Description: CS1 SERIES-OPERATION MANUAL (EN) - 2013-01-04 1 / 31
Description: CS1 SERIES-OPERATION MANUAL (EN) - 2013-01-04 1 / 31
■ FUNCTION DEFINE
■ Character Symbol ■ Display Functions
A b C d E F G H i J K L M Max / Mini recording:
a b c d e f g h i j k l m In order to review & trace the drifting PV, the meters
will keep the values of maximum and minimum in [user
n o P q r S t U v W X y Z level] during power on.
n o p q r s t u v w x y z Display function [dsply] for display screen
The [dsply] function in [input group] can be set
1 2 3 4 5 6 7 8 9 0 / . to show present value pv, Maximum Hold maXhd
1 2 3 4 5 6 7 8 9 0 / . or Minimum Hold miNhd or Remote display by RS485
command rs485. Please refer to following for detail.
■ Input & Scaling ● Present value pv
Input type [aItyp] for CS1-PR Display screen will show the value that is relative to
Programming range: Voltage:0~10V/0~5V/1~5V; input and [ lOsc](Low scale) and [ hIsc] (High scale)
setting.
Current: 4~20mA/0~20mA/0~10mA
It supports dual type input 0~10V and 0(4)~20mA
● Max. Hold maXhd or Mini. Hold miNhd for PV
between 3 terminals in one meter. Please specify the When the [dsply] function in [input group] set to
ordering code AV for input range. And, programming be maXhd(Max. Hold) or miNhd(Mini. Hold), that the
the function [aItyp] to co-ordinate with the input range meter will still display the values of PV in maximum(or
and wiring terminals. minimum) and the relative square orange LED will be
bright during power on, until manual reset by front key in
Scaling Function [ lOsc] & [ hIsc] [user level] or Down Key function has been done.
Setting the [lOsc] (Low scale) and [hIsc] (High The meter will update immediatelly new max./mini.
scale) in [input group] are relative to input signal. values after press Down Key again.
Reverse scaling will be done too. Please refer to the
Please paste the sticker1 M.H on the right side of
figure as below,
orange square LED to identify the status of display.
SCALE Default: [ lOsc]: )00, [ hIsc]: 10)00
Max. ( Mini.) Hold & Reset
[ hIsc] Change to [ lOsc]: 5)00, [ hIsc]: 19(99
Present Maximum Hold [ dsply]
19(99 Value maXh
Reverse slop
[ hIsc]
10)00
[ lOsc]
Reset the Max
Edge [ dNkey]
(Mini) Hold by
5)00 Front Key Trigger Mrst
[ lOsc] INPUT
)00 ● Remote display by RS485 command
)00 % 5)00 % 10)00 %
In past, The meter normally receive 4~20mA or
*Lower display resolution may caused by more narrow 0~10V from AO card or BCD card of PLC. We built-in a
scale. new solution by RS485 which it can save costs of AO
and wiring connecting to PLC simultaneously.
1)if set the positive value (X1) here to display "0" which [ lOsc]
)00 INPUT
it expressed to be low-cut the PV between "+X1 0V 2.75V 5V 9.00V 10V
(plus)" & "-X1(minus)" /absolute value
PV< l Setting value (X1) l, the display will be shown 0
■ Front Key Functions
EX: Low Cut is set for 0.50. If the display is from
Users can set the down key of front panel to be
-0.50~+0.50, that will be 0.
the functions as like as Relative PV(Tare) / PV Hold /
Low Cut set to be +0.50 Reset for max(mini) hold / Reset for relay energized
Present PV according latch.
Value to input signal
Ex. The [dNkey] function set to be reL.pv in [input
[ lOcut]
)50 0.50 group]. When user presses Key, the PV will show
X1 relative value until press Key again.
[ rYsd]
De-energized
Hysteresis
delay time
[ry_.rd] [ry_.fd]
■ RS 485 Communication
Relay CS1 series can be used as Remote Terminal Unit
Energized ON
(RTU) for monitoring and controlling in a SCADA
■ Analogue Output Functions (Supervisor Control And Data Acquisition) system.
Please specify the output type either 0~10V or
● Protocol: Modbus RTU Mode
4(0)~20mA in ordering code. The output low and high ● Baud Rate [ baud]:
can be programmable which it's related with various Programmable 1200/2400/4800/ 9600/ 19200/ 38400
display values. Reverse slope output is decided by ● Data Bits: 8 bits
reversing point positions. ● Stop Bits: Programmable 1 bit or 2 bits
Output range selection ([aOtyp]) ● Parity [prity]: Programmable Even / Odd / None
● Voltage output specified ● Device Number [adres]: Settable 1~255
Programming : V0-10(0~10V) / V0-5(0~5V) / Remote Display function [rs485]
V1-5(1~5V) CS1 series has been built in an innovation function
● Currnet output specified call remote display function.
Programming : A4-20(4~20mA) / A0-20(0~20mA) / When the [dsply] function set to be rs485, At
meantime, the display is no longer according to the input
A0-10(0~10mA)
signal. The PV screen will show the number from RS485
Low Output corresponds to Low display value command & data.
[ aOls]
In past, The meter normally receive 4~20mA or
Settable range: -19999~+29999; 0~10V from AO card or BCD card of PLC. We support a
Setting the Low Display value versus Low output range new solution by RS485 writing in so that can save cost
(as like as 4mA in A4-20). of AO and wiring into PLC.
High Output corresponds to High display value CS1 APPLICATION FOR REMOTE DISPLAY FROM RS485 COMMAND
[ aOhs] RS 485 Modbus RTU Mode (up to 38400bps)
M.H M.H
2 5
caLlo RL1
COM
caLhi
3 6
caLls caLhs
ENT/FN ? ? ? mm
■ ORDERING INFORMATION
6 / 31 CS1 SERIES–OPERATION MANUAL(EN)-2013-01-04
CS1−VA− − −
DC/AC/ Input Optional Aux.
TRMS Signal Output Powered
OPTION
CODE VOLT INPUT CODE CURRENT CODE OPTIONAL O/P CODE AXU. POWER
D DC measuring D DC measuring N None A AC 115/230 V
A AC measuring A AC measuring R1 1 Relay OPTION 4
T TRMS measuring T TRMS measuring 0(1) ~ 5 V / ADH* AC/DC 85~264V * It means RoHS
V 0 ~ 10 V
V1 0 ~ 199.99 mV A1 0 ~ 199.99 μA ADL* AC/DC 20~56V version.
V2 0 ~ 1.9999 V A2 0 ~ 1.9999 mA 0 ~ 10mA
I 0(4)~20 mA
V3 0 ~ 19.999 V A3 0 ~ 19.999 mA
V4 0 ~ 199.99 V A4 0 ~ 199.99 mA 8 RS 485
V5 0 ~ 300.0 V A5 0 ~ 1.9999 A Relay, Analogue Output
V6 0 ~ 600.0 V A6 0 ~ 1.0000 A or RS485 Port can be
VA 0~50 mV A7 0 ~ 5.000 A selected one only
VB 0~60 mV A8 0 ~ 10.000 A
VC 0~100 mV AO Specify A input
VO Specify V input
CS1−PR− − − −
Input Optional Excitation Aux.
Signal Output Supply Powered
OPTION
CODE INPUT RANGE CODE OPTIONAL O/P CODE EXCIT. SUPPLY CODE AXU. POWER
A1 0(4) ~ 20mA / 0 ~ 10mA N None N None A AC115/230V
V1 0 ~ 10V / 0(1) ~ 5V R1 1 Relay E24 DC 24V OPTION 4
AV 0~10V/0(4)~20mA(all in one) 0(1) ~ 5 V EO Specify ADH* AC/DC 85~264V * It means RoHS
V 0 ~ 10 V version.
AO Specify A input ADL* AC/DC 20~56V
VO Specify V input 0 ~ 10 mA * ADH* & ADL* can
I 0(4)~20 mA not support the
8 RS 485 excitation supply
Relay, Analogue Output
or RS485 Port can be
selected one only.
CS1−SG− − − −
Input Optional Excitation Aux.
Signal Output Supply Powered
OPTION
CODE INPUT CODE INPUT CODE OPTIONAL O/P CODE EXCITATION CODE AXU. POWER
S1 1.0mV/V S8 10.0mV/V N None E05 DC 5V A AC 115/230 V
S2 2.0mV/V S9 20.0mV/V R1 1 Relay E10 DC 10V OPTION 4
S3 4.0mV/V SA 40.0mV/V 0(1) ~ 10 mA EO Specify ADH* AC/DC 85~264V * It means
V 0 ~ 10 V RoHS
SO Specify ADL* AC/DC 20~56V
version.
0 ~ 10 mA * ADH* & ADL* can
I 0(4) ~ 20 mA not support the
8 RS 485 excitation supply
Relay, Analogue Output
or RS485 Port can be
selected one only
CS1−PM− − −
Input Optional Aux.
Signal Output Powered
OPTION
CS1−RS− − −
Input Optional Aux.
Signal Output Powered
OPTION
CODE INPUT RANGE CODE INPUT RANGE CODE OPTIONAL O/P CODE AXU. POWER
P1 Pt100Ω -50.00~199.99 °C K1 Type K 0.0~1200.0 °C N None A AC 115/230V
P2 Pt100Ω -150.0~800.0 °C J1 Type J 0.0~750.0 °C R1 1 Relay OPTION 4
E1 Type E 0.0~1000.0 °C 0(1) ~ 5 V ADH* AC/DC 85~264V * It means
V 0 ~ 10 V RoHS
T1 Type T 0.0~400.0 °C ADL* AC/DC 20~56V
version.
R1 T/C type R 400~1600 °C 0 ~ 10 mA
I 0(4) ~ 20 mA
S1 T/C type S 400~1600 °C
B1 T/C type B 400~1800 °C 8 RS 485
Relay, Analogue Output
or RS485 Port can be
selected one only
96.0 60.0
8.0
? ? ?
12.0
ENT/FN
FIX HOLDER:
Dimensions: 96mm x 48mm x 72mm PANEL CUT-OUT: 63 mm(L) / W M3
PANEL CUT-OUT 44.0
+0.2
Panel Cutout: 92mm x 44mm (advise) 92+0.2(W) x 44+0.2(H) mm 1.0~8.0 mm
Unit: mm
+0.2
92.0
■ Wiring Diagram
Please check the voltage of Connector
power supplied first, and then CS1-VA: #A1~A3(Signal Input): 20A/300Vac,
connect to the specified M3.5, 12~22AWG;
terminals. Herein, Max torque: 13Kg-cm
recommended that power
7.0mm max
supplied with protection by a
fuse or circuit breaker to the
7.0mm max
meter.
Others: 10A 300Vac, M2.6, 16~22AWG,
For input and RS485 wiring, RS485 Communication Port Max torque: 5Kg-cm
it's recommended to use twin Please use cord end terminal.
with shielding wire. Max. Distance: 1200M
Terminate Resistor
(at latest unit): 2.0mm max
A B 120~300ohm/0.25W
(typical: 150ohm)
Please set the torque of
4 5 6 automotive screwdriver to match the
limited of terminals.
RS485 Port
A1 A2 A3 4 5 6 7 8 9 10
AC115V
AC230V
Analogue FG
SIGNAL INPUT output ADH AC/DC 86~265V
ADL AC/DC 20~56V
A B AUX. POWER
RS 485 port
11 12 13 14 15 16 D-S 4 5 6 7 8 9 10
Dip-Switch
Dip-Switch 1 2 3 4 5 AC115V
0~50.0Ω/ O O
~2.0KΩ N N
AC230V
Analogue FG
POTENTIO- 0~2.0KΩ/ O O output ADH AC/DC 86~265V
~100.0KΩ
METER N N
ADL AC/DC 20~56V
Ohm(3W) AUX. POWER
INPUT A B
RS 485 port
[CS1-PR DC Process (10V/20mA) Indicator] [CS1-SG Strain Gauge / Load Cell Indicator]
Relay, Analogue o/p Relay Terminal blocks: Relay, Analogue o/p Relay Terminal blocks:
or RS485 port can be 10A/300Vac, M2.6, or RS485 port can be 10A/300Vac, M2.6,
selected one only. b c a 1.3~2.0mm2 (22~16AWG) selected one only. b c a 1.3~2.0mm2 (22~16AWG)
11 12 13 14 15 16 4 5 6 7 8 9 10 11 12 13 14 15 16 4 5 6 7 8 9 10
AC115V AC115V
0~20mA Excit. AC230V Excit. AC230V
Analogue FG mV/V Analogue FG
Supply output ADH AC/DC 86~265V SIGNAL
Supply output ADH AC/DC 86~265V
0~10V DC24V ADL AC/DC 20~56V ADL AC/DC 20~56V
INPUT
SIGNAL INPUT AUX. POWER AUX. POWER
A B A B
RS 485 port RS 485 port
2 wire Transmitter connection 4(0)~20mA Input connection Load Cell connection
4~20mA 24Vdc 4~20mA 24Vdc 10Vdc
Input Excit.S Input Excit.S mV Input Excit.S
11 12 13 14 15 11 12 13 14 15 11 12 13 14 15
+VE.S.
4~20mA -VE.S.
Front Key
Display screen
M.H function status
Operating Key: 4 keys for Enter(Function) /
~A Mini. Hold status
Operation Key
ENT/FN ? ? ?
Shift(Escape) / Up key / Down key
Engineer Unit
Pass Code: Settable range:0000~9999;
Numeric Screens User must key-in the exactly pass code for access
0.8”(20.0mm) red high-brightness LED for 4 2/3 digital to [Programming Level]. Otherwise, the meter will
present value. return to measuring page. If user forgets the pass
I/O Status Indication code, please contact with your service window.
● Relay Energized: 1 square red LED Function Lock: There are 4 levels programmable.
RL1 display when Relay 1 has been energized; ● None( none): no lock at all. User can access to all
● RS485 Communication: 1 square orange LED level for checking and setting.
COM will flash when the meter is receive or send data, and ● User Level( user): User Level lock. User can access
COM flash quickly means the data transient quicker. to User Level for checking, but can not setting.
● Max/Mini Hold indication: 2 square orange LEDs ● Programming Level( eng): Programming level lock.
CO M.H displayed: When the display function has been User can access to programming level for checking,
selected in Maximum or Minimum Hold function. but can not setting.
Stickers: ● ALL( all): All lock. User can access to all level for
Each meter has a sticker what are functions and checking but can not setting.
engineer label enclosure. Front Key Function
Functions stickers The Down Key can be set to be function as like as
Relative PV(Tare) / PV Hold / Reset for max(mini)
hold / Reset for relay energized latch.
Ex. The [dNkey] function set to be reL.pv in [input
group]. When user presses Key, the PV will show
relative value until press Key again.
● Relay energized:
H i Hi Energized L o Lo Energized
Hi. H Hi Energized & Latch Lo. H Lo Energized & Latch
● Front key functions:
PV Hold Tare Digital Input
Maximum or Minimum Reset
Reset fo Relay Latch
■ Error Masage
BEFORE POWER ON, PLEASE CHECK THE SPECIFICATION AND CONNECTION AGAIN.
SELF-DIAGNOSIS AND ERROR CODE:
DISPLAY DESCRIPTION REMARK
Display is positive-overflow (Signal is over
ovfl (Please check the input signal)
display range)
Display is negative-overflow (Signal is under
-ovfl (Please check the input signal)
display range)
ADC is positive-overflow (Signal is higher than
ovfl (Please check the input signal)
input 120%)
ADC is negative-overflow (Signal is lower than
-ovfl (Please check the input signal)
input -120%)
eep fail EEPROM occurs error (Please send back to manufactory for repaired)
aiCng pv Didn’t execute the calibrate of Input Signal (Please process Calibrating Input Signal)
aic fail Input signal calibrated error (Please check Calibrating Input Signal)
aoCng pv Didn’t execute the calibrate of output Signal (Please process Calibrating Output Signal)
aoc fail Output Signal calibrated error (Please check Calibrating Output Signal)
■ Operating Key:
(= ) (1) In function index, press to go back to (2) In setting status for function, press to
Up key previous function index select function
(3) During number Setting, press can roll
the digit up
(= ) (1) In Function Index Page, press will go to the (2) In setting status for function, press to
Down key next Function Index Page. select function
(3) During number Setting, press can roll
the digit down.
Power ON
Self-diagnosis
88888
Display the model User Level
cs!va cs!va: Volt/Current
cs!pr: DC 10V/20mA Press for 1 sec. to back Measuring Page
cs!sg: Strain Gauge
cs!pm: Potentiometer This page will show min: the Minimum model of the meter
16*88 min cs!va
0−0−1
0−3
0−6
cs!rs: Resistance out, when [dsply] value of PV saving firmware version
cs!t : Rtd T/C set to be rs485.
pv pv: Present Value
)00 Checking only ver@0 Checking only
0−4
0−0−1
the firmware version Set-point value of PV saving
ver@0: Version 2.0 10)00 -19999~+29999 19(99 Checking only pv
MEASURING PAGE rYrst: Reset for Mrst: Reset the
rYrst Mrst
0−2
0−5
Press 1sec Access energized Latch of saved value of
16*88 Escape Press 1sec
no Relay no Maximum & Minimum
yes / no yes / no
Enter the password to
Pcode access Programming
Level
enter
NO
Pass Code
Programming Level
Default:1000 Press for 1 sec. to back Measuring Page
YES
input INPUT GROUP relay RELAY GROUP ao ANALOGUE rs485 RS485 GROUP
OUTPUT GROUP
group group group group
input INPUT GROUP relay RELAY GROUP ao ANALOGUE rs485 RS485 GROUP
OUTPUT GROUP
group group group group
The function is for rYsb: Start band for aOtyp: Analogue adres: Device
aItyp CS1-PR only. It’ll be rYsb Relay energized aOtyp Output type and adres number of the meter
A−0
B−1
D−1
E−1
hiden for other models range selection 1~255
A4-20 ai.typ: Analogue Input
0 0~9999 digits A4-20 V0-10 / V0-5 /
1
type and range selection V1-5 / A0-20 /
V0-10 / V0-5 / V1-5 A4-20 / A0-10
/ A0-20 / A4-20 /
A0-10
pVdp: Decimal Point of rYsd: Start delay aOls: the low point baud: Baud rate
pVdp rYsd aOls baud
B−2
D−2
E−2
PV time for Relay is relative to the 1200 / 2400 /
A−1
D−3
E−3
-19999~+29999 energized mode is relative to the Nstb.1 / Nstb.1 /
A−2
highest of Analogue
)00 hi off / lo / hi / 10)00 output NstB2 odd / even
lOhld / hIhld /
-19999~+29999
do
hIsc: High scale of PV ry!hy: Relay 1 aOzro: Fine Zero
hIsc ry!hy aOzro
A−3
B−4
B−5
D−5
B−6
D−6
D−7
-19999~+29999
)00
avg: Average update
avg
A−9
for PV
5 1(None)~99times
mVavg: Moving
mVavg
A−10
0(None)/1~99times
0
dNkey: Down key
dNkey
A−12
function
none none / reLpv / pVhld
/ reLpv/ Mrst /
rYrst
Pcode: Pass Code
Pcode
A−13
Lock
none /
none / user /
all
eng
default=2000
00000 caLlo: Field Calibration Low
Press to read signal of the lower status.
Press again to finish the calibration lower point, and go to
next page.
caLls: the value to be set is relative to Field Calibration
caLls
F−2
lower point
00000 Press to set the value of lower scale
higher point
00000 Press to set the value of Higher scale
saving;
The meter will save the maximum of PV during
299(9 power on, until reset in [ Mrst](step 0-5). It will
save newest maximum after reset.
Mrst(M.rSt): reset the saved value of Programmable: yes / no
Mrst
0−5
168*8
Press for 1 second to back to Measuring Page in any page.
■ Programming Level
INDEX FUNCTION DESCRIPTION PARAMETERS & SETTING SET
MEASURING PAGE
168*8
Enter the pass code to access If user wants to change the pass
enter code, please go to step A-13 to
Programming Level
0000 set. Please remind the new pass
Pcode code.
Default:1000
1000
Enter the pass code to access
Pass Code
NO programming level.
YES Press for 1 second to back Measuring Page
■ Input Group
INDEX FUNCTION DESCRIPTION PARAMETERS & SETTING SET
input INPUT GROUP INDEX PAGE In following pages, press for
1 second to back INPUT GROUP
group INDEX PAGE.
A4-20 aItyp(Ai.tyP): Analog input type & range V0- 5(0~5V) / V1- 5(1~5V) /
A4-20 selection A0-10(0~10mA) / A0-20(0~20mA) /
There are 3 terminals for mA and V input, if A4-20(4~20mA)
V0-10 user selects ordering code in input for "AV" Up Down Enter
from input. Please confirm the wiring is
correct or not to set.
pVdp(Pv.dP): Decimal Point of PV Programmable:
pVdp
A−1
0 0/ )0 / )00 / )000 /
0 0.0000
)0000 Up Down Enter
NEXT PAGE
18 / 31 CS1 SERIES–OPERATION MANUAL(EN)-2013-01-04
lOsc(Lo.SC): Low scale of PV Programmable: -19999~29999
A−2
lOsc
000)0 ◘ CS1-SG/PM/RS: If the field calibration has Shift Up Down Enter
)0 be done and then the [ Csel] (Calibration SCALE Default: [ lOsc]: )00, [ hIsc]: 10)00
[ hIsc] Change to [ lOsc]: 5)00, [ hIsc]: 19(99
parameter selection) selected to be
00)00 field(field calibration), the [ lOsc] will be
19(99
Reverse slop
only in zero & span of PV, but also any lower 10)00
point for [pVzro] & higher point for [pVspn]. 8)00
5%00
The meter wills be linear for full scale. [ lOsc]
)00 INPUT
0V 2.75V 5V 9.00V 10V
200)0
none of Low / High points for PV display; none(None): Do not clear the fine
adjustment of Low / High.
none
pV.zro(PV.Zro): To clear the fine
both adjustment Low.
pV.spn (PV.SPn): To clear the fine
adjustment High
both(Both): To clear the fine
adjustment of Low and High.
Up Down Enter
dsply(dSPLY): Display Function for PV Programmable:
dsply
A−7
X2 -0.10
Low cut
function
00 The digital filter can reduce the influence 0(no function)/1~99 times.
0 of spark noise by magnetic of coil. Shift Up Down Enter
If the values of samples are over digital
99 filter band(fixed in firmware and about 5% of
stable reading) 3 times (Digital Filter set to
be 3) continuously, the meter will admit the
samples and update the new reading.
Otherwise, it will be as treat as a noise and
skip the samples.
dNkey(dn.key): Down key function Programmable:
dNkey
A−12
none Users can set the down key of front panel none(None): no fuction
none to be the functions as like as Relative reLpv(rEl.Pv): Relactive PV
PV(Tare) / PV Hold / Reset for max(mini) pVhld(Pv.HLd): PV hold
pVhld hold / Reset for relay energized latch. Mrst(M.rST): Reset for Max./Mini
hold
rYrst(rY.rST): Reset for Relay
energized latch
Up Down Enter
NEXT PAGE
20 / 31 CS1 SERIES–OPERATION MANUAL(EN)-2013-01-04
Pcode(P.CodE): Pass Code setting for Settable range: 0000~9999
A−13
Pcode access to programming level
1000 Shift Up Down Enter
0000 Please remind and write down the new pass
code so that access to programming level.
9999
none There are 4 levels programmable for lock none(None): no lock at all. User
that the function is to avoid miss-setting. can access to user level for
none
checking and setting.
all user(User Level): User level
lock. User can access to user
level for checking, but can not
setting.
eng(Programming Level):
Programming level lock. User
can access to programming
level for checking, but can not
setting.
all(All Level): All lock. User
can access to all level for
checking, but can not setting.
Up Down Enter
[ rYsd]
rYsd(rY.Sd): start delay time for Relay Settable range:
rYsd
B−2
(5(9
De-energized
Hysteresis
delay time
[ry_.rd] [ry_.fd]
Relay
Energized ON
(5(9
(5(9
10)00
[ aOls]
5)00
[ lOsc]
)00 OUTPUT
0.00% 50.00% 80.00% 100.00%
[ aOlmt]
■ RS485 Group (The group will be hidden, if the RS485 function is not to be specify )
INDEX FUNCTION DESCRIPTION PARAMETERS & SETTING SET
RS485 GROUP INDEX PAGE In following pages, press for
rs485 1 second to return the RS485
group GROUP INDEX PAGE.
2 5
caLlo RL1
COM
caLhi
3 6
caLls caLhs
ENT/FN ? ? ? mm
Pcode
&
NEXT PAGE
24 / 31 CS1 SERIES–OPERATION MANUAL(EN)-2013-01-04
enter Pass Code Page for Field Calibration Enter the exactly pass code of the
0000 Level meter to access the Field Calibration
Fcode Level. Otherwise, it will be turning
back to measuring page.
2000
NO
Pass Code
YES
Adjust the structure of machinery to be a lower signal output status(or any
lower status).
caLlo caLlo(CAL.Lo): Field Calibration Low. ► Waiting for the value till stable,
F−1
052eh The low calibration is not need the exactly pressed Key to read signal low
0022h "zero" to calibrate because of the "field of sensing device.
calibration" function could be calibrate any ► Waiting for above reading stable
lower point. (around 3~5seconds), press
Key again to complete the
calibration lower point, and go to
[caLls].
caLls caLls(CAL.LS): the value to be set is Settable range: -19999~29999
F−2
699bh The high calibration is not need the pressed Key to read signal high
6478h exactly "span" to calibrate because of the of sensing device.
"field calibration" function could be ► Waiting for above reading stable
calibrating any higher point. (around 3~5seconds), press
Key again to complete the
calibration higher point, and go to
[caLhs].
caLhs caLhs(CAL.HS): the value to be set is Settable range: -19999~29999
F−4
User level
Name Address Range Explain Initial Write/Read Note
pv 0000h -19999~29999 Present Value R
■ Trademark
The names used for identification only maybe registered trademark of their respective
companies.