Professional Documents
Culture Documents
Service Manual: Logamax Plus GB062
Service Manual: Logamax Plus GB062
GB062 - 14....
GB062 - 24....
2017/01_PRM-M21_U. Demir
Content
Content
6.8 Checking the expansion vessel . . . . . . . . . 50
1 Safety precautions and symbols . . . . . . . . . . . . . . . 3 6.9 Setting the heating system operating pressure
1 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 50
1.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . 3 6.10 Removing automatic air vent valve . . . . . . . 51
6.11 Checking the gas valve . . . . . . . . . . . . . . . 51
6.12 Removing the gas valve . . . . . . . . . . . . . . . 51
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.13 Remove the heating pump . . . . . . . . . . . . . 52
2.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.14 Removing the motor of the 3-way valve . . . 52
2.2 Before commissioning . . . . . . . . . . . . . . . . . . 4
6.15 Remove the heat exchanger . . . . . . . . . . . 52
2.3 Switching the appliance on/off . . . . . . . . . . . . 4
2.4 Setting the maximum flow temperature . . . . . 5
2.5 Setting the DHW temperature . . . . . . . . . . . . 5 7 Good to know . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.6 Setting summer mode . . . . . . . . . . . . . . . . . . 5 7.1 Integrated Weather Dependet Function (WDC) -
2.7 Short operating overview . . . . . . . . . . . . . . . . 6 Heat curve . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.8 Product Type Description . . . . . . . . . . . . . . . . 6 7.2 Boiler Frost protection . . . . . . . . . . . . . . . . 53
7.3 Air purging in central heating mode . . . . . . 53
7.4 Air Pressure Switch (APS) . . . . . . . . . . . . . 53
3 Service menu settings . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Operating the service menu . . . . . . . . . . . . . . 7
3.2 Service functions overview . . . . . . . . . . . . . . . 8 8 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2.1 Menu 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8.1 Mixing unit . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2.2 Menu 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8.2 Resonator & Burner . . . . . . . . . . . . . . . . . . 54
3.2.3 Menu 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 8.3 Venturi . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.4 Circulation Pump (ErP pump) . . . . . . . . . . . 56
4 Fault finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 Explanations of faults table . . . . . . . . . . . . . 15
4.2 Fault group definition . . . . . . . . . . . . . . . . . . 15
4.3 Faults and possible remedy steps . . . . . . . . 17
4.4 Faults that are not shown on the display . . . 40
2 Operation
2.2 Before commissioning
NOTICE: Commissioning without water will
destroy the appliance.
B Only operate the appliance once it has been
filled with water.
1 2 3 4 5 6 7
Fig. 2 Display
1 Burner operation
2 Fault display/standby mode display Fig. 3
3 Heating mode active
4 DHW heating active
5 Summer mode active
6 Service Mode
7 Temperature display (in °C)
The appliance has an anti-seizing function NOTICE: Heating system at risk through frost. In
which prevents the heating circuit pump and the summer mode, only the appliance is protected
3-way valve seizing up following long periods of against frost.
inactivity. B Observe frost protection measures where
The anti-seizing function remains active during there is a risk of frost.
standby mode.
To set summer mode:
2.4 Setting the maximum flow temperature B Keep pressing – until the symbol appears on the
The maximum flow temperature can be set between 40 °C display.
and 82 °C. The current flow temperature is shown on the B Press OK.
display. The set maximum flow temperature is displayed.
B Keep pressing – until the symbol appears on the B Keep pressing – until ... appears on the display.
display.
B Press OK to save the setting.
B Press OK.
is permanently displayed.
The set maximum flow temperature is displayed.
Additional instructions are contained in the operating instruc-
B Press + or – to set the required maximum flow
temperature. tions for the heating programmer.
B Press OK to save the setting.
The display shows the current flow temperature.
B Calling up a menu:
– Menu 1 (‡page 8)
– Menu 2 (‡ page 12)
– Menu 3 (‡ page 14)
B Press + or – to scroll through the menu's service
functions.
Making a setting
B Press OK to switch to the service function.
The value flashes on the display.
B Press + or – to set the required value.
Saving a setting
B Hold down OK until the selected service function appears
on the display.
3.2 Service functions overview B Hold down “Back”, + and – at the same time until L.1 is
shown on the display.
3.2.1 Menu 1 B Press OK to make settings in menu 1.
To call up a service function in this menu: B Press + or – to scroll through the menu's service
functions.
1.A Maximum output for cental heat- Some gas supply utilities charge a basic rate based on output.
ing
The output can be limited to the specific heat demand between the mini-
mum rated output and maximum rated output.
B Measure the gas flow rate and compare it with the information from
the setting tables. If they do not match, change the setting.
1.b Maximum output The output can be limited to the specific heat demand between the mini-
(DHW) mum rated output and maximum rated output.
B Measure the gas flow rate and compare it with the information from
the setting tables. If they do not match, change the setting.
1.E Pump mode Pump mode (pump run while burner off)
0 = as mode 2, but automatic selection
of mode 4
if outdoor sensor detected
1 = off after pump overrun
2 = depends on room thermostat
3 = depends on outdoor control
2.b Maximum flow temperature The maximum flow temperature can be set to between 30 °C and 82 °C.
2.C Venting function The venting function can be activated after maintenance.
This service function activates the heating of the DHW cylinder to 75 °C.
B Implement thermal disinfection as described.
2.F Operation Mode volatile With this service function, you can temporarily change the appliance
operating mode.
2.J Central heating / Storage tank Anternating mode for 10 minutes betweens both mode.
alternating mode (system boiler)
Setting range: 0 - 1
Default setting : 0 minutes.
3.A Automatic ant-cycle mode 0 : 0ff, 1 : on (installation with weather depanded controls)
Default setting : 0
3.b Time interval for starting and The time interval determines the minimum delay between the burner
stopping (anti-cycle) the burner stop and restart (only active, if 3.A = 0).
(in CH mode)
Setting range: 1 to 10 minutes.
Default setting : 3 minutes.
3.C Temperature differential for The temperature differential determines the level by which the flow tem-
stopping and restarting the perature must drop below the set flow temperature before the drop is
burner (Hysterisis) (via CHNTC) interpreted as a heat demand. Settings in 1 K steps are possible.
Default setting : 5 K.
3.F Domestic hot water standby Heating mode is disabled for this period of time following DHW heating.
time after tapping during CH Setting range: 0 - 30 minutes.
mode (Combi version) Default setting : 1 minutes.
Tab. 3 Menu 1
4.b max pre heat temperature for max DHW pre heat temperature for comfort function.
comfort function (combi)
The following settings are possible:
• 40 … 65 ºC
Default setting : 62 º
4.E Boiler type It will be detected automaticly of DHW or tank NTC and shown in display.
Possible values:
• 0 : only heating
• 1 : Combi
• 2 : Tank with NTC (system boiler)
5.A Reset service reminder If you see this symbol, you can reset to “0” after inspection.
5.b Fan overrun time Time intervall for the maintanence (month)
0 = Off
1 .. 72 = Time (Month)
5.F Inspection intervall If you see this symbol, you can reset to “0” after inspection.
6.A Calling up the last fault saved The function enables you to retrieve the last fault stored.
6.d Current turbine flow rate (combi) The current turbine flow rate is displayed.
7.E Building dry function The building drying function of boiler doesn’t corresponds to the dry func-
tion of the weather depended controls.
In case of activation of this function, DHW and chmniy sweep function is
no tpossible. During this period you can the symbol (dr) in display.
The following settings are possible:
• 00: Off
• 01: On
P.1 Setpoint B of the heat curve for 20 ... 50 : Flowtemperature (set point)
WDC
P.2 Setpoint A of the heat curve for 50.. 88 ... 90: Flowtemperature (set point)
WDC
Default setting : 0.
Default setting : 0.
Tab. 3 Menu 1
8.E Returning the appliance to its This service function enables you to reset the appliance to its standard set-
standard settings tings.
Setting 00.
9.A Permanent operating mode This function permanently sets an operating mode.
Default setting : 0.
9.E Signal turbine delay Through spontaneous pressure change in the water supply, the flow meter
(Combi version) (turbine) can signal that water is being drawn off.
This means the burner starts briefly although no water is drawn off.
The turbine signal delay can be set from 1 to 8. One step corresponds to
0.25 seconds.
Default setting : 4 (0,25 seconds).
9.F Heating circuit pump overrun time The pump overrun time is started by the control system at the end of the
heat demand.
The following settings are possible:
• 1 to 10: overrun time in minutes (steps of 1 minute)
A.A Temperature at flow temperature This service function allows you to display the temperature at the flow tem-
sensor perature sensor.
Tab. 4 Menu 2
A.b DHW temperature (Combi version) This service function allows you to display the DHW temperature.
A.C Temperature at cylinder tempera- This service function allows you to display the temperature in the DHW cyl-
ture sensor (system version) inder.
b.F DHW heating delay (solar mode) Heating will be suppressed until the DHW temperature sensor detects that
the water preheated by solar energy has reached the required outlet tem-
perature. Set the heating delay in accordance with system conditions.
E.1 Appliance type, output, DHW heat- This service function allows you to adjust the control unit to the appliance
ing (soft code) output and the type of DHW heating (see table below regarding the code list
for this service function). This is only necessary when the control unit is
replaced.
F.1 Gas Type With this service functlon is changed the gas type.
B To change the actual gas type, press + and - button together until the
scroll up/down symbol is shon in display.
• 0 : Naturalgas
• 1 : Liquidgas (LPG)
Tab. 5 Menu 3
Code List for the Service function E.1 :
This parameter is only available/active for the
spare part change. By origin PCB (electronic
Soft card) this function is only visible.
Country Definition of Appliance Code
This parameter should be adjusted by each
TR (Turkey) GB062-22 KD ... 21 PCB-Change regarding the TTNr. (Codelist is in
IT (Italy) GB062-24 (K) ..... 22 PCB included).
GB062-24 KD ... 23
GB062-14 ... 24
GB062-14 ... 29
GB062-24 KD .... 28
GB062-24 KD ... 28
GB062-14 .... 29
GB062-24 KD ... 26
GB062-14 .... 30
GB062-24 .... 25
Tab. 6 Code table for the service function E.1
4 Fault finding
Cause Failure
Failure Code Code Category Failure description Page
3Y 334 WAIT The differential pressure switch is open before ignition (during self 20
check) (only high modulation version).
4C 224 LOCK - Heat exchanger temperature limiter or flue gas temperature limiter has 30
tripped.
- The differential pressure switch does open when the fan runs (after
ignition) (only high modulation version).
6C 228 LOCK Flame detected even when the burner is switched off. 36
EP 327 LOCK The “OK” button was actually pressed for at least 5 seconds (= reset). 38
CL
Hot water temperature sensor (DHW-NTC) is faulty.
Step Remedy
-->3.
3. Check the cables for damages. yes: B Change the cable haarness.
B END
5L
BUS-Communication fault
Step Remedy
--> 2.
2. B Check the connections between the yes: B Switch on the boiler.
control (thermostat) and the boiler.
B Cut the main voltage supply.
Is resistance very high ?
B Change the connection cable between boiler and
control (thermostat).
5L on display ? --> 2.
no: --> 3.
B END
CP
System boiler: Cylinder / tank temperature sensor.
Step Remedy
-->3.
3. Check the NTC cables. yes: B Change the cable/NTC.
-->4.
no: --> 4.
B END
3Y
The differential pressure switch is open before ignition (during self check) (only high modulation version).
Steps Remedy
1. Check the contacts of diff. pressure yes: B Change the diff. pressure switch.
switch.
B Switch on the boiler.
B Switch off the boiler. 3Y ? -->2.
B Check the connection of diff. pressure no: B Connect the diff. pressure switch again.
switch.
B Switch on the boiler.
B Measure the circuit with a instrument. -->2.
The circuit /contact should be closed.
Is there any blockage or stuck on silikon B Change the silicon hose or correct the stuck.
hose ?
B Switch on the boiler.
3Y ? -->3.
no: -->3.
3. Check the low voltage cable for damages yes: B Change the low valtage cable.
or open circuit.
B Switch on the boiler.
B Switch off the boiler.
3Y ? --> 4.
B Remove the connection of PCB and
no: --> 4.
measure the circuit of the diff.
pressure switch.
B END
3C
Fan doesn't reach to start fan speed.
Step Remedy
1. Are the both fan cable (power and PMW yes: --> 2.
signal) correct connected ?
no: B Switch off the boiler.
3C ? --> 4.
no: --> 4.
B END
2E
Heating system charge pressure is too low (<0.5 bar). Water pressure switch is triggered.
Step Remedy
no: --> 2.
2. Check the manometer and manometer yes: B Switch off the boiler.
pipe. Is it defect or blocked ?
B Change the manometer.
no: --> 3.
2E ? --> 4.
4. Check the water pressure switch and yes: -- > 5.
the connection cable for damages,
no: B Switch off the boiler.
blockage or open circuit.
Is it correct ? B Change the water pressure switch or correct the
cable connection.
2E ? --> 5.
2E
Heating system charge pressure is too low (<0.5 bar). Water pressure switch is triggered.
Step Remedy
B END
8Y
External switching contact triggered.
Step Remedy
8Y ? --> 2.
2. B Switch off the boiler. yes: --> 3.
3. B Check the external temperature lim- yes: B Check the connection at limiter and fasten the screws
iter measure the circuit. very well.
Is the circuit open?
B Switch on the main voltage supply.
8Y ? --> 4.
no: --> 4.
4. B Switch off the boiler. yes: B Repair or change the connection cable.
B Cut the main voltage supply. B Switch on the main voltage supply.
--> 5.
8Y
External switching contact triggered.
Step Remedy
8Y ? --> 6.
no: --> 6.
8Y ? --> 7.
7. External temperature limiter is locked or B Switch off the boiler.
defect ?
B Cut the main voltage supply.
4Y
Flow temperature sensor (CH-NTC) faulty.
Step Remedy
2. Check the NTC cables for damages. yes: B Change the cable haarness.
B END
4C
- Heat exchanger temperature limiter or flue gas temperature limiter has tripped.
- The differential pressure switch does open when the fan runs (after ignition) (only high modulation version).
Step Step
4C ? --> 2.
2. Is the circulation pump blocked or yes: B Remove the blockage (turn the pump shaft).
problem voltage supply ? If no result :
4C ? --> 3.
no: --> 3.
3. Are the flue gas temperature limiter yes: B Switch off the boiler.
(STB) cables disconnected ?
B Connect the cables.
4C ? --> 4.
no: --> 4.
4. B Switch off the boiler. yes: B Change the flue gas temperature limiter (STB).
--> 5.
4C
- Heat exchanger temperature limiter or flue gas temperature limiter has tripped.
- The differential pressure switch does open when the fan runs (after ignition) (only high modulation version).
Step Step
4C ? --> 6.
no: --> 6.
6. B Switch off the boiler. yes: B Change the heat exchanger temperature limiter (STB).
--> 7.
B Remove the front cover and first no: B Clean the WB6. Check the burner, upper and down
visual check of main heat exchanger buffels (inside WB6). If there any damages on WB6,
(WB6) for damages, corrosions or change it.
rippen effect.
B Refill the system with water.
B Measure the actuating pressure for
B Switch on the boiler.
the maintenance necessity (Steuer-
druck). if the pressure not OK. Clean --> 8.
the WB6 (see capital in IM for the
maintenace pressure).
B Check the connection cables and the no: B Correct the cable or connection. If necessary, change
diff. pressure switch itself. the diff. pressure switch.
4C
- Heat exchanger temperature limiter or flue gas temperature limiter has tripped.
- The differential pressure switch does open when the fan runs (after ignition) (only high modulation version).
Step Step
B Check the flue gas 6Apipe/system yes: B Correct the flue gas installation (remove the blockage).
for blockage (In case of blockage,
B Switch on the boiler.
due to high pressure the contacs of
diff. presure switch is opening--> 4C) --> 10.
B END
6A
Flame not detected.
Step Remedy
2. Check / measure the ionisaiton cur- yes: B Switch off the boiler.
rent.
Is it correct ? B Cut the m6Aain supply.
--> 3.
6A ? --> 3.
3. Is gas valve open ? yes: --> 4.
6A ? --> 4.
4. Is there air in the gas line ? yes: B Open the gas valve.
6A ? --> 5.
no: --> 5.
5. Is the termal gas valve triggered ? yes: B Replace the thermal gas valve.
(if a termal gas valve is installed) B Press the RESET button and start the boiler again.
6A ? --> 6.
no: --> 6.
6A
Flame not detected.
Step Remedy
6A ? --> 7.
no: --> 7.
6A ? --> 7.
7. Is the siphon blocked ? yes: B Clean or correct the siphon.
--> 8.
no: --> 8.
8. Is the gas valve robust ? yes: B Connect the cable socket again.
B Disconnect the cable socket. B Press the RESET button and start the boiler again.
6A ? --> 9.
6A
Flame not detected.
Step Remedy
9. B Enter into the 2. service level. yes: B Press the “Return” button twice to exit the service
mode.
B Call the service function 8.F
Is the permanent ignition (without gas) -->10.
correct ?
no: B Press the service button twice to exit the service
mode.
-->10.
10. Ist the cable connected to the ignition yes: -->10.
electrode ?
no: B Connect the ignition cable to the electrode.
6A ? -->10.
11. Is the ignition cable connected correctly yes: -->11.
to the control unit ?
no: B Switch off the boiler.
6A ? -->11.
12. Ionization cable damage ? yes: B Switch off the boiler.
6A ? --> 12.
no: --> 12.
13. Check the ignition electrodes. yes: B Change the ignition electrodes.
B Remove (dismount) the ignition B Press the RESET button and start the boiler again.
electrodes.
6A ? --> 14.
Is the electrode worn or dam-
aged? no: B Install the ignition electrodes.
6A ? --> 14.
6A
Flame not detected.
Step Remedy
14. B Switch off the boiler. yes: B Install the diaphragm correctly in mix-unit again.
6A ? --> 15.
15. Check the gas-air ratio setting (max): yes: 6A ? --> 16.
B Remove the cap in the flue gas no: B In case of deviation, correct the gas adjustment.
measuring point.
6A ? --> 16.
B Activiate the permanent max opera-
tion mode (chimniy sweeper) via serv-
ice function 2.F3.
16. Check the gas-air ratio setting (min): yes: 6A ? --> 17.
B Remove the cap in the flue gas no: B In case of deviation, correct the gas adjustment and
measuring point. close the cap again.
17. B Switch off the boiler. yes: B Clean the flue gas system (maintanance).
6A ? --> 18.
6A
Flame not detected.
Step Remedy
18. Fresh air flow rate is too low ? yes: B Check the flue gas system for lengths, elbows
quantity, extension pipe and other accessories. If
needed, correct/change it.
6A ? --> 19.
no: 6A ? --> 19.
19. B Switch the boiler to max operating yes: B Switch off the boiler.
mode via service function 2.F3.
B Clean the main heatblock (WB6).
B Measure the actuating pressure for
B Switch on the boiler.
the maintenance necessity (Steuer-
druck) (see capital in IM for the main- 6A ? --> 20.
tenace pressure).
no: 6A ? --> 20.
Is the actuating pressure (Steuer-
druck) in heat exchanger (WB6)
correct ?
B END.
EC
Internal fault (Internal fault in the program sequence or failure of the mains voltage).
Step Remedy
1. Is blinking error code in display ? yes: B Reset the boiler and restart the boiler again.
EC ? --> 2.
no: --> 2.
2. B Switch off the boiler. yes: B Change the ignition cable and the connection or if
possible fix it.
B Is the ignition cable connection loose
or damaged ? B Switch on the boiler.
EC ? --> 3.
no: --> 3.
EC ? --> 4.
4. B Switch off the boiler. yes: B Change the connection cable to securty valve.
B END.
6C 228
Flame detected even when the burner is switched off.
Step Remedy
B END.
6C 306
After switching gas off : Flame is detected.
Step Remedy
6C ? --> 2.
2. Cable harness is defect. B Switch off the boiler.
6C ? --> 3.
3. Electronic board (PCB) is defect. B Switch off the boiler.
EP
The “OK” button was actually pressed for at least 5 seconds (= reset) or short circuit form low voltage cable to the
frame.
Step Remedy
yes: B Press the RESET button and start the boiler again.
EP ? --> 3.
2. Check the low voltage cable (STB, gas B Switch off the boiler.
valve cable) for short circuit to the frame.
B Cut the main voltage supply.
(Gradient Monitoring)
Rapid overshooting of the flow water temperature (Gradient control) (Heating circuit is blocked for 2 min.)
Step Remedy
B END.
P
Appliance not defined.
Step Remedy
B END.
Water circulation noises B Set the pump rate or pump characteristic map correctly
and match it to the maximum performance.
Heat-up lasts too long B Set the pump rate or pump characteristic map correctly
and match it to the maximum performance.
Flue gas readings incorrect; CO content too high B Check gas type.
Condensate in air box. B Check diaphragm in the mixer unit, replace if required
DHW volume not reached. B Check the DHW water inlet pressure.
No function, the display remains dark. B Check electrical wiring for damage.
Temperature ( °C)
5.1.1 Domestic hot water temperature Sensor
Measure Tolerance ± %10 Resistance ( Ω)
Temperature ( °C) -20 95893
Measure Tolerance ± %10 Resistance ( Ω) -15 72228
0 28704 -10 54889
10 18410 0 32506
20 12171 10 19860
25 10000 20 12486
30 8269 30 8060
35 6881 5.1.4 Buderus Outdoor Temperature Sensor
40 5759
45 4847
50 4101
55 3488
60 2981
65 2559
70 2207
75 1912
80 1662
85 1451
90 1272
Tab. 10 Domestic hot water temperature Sensor
5.3.1 GB062-24K....
1 Gas valve EV1 (Pin : 3-4) 100 Ohm ±10 Supply 24 VDC
Ohm
EV2 (Pin : 1-3) 230 Ohm
Service
Func- Toler-
Pos. Description Measurement Point Expected value tion ance Remark
7 Flowrate sensor Cable colour : black / 1,5 l/min. = 5 Hz 6.d ± 2 Hz Supply : 4,5 - 13
(Turbine) white / grey Output current :
10 l/min. = 33 Hz
15 mA
15 l/min. = 50 Hz
Tab. 12 Electrical values
B Before carrying out work on electrical components, isolate B Check all joints for leaks.
them from the power supply (230 V AC) (fuse, circuit B Check the gas/air ratio.
breaker) and secure against unintentional reconnection.
6.2 Check the heat exchanger 2. Press the locking device onto the mixer unit, rotate it down-
ward, and remove the mixer unit by pulling it forward.
B Remove the casing.
B Remove the cap from the test nipple, and connect a pres- 1.
sure gauge.
2.
CAUTION : 4.
Risk of burns due to hot surfaces! 3.
Individual components of the boiler can become
1.
very hot even after being shut down for a long
time.
Use accessory no. 1156, part no. 7 719 003 006, comprising Fig. 9 Removing the Fan
a brush and removal tool, to clean the heat exchanger. B Remove electrode set with gasket and check electrodes
1. Remove the suction line. for contamination : clean or replace, if required.
B Remove burner.
B Refit the displacement bodies. B Make sure that the condensate drains cor-
rectly.
B Remove the condensate trap and place a suitable con-
tainer below.
B Flush out the heat exchanger with water from the top.
1. 2.
O
H2
6 720 611 626-85.2O
3.
0 010 005 831-001
6.6 Checking the strainer in the cold water pipe 6.7 GB062..K.. (Combi) appliances: Check the
B Remove the clip. plate heat exchanger
B Pull out the pressure relief valve. If the DHW output is insufficient :
1.
2.
0 010 006 637-001
B Top up the water until the indicator is between 1 bar and 2 6.12 Removing the gas valve
bar again. B Close the gas valve.
If pressure is not being maintained :
1. Remove the clip.
B TCheck expansion vessel and heating system for leaks. 2. Open the lockings system on the gas pipe.
3. Remove the gas pipe.
6.10 Removing automatic air vent valve
4. Pull plug (24 V) from the gas valve
1. Remove the clip.
5. Unscrew the nut.
2. Remove the automatic air vent valve.
1.
2.
2.
1.
1.
3.
3
1
4
2x
2.
1.
2.
3.
Fig. 25 4.
6.14 Removing the motor of the 3-way valve
3.
1. Undo clip. 0 010 005 852-001
2. Remove the motor of the 3-way valve. Fig. 27 Remove the flow pipe and disconnect the cable
1. 2.
1.
0 010 006 640-002 3.
Fig. 26
B Press the cable restraint and remove the plug.
7 Good to know
7.1 Integrated Weather Dependet but goes on after DHW request. Pump is switching on
Function (WDC) - Heat curve and off every 20 seconds.
Weather dependet function (WDC) can activated via
service funtion 1.P.0.
Following parameter A, B and S can be adjustet.
8 Components
8.3 Venturi
Fig. 36 Pump_LEDs