Victaulic Firelock Igs Installation-Ready Style V9 Sprinkler Coupling
Victaulic Firelock Igs Installation-Ready Style V9 Sprinkler Coupling
Victaulic Firelock Igs Installation-Ready Style V9 Sprinkler Coupling
Patented
2.0 CERTIFICATION/LISTINGS
1 It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to the latest Victaulic Gasket Selection
Guide for specific gasket service guidelines and for a listing of services which are not compatible.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
10.65 11319 Rev C Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
1
victaulic.com
4.0 DIMENSIONS
Style V9 Sprinkler Coupling
Z Z
YL YL YB
YB
X X
Style V9 Pre-Assembled
Style V9 Joint Assembled
(Push On Condition)
Pipe End
Preassembled Assembled Joint
Actual Outside Separation Approx.
Nominal Diameter Allowable2 Qty. Size YL YB X Z YL YB X Z (Each)
inches inches inches inches inches inches inches inches inches inches inches inches lb
mm mm mm mm mm mm mm mm mm mm mm mm kg
1 x 1/2 1.315 x 0.840 .13 1.36 1.66 2.18 1.17 1.37 1.73 1.97 1.17 .36
1 5/16 × 1 1/8
DN25 DN15 33.7 21.3 3.3 34.6 42.1 55.3 29.7 34.7 44.0 50.0 29.7 .16
3/4 1.050 .13 1.36 1.66 2.18 1.17 1.37 1.73 1.97 1.17 .36
1 5/16 × 1 1/8
DN20 26.9 3.3 34.6 42.1 55.3 29.7 34.7 44.0 50.0 29.7 .16
1 1.315 .13 1.36 1.66 2.18 1.17 1.37 1.73 1.97 1.17 .36
1 5/16 × 1 1/8
DN25 33.7 3.3 34.6 42.1 55.3 29.7 34.7 44.0 50.0 29.7 .16
2 The allowable pipe separation dimension shown is for system layout purposes only. FireLock™ sprinkler couplings are considered rigid connections and will
not accommodate expansion or contraction of the piping system.
5.0 PERFORMANCE
Listings/Approval
The information provided below is based on the latest listing and approval data at the time of publication.
Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for
performance on other pipe and the latest listings and approvals.
Size UL FM
Nominal
inches psi psi
mm kPa kPa
1 x 1/2 250 175
DN25 DN15 1725 1205
3/4 175 175
DN20 1205 1205
1 175 175
DN25 1205 1205
10.65 11319 Rev C Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any
Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
10.65 11319 Rev C Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 3