4 Monunting............................................................................................................................................15
4.1 Mounting of the control unit........................................................................................................... 15
4.2 Mounting of the sensors................................................................................................................ 15
4.3 Cables........................................................................................................................................... 17
4.3.1 Sensor cables ........................................................................................................................... 17
4.3.2 Power supply / Control cables .................................................................................................. 17
6 Start-up ................................................................................................................................................23
6.1 Keys and indicators....................................................................................................................... 23
6.2 Allocation and function of keys ..................................................................................................... 24
6.3 Switching on and Powering up...................................................................................................... 24
6.4 Operational conditions .................................................................................................................. 25
6.4.1 Undisturbed operation .............................................................................................................. 25
6.4.2 Detection of 0-sheet, 1-sheet or 2-sheet .................................................................................. 25
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
3
Manual
8 Maintenance ........................................................................................................................................35
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
4
Manual
Roland Electronic GmbH declare that the product listed above complies with the requirements of
the EMC directives listed below.
Applied Directives:
2004/108/EU: Generic emission standard;
EN61000-6-2: 2005 EN61000-6-4: 2001
The declaration confirms the compliance with the cited directives. However, it is not any implied warranty of fitness for a
particular purpose especially as it may relate to product liability.
The safety instructions and warnings must be observed.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
5
Manual
Blank page
Pos: 4 /Kapitelübersicht/01. Sicherheitshinweise @ 0\mod_1121421059859_501.doc @ 505
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
6
Manual
1 Safety advices
Pos: 5 /Doppelblech/Geräte/R100/1 Sicherheitshinweise/Allgemeines zu diesem Dokument @ 0\mod_1184842595390_501.doc @ 4065
1.1 General
This document was created with utmost care. Anyhow, faults and cases of misunderstanding
cannot be totally excluded. Please contact us in case of differences or weak understanding. We will
be pleased to assist you.
We reserve the right to improve this document at any time without announcement. No exchange of
delivered documents.
Note The factory pre-settings – especially the upper / lower limit values – have
been chosen such that an optimal machine protection is ensured.
Diverging settings can impair the machine protection.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
7
Manual
Blank page
Pos: 8 /Kapitelübersicht/02. Systembeschreibung @ 0\mod_1121421150062_501.doc @ 507
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
8
Manual
2 System description
Pos: 9 /Doppelblech/Geräte/A100 / I100/2 Systembeschreibung/A100/Einführung @ 0\mod_1184844531515_501.doc @ 4080
2.1 Introduction
When automatically feeding sheets from a stack to a processing machine, it can unintentionally
happen that more than one sheet is picked up and transported. This can result in damage to the
machine, tool damage, expensive repairs and production loss. The A100 double sheet detectors
can reliably prevent from such incidents by measuring the thickness of every sheet with a single
probe sensor.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
9
Manual
Note! “Active“ means, that the signal output will switch. In case the supply
voltage fails, all signal outputs (0-, 1-, 2-sheet) will become inactive.
The PLC must then stop the material transport.
Caution! Usually, the signal outputs of the control unit will be used for stopping
the material transport facilites and / or machines in case of double
sheet.
As soon as the double sheet is removed from the sensor(s), the signal
outputs revert instantly to normal conditions (0-sheet / 1-sheet).
Suitable control measures must ensure that the previously stopped
material transport facilites and / or machines cannot automatically
restart and thus create hazardous situations.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
10
Manual
3 Technical data
Pos: 14 /Doppelblech/Geräte/A100 / I100/3 Technische Daten/A100/Auswertegerät A100 @ 0\mod_1184852330828_501.doc @ 4187
125,4
fault 2 sheet
power 1 sheet
0 sheet
103
46,5
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
11
Manual
Description
Deckel / Lid
30
1 Screw fitting M16
for control cable
Wrench size 19 mm
2 Screw fitting M12
90
for sensor cable
M16×1,5 M12×1,5
Wrench size 15mm
SW 19 SW 15
40
114
90,5
148
154
160
135
fault 2 sheet
power 1 sheet
0 sheet
1 2
4,2 Ø
35
38
120
Fig. 2: Dimensions of A100-IP65 (in protective enclosure IP65) A100 in multibox IP65.wmf
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
12
Manual
3.2 T sensors
The sensors are available either with fixed cable or plug connector.
The pluggable version has the addition S (e.g. T15 -> T15S)
For all sensors: Ambient temperature 0 – 50 °C (during operation)
The useful sheet thicknesses depend very much on the properties of the material to be measured,
they can deviate from the values stated below.
Technical data
Single sheet thickness: min. 0,04 mm max. 0,4 mm (.016 in.)
Min. adhesive force on axial tear-off 1,5 kg (3.3 lbs.)
Weight: 0,15 kg (.33 lbs.)
Technical data
Single sheet thickness: min. 0,08 mm max. 0,8 mm (.032 in.)
Min. adhesive force on axial tear-off 8 kg (17.6 lbs.)
Weight: 0,32 kg (1.45 lbs.)
Technical data
Single sheet thickness: min. 0,1 mm max. 1,5 mm (.06 in.)
Min. adhesive force on axial tear-off 15 kg (34 lbs.)
Weight: 0,38 kg (.83 lbs.)
Technical data
Single sheet thickness: min. 0,2 mm (.012 in.) max. 3,0 mm (.12 in.)
Min. adhesive force on axial tear-off 35 kg (77.2 lbs.)
Weight: 1,1 kg (2.43 lbs.)
Technical data
Single sheet thickness: min. 0,3 mm (.01 in.) max. 4,0 mm (.16 in.)
Min. adhesive force on axial tear-off 55 kg (122 lbs.)
Weight: 2,3 kg (5.1 lbs.)
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
13
Manual
55 60
80
100
47
50
2 1
ws (weiß / white) [1]
gn (grün / green) [2]
br (braun / brown) [3]
ge (gelb / yellow) [4]
ge-gn (gelb-grün / yellow-green)
[Schirm / Shield]
3 4
Fig. 4: Allocation of sensor cable KS Kabel_KS.wmf
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
14
Manual
4 Monunting
Pos: 21 /Doppelblech/Geräte/R100/4 Montage/Montage des Gerätes @ 0\mod_1184845853703_501.doc @ 4100
Sensors with different sizes are available. The size determines the thickness measuring range and
the magnetic force of attraction. This force is proportional to the thickness of the measured sheet
metal.
When removing the sensor off the sheet or putting it on, the force of attraction must be overcome
by mechanical, hydraulic or pneumatic means. The force of attraction can be reduced by creating a
small air gap between sensor and sheet metal (recessed installation, use of a roller block).
Mounting:
The place of mounting depends on the destacking and feeding equipment. In principle a distance of
more than 0.5m must be kept from magnetic/electromagnetic interference sources like e.g. valve
coils, transportation magnets, inductive proximity switches or the like.
The sensor can be mounted in any direction, either over or under the sheet metal.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
15
Manual
Recommendable are:
• Flush mounting into the material slide either tight fit or interference fit.
Advantage: no wear and no deposite of chips and particles.
Recessed installation is possible; however, care should be taken that no chips and
particles collect in the recess (possibly fill up recess with non-ferrous-magnetic material).
• Spring suspended sensor bracket for use with thick sheet metals.
Advantage: the sensor can adapt to bowed sheet metal, thus avoiding unintended air gaps.
The minimum dwell time of the sheet metal on the sensor is 15ms.
Note! If the sensor is used for double sheet detection of preformed sheet
metals, an air gap between first and second sheet can develop; thus
the double sheet condition might not be detected. This must be
considered when selecting the place for mounting the sensor, select
the next larger sensor if the occasion arises.
Opposite of the sensor face there must be no other ferromagnetic
material within the distance of 1.5 x sensor diameter, because this will
severely affect the measurement. The diameter of the sensor should
correspond to the minimum measuring area of the sheet.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
16
Manual
4.3 Cables
All cables must be professionally installed. Bending radii (see data sheets of manufacturer) must
be adhered. The cables must be protected from chafing and buckling by suitable installation.
Damaged cables must not be used and need to be replaced immediately.
If the recommended cables cannot be used (e.g. due to missing UL/CSA approval), substitutes
should be cleared with Roland Electronic.
Note! Keep the sensor cables as well as the power supply / control cable
away from unshielded cables with strong electro magnetical
interference potential (e.g. servo motor and power cables).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
17
Manual
Blank page
Pos: 25 /Kapitelübersicht/05. Elektrische Installation @ 0\mod_1121421905234_501.doc @ 509
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
18
Manual
5 Electrical installation
Pos: 26 /Doppelblech/Geräte/R100/5 Elektrische Installation/Allgemeines @ 0\mod_1185267326656_501.doc @ 4329
The system should be installed only by professional electricians. The cables must correspond with
the specifications stated in section „Cables“.
The required supply voltage is 24 V DC and should be supplied from the associated machine
controls.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
19
Manual
+ VH
– VH
+ IH
– IH
+24V COMMON
2-Blech / 2-sheet
1-Blech / 1-sheet
0-Blech / 0-sheet
Schirm / shield
braun / brown
PE green-yellow
gelb / yellow
grün / green
weiß / white
grün-gelb
Teach-In
+24 V
GND
zur SPS
to PLC zum Sensor
to sensor
4 5 6 7 8
+24V max.
Teach-In
2-Blech
1-Blech
0-Blech
2-sheet
1-sheet
0-sheet
COMMON
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
20
Manual
+ VH
– VH
+ IH
– IH
+24V COMMON
2-Blech / 2-sheet
1-Blech / 1-sheet
0-Blech / 0-sheet
schwarz / black
braun / brown
PE green-yellow
weiß / white
blau / blue
grün-gelb
Teach-In
+24 V
GND
zur SPS
to PLC zum Sensor
to sensor
Fig. 8: Connecting diagram for A100 for sensors T…GS and cable KTGS-G A100 anschlussleiste kabel KTGS-G.wmf
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
21
Manual
Blank page
Pos: 29 /Kapitelübersicht/07. Inbetriebnahme @ 0\mod_1121421999890_501.doc @ 511
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
22
Manual
6 Start-up
Pos: 30 /Doppelblech/Geräte/R100/6 Inbetriebnahme / Bedienung/Bedienelemente und Anzeigen @ 0\mod_1184848094000_501.doc @ 4115
Description
1 1 LCD display
2 Operating keys
3 LEDs for condition of unit
FAULT malfunction
POWER power supply
4 LEDs for switch conditions
2 2-Sheet
1-Sheet
0-Sheet
fault 2 sheet
3 power 1 sheet 4
0 sheet
Pos: 31 /Doppelblech/Geräte/R100/6 Inbetriebnahme / Bedienung/Belegung und Funktion der Tasten @ 0\mod_1184849242203_501.doc @ 4130
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
23
Manual
Note! If a function causes a fault, a fault number is indicated and the yellow
LED "FAULT" lights.
The error condition can be confirmed with the right "ENTER" key.
Otherwise the system changes to the measuring mode after approx 5
seconds. The “FAULT” LED will, however, go off only if upon a new
attempt the requested function is fault free.
If a function consists of several steps, which are not completely
executed, the system automatically changes back to the original
measuring mode after approx. 5 seconds.
Roland
Electronic GmbH
and then
The unit changes automatically to the measuring mode and will work with the last taught values.
1
Depending on software version
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
24
Manual
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
25
Manual
In the measurement mode the current measurement value and the switching thresholds will be
shown.
Since the display shows the actual measurement value as well as the set switching thresholds, it
can easily be checked whether the thresholds are correctly set.
2-sheet threshold:
The threshold for 2-sheet should be selected such that it is located slightly above the normal
variation range for 1-sheet, but will be significantly exceeded in case of 2-sheet so that 2-sheet will
be securely detected.
0-sheet threshold:
The threshold for 0-sheet should be selected such that it is located slightly below the normal
variation range for 1-sheet, but will be significantly exceeded in case of 0-sheet so that 0-sheet will
be securely detected.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
26
Manual
6.6 Teach-In
This function is useful in case of changing material or upon initial commissioning.
The system is in the measurement mode.
Attention! The function must not be used, if threshold values other than the
standard values (85% / 115%) are used. This function deletes the
modified values and uses the standard values instead.
Step 1
Step 2
Note! If the Teach-In fails, the previous thresholds stay active. The yellow
“FAULT” LED lights until the next Teach-in is successfully performed.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
27
Manual
Note! If this function is executed, the external Teach-In will also work with
the changed values.
Step 1
Step 2
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
28
Manual
Step 3
Step 4
The sign “!“ before “L“ indicates that the value L can be changed.
Step 5
Fig. 19: Selecting the upper threshold value U and changing the value R100TChangeHandNext.bmp
Step 6
Closing the setting:
With the key „exit“ the values are stored. The system changes over to the measurement mode. The
changed thresholds will be used from now on.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
29
Manual
Step 1
Step 2
Step 3
Has the function been executed, the system automatically changes to the measurement mode and
shows the new thresholds. If the function could not be executed, a fault message appears in the
LCD display.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
30
Manual
Step 1
Switch the input “Teach-In“ (terminal 4) to GND for a short time (see section “connection diagram“).
After that the signal outputs “1-sheet“ AND “2-sheet“ activated as feedback.
Step 2
Again switch the input “Teach-In“ (terminal 4) to GND for a short time. The teach-In will then be
performed.
If the Teach-In was successful, the system releases the measurement result “1-sheet“ and
automatically switches over to the measurement mode.
Note! If the second step is not performed, the system reverts back to the
measurement mode after approx. 5 seconds without any changes.
If the Teach-In was not successful, the signal outputs “1-sheet“ and “2-sheet“ will stay active for the
present. Furthermore, an error message will be shown on the LCD indication and the yellow
“FAULT” LED will be actuated.
The error message will disappear after approx. 5 seconds, and the outputs “1-sheet“ and “2-sheet“
will be de-activated. The system then automatically reverts back to the measurement mode.
Measurements are performed with the currently existing Teach-In value.
The “FAULT” LED will go off only if a new Teach-In has been succesful or if the system is re-
started by recycling power.
Note! The external Teach-In will always be performed with the last valid
thresholds.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
31
Manual
Blank page
Pos: 40 /Kapitelübersicht/09. Fehlermeldungen @ 0\mod_1121422043093_501.doc @ 513
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
32
Manual
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
33
Manual
Blank page
Pos: 43 /Kapitelübersicht/10. Wartung @ 0\mod_1121422080015_501.doc @ 514
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
34
Manual
8 Maintenance
Pos: 44 /Doppelblech/Geräte/R100/10 Wartung/Allgemein A100 @ 0\mod_1184851819781_501.doc @ 4165
Due to the use of a permanent magnet inside the sensor, chips and metal particles can accumulate
at the sensor. Thus the sensor must be cleaned from time to time.
In case of heavy abrasion the sensor can wear out. It must be replaced, if the sensor face begins to
show small punctures.
A sensor and a sensor cable should be kept on stock as spare parts.
When ordering spare parts, always state the serial number, the order information and the part
number (if available).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
35
Manual
Blank page
Pos: 46 /Kapitelübersicht/12. Bestelldaten @ 0\mod_1121422152468_501.doc @ 516
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
36
Manual
9 Order data
Pos: 47 /Doppelblech/Geräte/R100/12 Bestelldaten/Bestelldaten A100 @ 0\mod_1184851519046_501.doc @ 4160
Control unit
Order information Comment
A100 Control unit, for use with single probe sensors,
supply voltage is 24 V DC.
A100-IP65 Control unit, for use with single probe sensors,
supply voltage is 24 V DC,
mounted in a protective enclosure (IP65).
Sensors
Order information Comment
T04 Fixed cable for terminal block wiring.
Standard cable length is 2 meters, lengths up to 20 meters made to order.
T08
T15
T30
T40
T08S With plug connector for connecting the sensor cable
(order cable KS separately).
T15S
T30S
T40S
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
37
Manual
Blank page
===== Ende der Stückliste =====
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33