1.0 [DL+SIDL+(ELX+e)] X 0.00111 3.4719 13 O.K.
Floor 03 B09: 1.0 [DL+SIDL-(ELX+e)] X 0.00110 3.4375 13 O.K.
Floor 03 B10: 1.0 [DL+SIDL+(ELX-e)] X 0.00092 2.8844 13 O.K.
Floor 03 B11: 1.0 [DL+SIDL-(ELX-e)] X 0.00091 2.8500 13 O.K.
Floor 03 B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) X 0.00022 0.6875 13 O.K.
Floor 03 B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) X 0.00021 0.6500 13 O.K.
Floor 03 B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) X 0.00039 1.2313 13 O.K.
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check
Ground Floor B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) X 0.00050 1.5656 13 O.K.
Ground Floor B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) X 0.00058 1.8156 13 O.K.
Ground Floor B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] X 0.00048 1.5125 13 O.K.
Ground Floor B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] X 0.00057 1.7656 13 O.K.
Ground Floor B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] X 0.00052 1.6156 13 O.K.
Ground Floor B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] X 0.00060 1.8656 13 O.K.
Ground Floor B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] X 0.00014 0.4281 13 O.K.
Ground Floor B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] X 0.00015 0.4531 13 O.K.
Head Room Slab B01: 1.0 (DL+SIDL+LL) Y 0.00007 0.2094 13 O.K.
Head Room Slab B02: 1.0 (DL+SIDL+WLX) Y 0.00006 0.1781 13 O.K.
Head Room Slab B03: 1.0 (DL+SIDL-WLX) Y 0.00006 0.1750 13 O.K.
Head Room Slab B12: 1.0 (DL+SIDL+ELY) Y 0.00046 1.4438 13 O.K.
Head Room Slab B13: 1.0 (DL+SIDL-ELY) Y 0.00036 1.1375 13 O.K.
Head Room Slab B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00047 1.4750 13 O.K.
Head Room Slab B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00037 1.1688 13 O.K.
Head Room Slab B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00046 1.4406 13 O.K.
Head Room Slab B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00036 1.1250 13 O.K.
Head Room Slab B18: 1.0 (DL+SIDL) + 0.8 (LL+WLX) Y 0.00007 0.2125 13 O.K.
Head Room Slab B19: 1.0 (DL+SIDL) + 0.8 (LL-WLX) Y 0.00007 0.2125 13 O.K.
Head Room Slab B20: 1.0 (DL+SIDL) + 0.8 (LL+WLY) Y 0.00007 0.2313 13 O.K.
Head Room Slab B21: 1.0 (DL+SIDL) + 0.8 (LL-WLY) Y 0.00007 0.2250 13 O.K.
Head Room Slab B22: 1.0 (DL+SIDL) + 0.8 (LL+ELX) Y 0.00007 0.2156 13 O.K.
Head Room Slab B23: 1.0 (DL+SIDL) + 0.8 (LL-ELX) Y 0.00007 0.2188 13 O.K.
Head Room Slab B24: 1.0 (DL+SIDL) + 0.8 [LL+(ELX+e)] Y 0.00007 0.2031 13 O.K.
Head Room Slab B25: 1.0 (DL+SIDL) + 0.8 [LL-(ELX+e)] Y 0.00007 0.2031 13 O.K.
Head Room Slab B26: 1.0 (DL+SIDL) + 0.8 [LL+(ELX-e)] Y 0.00008 0.2469 13 O.K.
Head Room Slab B27: 1.0 (DL+SIDL) + 0.8 [LL-(ELX-e)] Y 0.00008 0.2438 13 O.K.
Head Room Slab B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00039 1.2281 13 O.K.
Head Room Slab B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00027 0.8406 13 O.K.
Head Room Slab B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00040 1.2500 13 O.K.
Head Room Slab B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00028 0.8625 13 O.K.
Head Room Slab B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00039 1.2250 13 O.K.
Head Room Slab B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00027 0.8281 13 O.K.
Terrace B01: 1.0 (DL+SIDL+LL) Y 0.00002 0.0563 13 O.K.
Terrace B12: 1.0 (DL+SIDL+ELY) Y 0.00054 1.6813 13 O.K.
Terrace B13: 1.0 (DL+SIDL-ELY) Y 0.00052 1.6125 13 O.K.
Terrace B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00066 2.0594 13 O.K.
Terrace B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00064 2.0094 13 O.K.
Terrace B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00067 2.0813 13 O.K.
Terrace B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00064 1.9969 13 O.K.
Terrace B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00044 1.3656 13 O.K.
Terrace B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00041 1.2781 13 O.K.
Terrace B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00053 1.6594 13 O.K.
Terrace B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00051 1.5938 13 O.K.
Terrace B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00054 1.6844 13 O.K.
Terrace B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00051 1.5781 13 O.K.
Floor 03 B01: 1.0 (DL+SIDL+LL) Y 0.00002 0.0469 13 O.K.
Floor 03 B12: 1.0 (DL+SIDL+ELY) Y 0.00072 2.2469 13 O.K.
Floor 03 B13: 1.0 (DL+SIDL-ELY) Y 0.00070 2.1906 13 O.K.
Floor 03 B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00090 2.8250 13 O.K.
Floor 03 B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00091 2.8281 13 O.K.
Floor 03 B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00092 2.8875 13 O.K.
Floor 03 B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00090 2.8094 13 O.K.
Floor 03 B28: 1.0 (DL+SIDL) + 0.8 (LL+ELY) Y 0.00058 1.8125 13 O.K.
Floor 03 B29: 1.0 (DL+SIDL) + 0.8 (LL-ELY) Y 0.00056 1.7500 13 O.K.
Floor 03 B30: 1.0 (DL+SIDL) + 0.8 [LL+(ELY+e)] Y 0.00072 2.2594 13 O.K.
Floor 03 B31: 1.0 (DL+SIDL) + 0.8 [LL-(ELY+e)] Y 0.00072 2.2625 13 O.K.
Floor 03 B32: 1.0 (DL+SIDL) + 0.8 [LL+(ELY-e)] Y 0.00074 2.3250 13 O.K.
Floor 03 B33: 1.0 (DL+SIDL) + 0.8 [LL-(ELY-e)] Y 0.00071 2.2313 13 O.K.
Floor 02 B01: 1.0 (DL+SIDL+LL) Y 0.00001 0.0375 13 O.K.
Floor 02 B12: 1.0 (DL+SIDL+ELY) Y 0.00079 2.4750 13 O.K.
Floor 02 B13: 1.0 (DL+SIDL-ELY) Y 0.00079 2.4531 13 O.K.
Floor 02 B14: 1.0 [DL+SIDL+(ELY+e)] Y 0.00101 3.1688 13 O.K.
Floor 02 B15: 1.0 [DL+SIDL-(ELY+e)] Y 0.00103 3.2313 13 O.K.
Floor 02 B16: 1.0 [DL+SIDL+(ELY-e)] Y 0.00104 3.2531 13 O.K.
Floor 02 B17: 1.0 [DL+SIDL-(ELY-e)] Y 0.00103 3.2219 13 O.K.
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Storey Drift Limitation Check
Note:
Storey Drift is nothing but relative displacement between floors above and/or below
the storey under consideration. Storey drift in any story shall not exceed 0.004 times the storey
height, under the action of design base shear VB with no load factor that is, partial safety factor
for all loads taken as 1.0 which is nothing but service load combinations. The check is given
Calculations:
in Clause 7.11.1 of IS 1893 (Part-1): 2016.
as per Indian Standard 1893:2016 Clasue 7.11.1.1 Storey Drift Limitation
Storey Drift in any storey shall not exceed 0.004 times the storey height
Drift shown in ETABS is as Storey Drift / Floor Height
where, Height between slabs is 3.25 m i.e., 3250 mm
Allowable Drift = 0.004 × Storey Height = 0.004 × 3250 = 13 mm
hence, here Storey Drift for all storey is not exceeding 0.004 times the storey height for all Service Load Combinations
⸫ Check for Storey Drift Limitation is O.K.
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Torsional Irregularity Check
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Notes:
The designer should review the structural arrangement of the structural elements to
ensure that the code requirements against building irregularity will be satisfied. Building
Irregularity checks are depending on the code that we are using, although there are similarities.
The most common checks under a building irregularity are the torsional irregularity check
which will be tackled by applying check as per IS 1893: 2016 (Part-1) Clause 7.1 and Table
No. 5. The code states that the ratio of maximum horizontal displacement at one end minimum
horizontal displacement at another end should not exceed 1.5
Course: Design of RCC Building as per IS Codes by ETABS By, Akshay Thakur
Note:
This is Design check given by IS 456: 2000 in Clause 20.5; this check is regarding the deflection at top storey with respect to the height of
the structure where the clause states that under transient wind load the lateral sway at top should not exceed H/500, where H is the total height of
the building. Hence for Wind Load Check the Story Displacement for Top of the Structure
Calculations:
as per Indian Standard 456:2000 Clause 20.5 Lateral Sway at Top should not exceed H/500
here, H is the total height of building i.e; 17.5 meter at Head Room Slab Level ⸫ H = 17500 milimeter
& 14.25 meter at Head Room Slab Level ⸫ H = 14250 milimeter
⸫ for Top of Head Room Slab, H/500 = 17500/500 = 35 mm & for Terrace Level H/500= 14250/500 = 28.5
hence, here Lateral Sway at Top for Wind Load is within Acceptable Limits which is as per IS 456:200 Clause 20.5
⸫ Check for Lateral Sway is O.K.