Professional Documents
Culture Documents
Epe196mlddcstrdc, FM, Fl&ips - 112a
Epe196mlddcstrdc, FM, Fl&ips - 112a
CONSTRUCTION OF WATER TREATMENT PLANT OF CAPACITY 196MLD EXPANDABLE TO 270MLD WITH COMPLETE
SCADA SYSTEM FOR THE ENTIRE PROJECT ON DESIGN BUILD, OPERATE AND TRANSFER BASIS FOR NEW WATER
SUPPLY SCHEME IN TIRUPPUR CITY MUNICIPAL CORPORATION.
CLIENT :
CMSC :
TITLE :
NAME SIGN DATE
SIZE REV.
DOC.No. EPE/196MLD/DC/STR/DC, FM, FL&IPS - 112A
A4 0
TABLE OF CONTENTS
DESIGN OF STAIRCASE 1
DESIGN OF STAIRCASE - FLIGHT 3 & FLIGHT 4
Fck Fy Cover Safety
N/mm2 N/mm2 mm factor
30 500 25 1.5
Tread = 250 mm
Riser = 175 mm
Thickness of slab assumed, D = 125 mm
Effective Depth (125-25-12/2) = 94 mm
Span of flight = 3250 mm
Width of landing = 600 mm
Total Span = 3850 mm
Load Calculation:
Flight location
2
Total Dead Load (3.82+2.19+1.2) = 7.21 kN/m
2
Live Load = 3.00 kN/m
Landing location
2
Total Dead Load (3.13+1.2) = 4.33 kN/m
2
Live Load = 3.00 kN/m
Factored load
Flight location
2
Total Dead Load, Wu,DL1 (7.21*1.5) = 10.815 kN/m
2
Live Load , Wu,LL1 (3*1.5) = 4.50 kN/m
2
Total load = 15.315 kN/m
Landing location
2
Total Dead Load , Wu,DL2 (4.33*1.5) = 6.495 kN/m
2
Live Load , Wu,LL2 (3*1.5) = 4.50 kN/m
2
Total load = 10.995 kN/m
DL = 10.815 kN/m
LL = 4.50 kN/m DL = 6.495 kN/m
LL = 4.50 kN/m
A B
3250 mm 600 mm
Ra Rb
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943,54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
project on design build, operate and transfer basis for new water supply 01.02.2020
112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
Flocculator and Inclined Plate Settler for 196MLD WTP, Ottarpalayam Village - SVK JTP MGK 0
Tiruppur
Main Reinforcement:
Mu1 dpro pt,req pt,min f1 Spacing pt,pro Pt req < Pt pro
R
kNm mm % % mm mm % SAFE
27.695 3.13 94 0.84 0.12 12 100 1.20
Distribution Reinforcement:
pt,min f1 Spacing pt,pro
% mm mm %
0.12 8 200 0.20
Provide 3 Nos of Y16 at top & 3 Nos of Y16 at bottom as reinforcement with
Stirrups as Y8 at 200 mm c/c.
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943,54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
project on design build, operate and transfer basis for new water supply 01.02.2020
112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
Flocculator and Inclined Plate Settler for 196MLD WTP, Ottarpalayam Village - SVK JTP MGK 0
Tiruppur
Provide 3 Nos of Y16 at top & 3 Nos of Y16 at bottom as reinforcement with
Stirrups as Y8 at 200 mm c/c.
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943,54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
project on design build, operate and transfer basis for new water supply 01.02.2020
112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
Flocculator and Inclined Plate Settler for 196MLD WTP, Ottarpalayam Village - SVK JTP MGK 0
Tiruppur
DESIGN OF STAIRCASE 2
DESIGN OF STAIRCASE - FLIGHT 3 & FLIGHT 4
Fck Fy Cover Safety
N/mm2 N/mm2 mm factor
30 500 25 1.5
Tread = 250 mm
Riser = 180 mm
Thickness of slab assumed, D = 125 mm
Effective Depth (125-25-12/2) = 94 mm
Span of flight = 2500 mm
Width of landing = 1200 mm
Total Span = 3700 mm
Load Calculation:
Flight location
2
Total Dead Load (3.86+2.25+1.2) = 7.31 kN/m
2
Live Load = 3.00 kN/m
Landing location
2
Total Dead Load (3.13+1.2) = 4.33 kN/m
2
Live Load = 3.00 kN/m
Factored load
Flight location
2
Total Dead Load, Wu,DL1 (7.31*1.5) = 10.965 kN/m
2
Live Load , Wu,LL1 (3*1.5) = 4.50 kN/m
2
Total load = 15.465 kN/m
Landing location
2
Total Dead Load , Wu,DL2 (4.33*1.5) = 6.495 kN/m
2
Live Load , Wu,LL2 (3*1.5) = 4.50 kN/m
2
Total load = 10.995 kN/m
DL = 10.965 kN/m
LL = 4.50 kN/m DL = 6.495 kN/m
LL = 4.50 kN/m
A C
B
2500 mm 1200 mm
Ra Rb
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943,54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
project on design build, operate and transfer basis for new water supply 01.02.2020
112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
Flocculator and Inclined Plate Settler for 196MLD WTP, Ottarpalayam Village - SVK JTP MGK 0
Tiruppur
Main Reinforcement:
Mu1 dpro pt,req pt,min f1 Spacing pt,pro Pt req < Pt pro
R
kNm mm % % mm mm % SAFE
8.124 0.92 94 0.22 0.12 12 100 1.20
Distribution Reinforcement:
pt,min f1 Spacing pt,pro
% mm mm %
0.12 8 200 0.20
DESIGN
Tread = 250 mm
Riser (Max) = 180 mm
Thickness of slab assumed, D = 125 mm
Effective Depth (125-25-12/2) = 94 mm
Span of flight = 2500 mm
Width of landing 1 = 1200 mm
Width of landing 2 = 1200 mm
Total Span = 4900 mm
Load Calculation:
Self wt of inclined Slab (125/1000*25) = 3.130 kN/m2
Self wt of Slab on horizontal (3.13*SQRT(250^2+180^2)/250) = 3.86 kN/m2
DL of each step on horizontal (0.5*250*180/250/1000*25) = 2.25 kN/m2
Floor finish = 1.20 kN/m2
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943,54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
project on design build, operate and transfer basis for new water supply 01.02.2020
112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
Flocculator and Inclined Plate Settler for 196MLD WTP, Ottarpalayam Village - SVK JTP MGK 0
Tiruppur
Flight location
2
Total Dead Load (3.86+2.25+1.2) = 7.310 kN/m
2
Live Load = 3.00 kN/m
Landing location
2
Total Dead Load (3.13+1.2) = 4.33 kN/m
2
Live Load = 3.00 kN/m
Factored load
Flight location
2
Total Dead Load, Wu,DL1 (7.31*1.5) = 10.965 kN/m
2
Live Load , Wu,LL1 (3*1.5) = 4.50 kN/m
2
Total load = 15.47 kN/m
Landing location
2
Total Dead Load , Wu,DL2 (4.33*1.5) = 6.495 kN/m
2
Live Load , Wu,LL2 (3*1.5) = 4.50 kN/m
2
Total load = 11.00 kN/m
DL = 10.965 kN/m
DL = 6.50 kN/m LL = 4.50 kN/m DL = 6.495 kN/m
LL = 4.50 kN/m LL = 4.50 kN/m
D C
B
1200 mm 2500 mm 1200 mm
Rd Rb
Load comb
(1.5DL + 1.5 LL)
Main Reinforcement:
Mu1 dpro pt,req pt,min f1 Spacing pt,pro Pt req < Pt pro
R
kNm mm % % mm mm % SAFE
18.46 2.09 94 0.53 0.12 12 100 1.20
Distribution Reinforcement:
pt,min f1 Spacing pt,pro
% mm mm %
0.12 8 200 0.201
Provide 3 Nos of Y16 at top & 3 Nos of Y16 at bottom as reinforcement with
Stirrups as Y8 at 200 mm c/c.
Provide 3 Nos of Y16 at top & 3 Nos of Y16 at bottom as reinforcement with
Stirrups as Y8 at 200 mm c/c.
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., New Tiruppur Area
Tiruppur City Municipal
Plot No:943, 54th street, TVS Colony, Development Corporation Ltd
Corporation, Tiruppur.
Anna Nagar West Ext, Chennai (NTADCL), Tiruppur.
Name of the Project: Construction of water treatment plant of capacity DOCUMENT NO. DATE
196 MLD expandable to 270 MLD with complete scada system for the EPE/196MLD/DC/STR/DC, FM,
entire project on design build, operate and transfer basis for new water 01.02.2020
FL&IPS - 112A
supply scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash
Mixer, Flocculator and Inclined Plate Settler for 196MLD WTP, SVK JTP MGK 0
Ottarpalayam Village - Tiruppur
fck = 30 N/mm2
fy = 500 N/mm2
Cover = 50 mm
Depth of excavation = 0.8 m from FGL
Depth of excavation = 0.6 m from NGL
gsoil = 18 kN/m3
gcon = 25 kN/m3
Net SBC = 170 kN/m2
Width assumed = 1.00 m
d/2 d
d/2
Column moment, My
Column moment, Mz
Bc Lc
Z L
Support Moment, Mz X
Support Moment, Mx
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
12 3 0 0 55 0 0 300 300 1.00 1.00 71 0.00 0.00 71 71 181 170 55 55 8 8 71 71 71 71 300 0.35 5 241 245 0.02 0.16 10 200 0.35 5 221 235 0.02 0.17 10 200 9 22 0.30 3.45 0.04 9 21 0.31 3.45 0.04 1.00 1.50 1.37 0.17 SAFE
19 3 0 0 9 0 0 300 300 1.00 1.00 25 0.00 0.00 25 25 181 170 9 9 8 8 25 25 25 25 300 0.35 1 241 245 0.00 0.16 10 200 0.35 1 221 235 0.00 0.17 10 200 1 22 0.30 3.45 0.01 2 21 0.31 3.45 0.01 1.00 1.50 1.37 0.03 SAFE
8 3 0 0 63 4 0 300 300 1.00 1.00 79 21.25 0.00 100 57 181 170 84 42 8 8 100 100 57 57 300 0.35 8 241 245 0.03 0.16 10 200 0.35 8 221 235 0.03 0.17 10 200 13 22 0.30 3.45 0.05 15 21 0.31 3.45 0.06 1.00 1.50 1.37 0.26 SAFE
12 3 0 0 18 0 0 300 300 1.00 1.00 33 0.00 0.00 33 33 181 170 18 18 8 8 33 33 33 33 300 0.35 2 241 245 0.01 0.16 10 200 0.35 2 221 235 0.01 0.17 10 200 3 22 0.30 3.45 0.01 3 21 0.31 3.45 0.01 1.00 1.50 1.37 0.05 SAFE
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
LOAD CALCULATIONS
Inlet channel:
Seismic load
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 32.49 mm
2
fs = M/Ast1(d-x/3) = 101.83 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000819
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000224
The average surface strain em
em (e1-e2) = 0.000595
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 66.63
Cmin = 30
The design crack width W cr = 0.07
Hence Safe against cracking
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF OUTER WALL FOR INLET CHANNEL: (Along the length) Wall - W10
Properties of material
fck = 30 N/mm2
fy = 500 N/mm2
Dimensions
Thickness of Wall D = 200 mm
Clear cover to rebar C = 45 mm
Dia of main rebar = 10 mm
Eff. Thickness of Wall d = 150 mm
(200-45-10/2)
Height of Liquid /wall = 1900 mm (406.3-404.9+0.5)x1000
Unit weight of liquid = 9.81 kN/m3
Maximum Bending moment causing tension in the sewage / soilface = 16.28 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 42.18 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
2
fs = M/Ast1(d-x/3) = 190.6 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001395
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000291
The average surface strain em
em (e1-e2) = 0.001104
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 75.04
Cmin = 45
The design crack width W cr = 0.18
Hence Safe against cracking
Bottom moment of base slab (Due to self weight of base slab &Liquid):
Unfactored moment = 19.21 kNm (Tension @ bottom)
Load factor = 1.5
Mu = 28.8 kNm
Percentage of steel required = 0.311 %
Area of steel reqd @ bottom = 467 mm2 (0.311x1000x150/100)
Depth of Surface Zone = 100 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ bottom = 350 mm2 (0.35x1000x100/100)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 19.21 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.22 mm
2
fs = M/Ast1(d-x/3) = 181.77 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001347
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.001111
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.17
Hence Safe against cracking
Bottom moment of base slab (Fixed end moment of inlet channel wall):
Unfactored moment = 16.28 kNm (Tension @ Top)
Load factor = 1.5
Mu 24.4 kNm
Percentage of steel required = 0.260 %
Area of steel reqd @ Top = 390 mm2 (0.26x1000x150/100)
Depth of Surface Zone = 100.0 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ Top = 350 mm2
Spacing of reinft. Reqd. = 201 mm
Spacing of reinft. Provided = 150 mm
Area of steel provided @ Top = 524 mm2 Safe
(1000/150x0.7854x10^2)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 16.28 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 44.82 mm
2
fs = M/Ast1(d-x/3) = 207.2 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001338
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000216
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
fck = 30 N/mm2
fy = 500 N/mm2
Cover = 50 mm
Depth of excavation = 0.80 m from FGL
Depth of excavation = 0.75 m from FGL
gsoil = 18 kN/m3
gcon = 25 kN/m3
Net SBC = 170 kN/m2
Width assumed = 1.00 m
d/2 d
d/2
Column moment, My
Column moment, Mz
Bc Lc
Z L
Support Moment, Mz X
Support Moment, Mx
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
1 101 2.8 0.21 255 1 -5 300 300 1.45 1.45 138 0.85 8.10 147 129 184 170 130 112 24 13 147 131 129 146 450 0.58 32 622 394 0.05 0.14 12 200 0.58 32 585 382 0.05 0.15 12 200 35 24 0.29 3.45 0.09 38 24 0.29 3.45 0.10 1.00 1.50 1.37 0.33 SAFE
102 10 0.35 223 1 27 300 300 1.45 1.45 123 1.35 51.71 176 70 226 213 159 53 24 13 176 73 70 174 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
103 2.5 12 211 -30 -4 300 300 1.45 1.45 118 57.69 7.17 182 53 226 213 165 35 24 13 182 168 53 67 450 0.58 41 622 394 0.06 0.14 12 200 0.58 41 585 382 0.07 0.15 12 200 45 24 0.29 3.45 0.11 48 24 0.29 3.45 0.13 1.00 1.50 1.37 0.42 SAFE
104 16 0.07 238 1 -34 300 300 1.45 1.45 130 0.03 66.36 197 64 226 213 180 47 24 13 197 64 64 197 450 0.58 45 622 394 0.07 0.14 12 200 0.58 45 585 382 0.07 0.15 12 200 49 24 0.29 3.45 0.12 52 24 0.29 3.45 0.14 1.00 1.50 1.37 0.45 SAFE
105 2.6 12.4 251 31 -4 300 300 1.45 1.45 136 59.07 7.49 203 70 226 213 185 52 24 13 203 188 70 85 450 0.58 46 622 394 0.07 0.14 12 200 0.58 46 585 382 0.07 0.15 12 200 50 24 0.29 3.45 0.13 54 24 0.29 3.45 0.14 1.00 1.50 1.37 0.47 SAFE
106 10 0.35 248 1 26 300 300 1.45 1.45 135 1.51 50.93 187 82 226 213 170 65 24 13 187 85 82 184 450 0.58 42 622 394 0.06 0.14 12 200 0.58 42 585 382 0.07 0.15 12 200 46 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.43 SAFE
107 2.8 12 235 -30 -5 300 300 1.45 1.45 129 57.53 7.94 195 64 226 213 177 46 24 13 195 179 64 79 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
108 16 0.07 263 1 -35 300 300 1.45 1.45 142 0.18 67.14 209 75 226 213 192 57 24 13 209 75 75 209 450 0.58 48 622 394 0.07 0.14 12 200 0.58 48 585 382 0.08 0.15 12 200 52 24 0.29 3.45 0.13 56 24 0.29 3.45 0.15 1.00 1.50 1.37 0.49 SAFE
109 2.8 12.4 275 31 -5 300 300 1.45 1.45 148 59.23 8.27 215 80 226 213 198 63 24 13 215 199 80 97 450 0.58 49 622 394 0.07 0.14 12 200 0.58 49 585 382 0.08 0.15 12 200 54 24 0.29 3.45 0.14 57 24 0.29 3.45 0.15 1.00 1.50 1.37 0.50 SAFE
2 101 2.4 0.2 216 -1 -4 300 300 1.45 1.45 120 0.34 6.91 127 112 184 170 110 95 24 13 127 113 112 126 450 0.58 27 622 394 0.04 0.14 12 200 0.58 27 585 382 0.04 0.15 12 200 30 24 0.29 3.45 0.08 32 24 0.29 3.45 0.08 1.00 1.50 1.37 0.28 SAFE
102 10 0.06 208 1 26 300 300 1.45 1.45 116 0.17 51.16 167 65 226 213 150 47 24 13 167 65 65 167 450 0.58 37 622 394 0.06 0.14 12 200 0.58 37 585 382 0.06 0.15 12 200 41 24 0.29 3.45 0.10 43 24 0.29 3.45 0.11 1.00 1.50 1.37 0.38 SAFE
103 2.4 12.4 235 -30 -4 300 300 1.45 1.45 129 58.87 7.03 195 63 226 213 178 46 24 13 195 181 63 77 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
104 15 0.34 224 -1 -33 300 300 1.45 1.45 123 1.16 64.90 189 57 226 213 172 40 24 13 189 60 57 187 450 0.58 43 622 394 0.06 0.14 12 200 0.58 43 585 382 0.07 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.44 SAFE
105 2.3 12 196 30 -4 300 300 1.45 1.45 110 57.88 6.71 175 46 226 213 158 29 24 13 175 162 46 59 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
106 10 0.06 208 1 26 300 300 1.45 1.45 116 0.32 51.12 167 65 226 213 150 47 24 13 167 65 65 167 450 0.58 37 622 394 0.06 0.14 12 200 0.58 37 585 382 0.06 0.15 12 200 41 24 0.29 3.45 0.10 43 24 0.29 3.45 0.11 1.00 1.50 1.37 0.38 SAFE
107 2.4 12.4 235 -30 -4 300 300 1.45 1.45 129 58.72 7.07 195 63 226 213 178 46 24 13 195 181 63 77 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
108 15 0.34 224 -1 -33 300 300 1.45 1.45 123 1.01 64.94 189 57 226 213 172 40 24 13 189 59 57 187 450 0.58 43 622 394 0.06 0.14 12 200 0.58 43 585 382 0.07 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.44 SAFE
109 2.4 12 196 30 -4 300 300 1.45 1.45 110 58.03 6.75 175 46 226 213 158 28 24 13 175 162 46 59 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
5 101 0.6 0.2 324 1 1 300 300 1.60 1.60 144 0.61 1.38 146 142 184 170 129 125 29 16 146 143 142 145 450 0.65 41 622 394 0.06 0.14 12 200 0.65 41 585 382 0.06 0.15 12 200 49 24 0.29 3.45 0.13 52 24 0.29 3.45 0.14 1.00 1.50 1.37 0.33 SAFE
102 15 0.23 297 1 33 300 300 1.60 1.60 133 0.59 47.44 181 85 226 213 164 68 29 16 181 86 85 180 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
103 0.6 13.5 272 -33 1 300 300 1.60 1.60 123 48.29 1.36 173 74 226 213 156 56 29 16 173 170 74 76 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
104 13 0.18 290 1 -31 300 300 1.60 1.60 131 0.42 44.94 176 85 226 213 159 68 29 16 176 86 85 175 450 0.65 50 622 394 0.08 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 61 24 0.29 3.45 0.15 64 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
105 0.5 13.9 315 34 1 300 300 1.60 1.60 140 49.31 1.14 191 90 226 213 173 72 29 16 191 188 90 92 450 0.65 55 622 394 0.08 0.14 12 200 0.65 55 585 382 0.09 0.15 12 200 67 24 0.29 3.45 0.17 70 24 0.29 3.45 0.18 1.00 1.50 1.37 0.45 SAFE
106 15 0.22 328 1 33 300 300 1.60 1.60 145 0.70 47.57 193 97 226 213 176 80 29 16 193 98 97 192 450 0.65 56 622 394 0.08 0.14 12 200 0.65 56 585 382 0.09 0.15 12 200 68 24 0.29 3.45 0.17 71 24 0.29 3.45 0.19 1.00 1.50 1.37 0.46 SAFE
107 0.7 13.5 303 -33 2 300 300 1.60 1.60 136 48.19 1.49 185 86 226 213 168 69 29 16 185 182 86 89 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
108 13 0.18 321 1 -31 300 300 1.60 1.60 143 0.53 44.82 188 97 226 213 171 80 29 16 188 98 97 187 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 66 24 0.29 3.45 0.17 69 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0.6 13.9 346 34 1 300 300 1.60 1.60 152 49.41 1.27 203 102 226 213 186 84 29 16 203 200 102 104 450 0.65 59 622 394 0.09 0.14 12 200 0.65 59 585 382 0.09 0.15 12 200 71 24 0.29 3.45 0.18 75 24 0.29 3.45 0.20 1.00 1.50 1.37 0.48 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
6 101 0.5 0.21 274 -1 1 300 300 1.60 1.60 124 0.27 1.19 126 123 184 170 108 106 29 16 126 123 123 125 450 0.65 34 622 394 0.05 0.14 12 200 0.65 34 585 382 0.05 0.15 12 200 42 24 0.29 3.45 0.11 44 24 0.29 3.45 0.11 1.00 1.50 1.37 0.28 SAFE
102 14 0.18 277 -1 32 300 300 1.60 1.60 126 0.29 46.59 172 79 226 213 155 61 29 16 172 79 79 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 62 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
103 0.5 13.9 296 -34 1 300 300 1.60 1.60 133 49.17 1.07 183 82 226 213 166 65 29 16 183 181 82 85 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
104 13 0.23 271 -1 -31 300 300 1.60 1.60 123 0.46 44.24 168 78 226 213 150 61 29 16 168 79 78 167 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0.6 13.5 253 34 1 300 300 1.60 1.60 116 48.42 1.29 166 66 226 213 148 49 29 16 166 163 66 69 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
106 14 0.19 278 -1 32 300 300 1.60 1.60 126 0.19 46.60 172 79 226 213 155 61 29 16 172 79 79 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 62 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
107 0.5 13.9 296 -34 1 300 300 1.60 1.60 133 49.07 1.08 183 83 226 213 166 65 29 16 183 181 83 85 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
108 13 0.23 271 -1 -31 300 300 1.60 1.60 123 0.36 44.23 168 79 226 213 150 61 29 16 168 79 79 167 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0.6 13.5 253 34 1 300 300 1.60 1.60 116 48.52 1.30 166 66 226 213 148 49 29 16 166 163 66 69 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
9 101 0.1 0.2 312 1 -1 300 300 1.60 1.60 139 0.63 0.23 140 138 184 170 122 121 29 16 140 139 138 138 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.21 281 1 32 300 300 1.60 1.60 127 0.52 45.49 173 81 226 213 156 64 29 16 173 82 81 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
103 0.1 13.8 260 -34 -1 300 300 1.60 1.60 119 49.37 0.13 168 69 226 213 151 52 29 16 168 168 69 69 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.2 283 1 -32 300 300 1.60 1.60 128 0.51 45.90 174 81 226 213 157 64 29 16 174 82 81 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.41 SAFE
105 0.1 14.2 304 35 -1 300 300 1.60 1.60 136 50.40 0.28 187 85 226 213 169 68 29 16 187 186 85 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.21 311 1 32 300 300 1.60 1.60 139 0.64 45.47 185 93 226 213 167 75 29 16 185 94 93 183 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.18 1.00 1.50 1.37 0.43 SAFE
107 0.1 13.8 290 -34 -1 300 300 1.60 1.60 130 49.25 0.15 180 81 226 213 162 64 29 16 180 179 81 81 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.2 312 1 -32 300 300 1.60 1.60 139 0.62 45.92 186 93 226 213 168 75 29 16 186 94 93 184 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0.1 14.2 334 35 -1 300 300 1.60 1.60 148 50.51 0.30 198 97 226 213 181 79 29 16 198 198 97 97 450 0.65 57 622 394 0.09 0.14 12 200 0.65 57 585 382 0.09 0.15 12 200 69 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
10 101 0.1 0.21 263 -1 -1 300 300 1.60 1.60 120 0.26 0.20 121 120 184 170 103 102 29 16 121 120 120 120 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 41 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 13 0.2 263 -1 31 300 300 1.60 1.60 120 0.36 44.73 165 75 226 213 148 57 29 16 165 75 75 164 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 59 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
103 0.1 14.2 285 -35 -1 300 300 1.60 1.60 129 50.25 0.27 179 78 226 213 162 61 29 16 179 179 78 79 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 14 0.21 264 -1 -31 300 300 1.60 1.60 120 0.38 45.12 166 75 226 213 148 57 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0.1 13.8 241 34 -1 300 300 1.60 1.60 111 49.51 0.12 161 62 226 213 144 44 29 16 161 161 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 55 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.37 SAFE
106 13 0.2 263 -1 31 300 300 1.60 1.60 120 0.25 44.73 165 75 226 213 147 57 29 16 165 75 75 164 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 59 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
107 0.1 14.2 286 -35 -1 300 300 1.60 1.60 129 50.13 0.27 179 78 226 213 162 61 29 16 179 179 78 79 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 264 -1 -31 300 300 1.60 1.60 120 0.27 45.12 166 75 226 213 148 58 29 16 166 75 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0.1 13.8 241 34 -1 300 300 1.60 1.60 111 49.62 0.12 161 62 226 213 144 44 29 16 161 161 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 55 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.37 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
13 101 0 0.2 314 1 1 300 300 1.60 1.60 140 0.63 0.09 141 139 184 170 123 122 29 16 141 140 139 139 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.21 285 1 32 300 300 1.60 1.60 128 0.51 45.90 175 82 226 213 157 65 29 16 175 83 82 174 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
103 0 13.9 262 -34 1 300 300 1.60 1.60 120 49.62 0.13 169 70 226 213 152 52 29 16 169 169 70 70 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.21 284 1 -32 300 300 1.60 1.60 128 0.52 45.72 174 82 226 213 157 65 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
105 0 14.3 307 35 1 300 300 1.60 1.60 137 50.65 0.04 188 86 226 213 170 69 29 16 188 188 86 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.17 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.2 315 1 32 300 300 1.60 1.60 140 0.63 45.90 187 93 226 213 169 76 29 16 187 95 93 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0.1 13.9 292 -34 1 300 300 1.60 1.60 131 49.50 0.14 181 82 226 213 164 64 29 16 181 181 82 82 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 314 1 -32 300 300 1.60 1.60 140 0.63 45.72 186 94 226 213 169 76 29 16 186 95 94 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0 14.3 337 35 1 300 300 1.60 1.60 149 50.76 0.05 199 98 226 213 182 80 29 16 199 199 98 98 450 0.65 58 622 394 0.09 0.14 12 200 0.65 58 585 382 0.09 0.15 12 200 70 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
14 101 0 0.21 266 -1 1 300 300 1.60 1.60 121 0.25 0.08 121 121 184 170 104 103 29 16 121 121 121 121 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 42 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 14 0.21 266 -1 31 300 300 1.60 1.60 121 0.37 45.12 167 76 226 213 149 58 29 16 167 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0 14.3 288 -35 1 300 300 1.60 1.60 130 50.50 0.04 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 14 0.21 266 -1 -31 300 300 1.60 1.60 121 0.37 44.96 166 76 226 213 149 58 29 16 166 76 76 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0 13.9 244 34 1 300 300 1.60 1.60 112 49.76 0.13 162 62 226 213 145 45 29 16 162 162 62 63 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
106 14 0.21 266 -1 31 300 300 1.60 1.60 121 0.25 45.12 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0 14.3 288 -35 1 300 300 1.60 1.60 130 50.38 0.04 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 266 -1 -31 300 300 1.60 1.60 121 0.25 44.96 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0 13.9 244 35 1 300 300 1.60 1.60 112 49.87 0.13 162 62 226 213 145 45 29 16 162 162 62 63 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
17 101 0 0.21 314 1 -1 300 300 1.60 1.60 140 0.63 0.01 140 139 184 170 123 122 29 16 140 140 139 139 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.21 284 1 32 300 300 1.60 1.60 128 0.51 45.78 174 82 226 213 157 64 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
103 0 13.9 262 -34 1 300 300 1.60 1.60 119 49.64 0.01 169 70 226 213 152 52 29 16 169 169 70 70 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.21 284 1 -32 300 300 1.60 1.60 128 0.52 45.79 174 82 226 213 157 64 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
105 0 14.3 306 35 -1 300 300 1.60 1.60 137 50.67 0.02 187 86 226 213 170 69 29 16 187 187 86 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.17 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.21 314 1 32 300 300 1.60 1.60 140 0.63 45.78 186 93 226 213 169 76 29 16 186 95 93 185 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0 13.9 292 -34 1 300 300 1.60 1.60 131 49.52 0.01 181 82 226 213 163 64 29 16 181 181 82 82 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 314 1 -32 300 300 1.60 1.60 140 0.63 45.79 186 93 226 213 169 76 29 16 186 95 93 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0 14.3 336 35 -1 300 300 1.60 1.60 148 50.78 0.02 199 98 226 213 182 80 29 16 199 199 98 98 450 0.65 58 622 394 0.09 0.14 12 200 0.65 58 585 382 0.09 0.15 12 200 70 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
18 101 0 0.21 265 -1 -1 300 300 1.60 1.60 121 0.25 0.00 121 121 184 170 104 103 29 16 121 121 121 121 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 42 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 14 0.21 265 -1 31 300 300 1.60 1.60 121 0.37 45.02 166 75 226 213 149 58 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0 14.3 288 -35 -1 300 300 1.60 1.60 129 50.52 0.02 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 14 0.21 265 -1 -31 300 300 1.60 1.60 121 0.37 45.03 166 75 226 213 149 58 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0 13.9 243 34 1 300 300 1.60 1.60 112 49.78 0.01 162 62 226 213 145 45 29 16 162 162 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
106 14 0.21 265 -1 31 300 300 1.60 1.60 121 0.25 45.02 166 75 226 213 149 58 29 16 166 76 75 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0 14.3 288 -35 -1 300 300 1.60 1.60 129 50.40 0.02 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 265 -1 -31 300 300 1.60 1.60 121 0.25 45.03 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0 13.9 243 35 1 300 300 1.60 1.60 112 49.89 0.01 162 62 226 213 145 45 29 16 162 162 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
21 101 0 0.21 314 1 1 300 300 1.60 1.60 140 0.63 0.01 140 139 184 170 123 122 29 16 140 140 139 139 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.21 284 1 32 300 300 1.60 1.60 128 0.52 45.79 174 82 226 213 157 64 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
103 0 13.9 262 -34 -1 300 300 1.60 1.60 119 49.64 0.01 169 70 226 213 152 52 29 16 169 169 70 70 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.21 284 1 -32 300 300 1.60 1.60 128 0.51 45.78 174 82 226 213 157 64 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
105 0 14.3 306 35 1 300 300 1.60 1.60 137 50.67 0.02 187 86 226 213 170 69 29 16 187 187 86 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.17 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.21 314 1 32 300 300 1.60 1.60 140 0.63 45.79 186 93 226 213 169 76 29 16 186 95 93 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0 13.9 292 -34 -1 300 300 1.60 1.60 131 49.52 0.01 181 82 226 213 163 64 29 16 181 181 82 82 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 314 1 -32 300 300 1.60 1.60 140 0.63 45.78 186 93 226 213 169 76 29 16 186 95 93 185 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0 14.3 336 35 1 300 300 1.60 1.60 148 50.78 0.02 199 98 226 213 182 80 29 16 199 199 98 98 450 0.65 58 622 394 0.09 0.14 12 200 0.65 58 585 382 0.09 0.15 12 200 70 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
22 101 0 0.21 265 -1 1 300 300 1.60 1.60 121 0.25 0.00 121 121 184 170 104 103 29 16 121 121 121 121 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 42 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 14 0.21 265 -1 31 300 300 1.60 1.60 121 0.37 45.03 166 75 226 213 149 58 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0 14.3 288 -35 1 300 300 1.60 1.60 129 50.52 0.02 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 14 0.21 265 -1 -31 300 300 1.60 1.60 121 0.37 45.02 166 75 226 213 149 58 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0 13.9 243 34 -1 300 300 1.60 1.60 112 49.78 0.01 162 62 226 213 145 45 29 16 162 162 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
106 14 0.21 265 -1 31 300 300 1.60 1.60 121 0.25 45.03 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0 14.3 288 -35 1 300 300 1.60 1.60 129 50.40 0.02 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 265 -1 -31 300 300 1.60 1.60 121 0.25 45.02 166 75 226 213 149 58 29 16 166 76 75 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0 13.9 243 35 -1 300 300 1.60 1.60 112 49.89 0.01 162 62 226 213 145 45 29 16 162 162 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
25 101 0 0.2 314 1 -1 300 300 1.60 1.60 140 0.63 0.09 141 139 184 170 123 122 29 16 141 140 139 139 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.21 284 1 32 300 300 1.60 1.60 128 0.52 45.72 174 82 226 213 157 65 29 16 174 83 82 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
103 0 13.9 262 -34 -1 300 300 1.60 1.60 120 49.62 0.13 169 70 226 213 152 52 29 16 169 169 70 70 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.21 285 1 -32 300 300 1.60 1.60 128 0.51 45.90 175 82 226 213 157 65 29 16 175 83 82 174 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
105 0 14.3 307 35 -1 300 300 1.60 1.60 137 50.65 0.04 188 86 226 213 170 69 29 16 188 188 86 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.17 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.21 314 1 32 300 300 1.60 1.60 140 0.63 45.72 186 94 226 213 169 76 29 16 186 95 94 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0.1 13.9 292 -34 -1 300 300 1.60 1.60 131 49.50 0.14 181 82 226 213 164 64 29 16 181 181 82 82 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.2 315 1 -32 300 300 1.60 1.60 140 0.63 45.90 187 93 226 213 169 76 29 16 187 95 93 185 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
109 0 14.3 337 35 -1 300 300 1.60 1.60 149 50.76 0.05 199 98 226 213 182 80 29 16 199 199 98 98 450 0.65 58 622 394 0.09 0.14 12 200 0.65 58 585 382 0.09 0.15 12 200 70 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
26 101 0 0.21 266 -1 -1 300 300 1.60 1.60 121 0.25 0.08 121 121 184 170 104 103 29 16 121 121 121 121 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 42 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 14 0.21 266 -1 31 300 300 1.60 1.60 121 0.37 44.96 166 76 226 213 149 58 29 16 166 76 76 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0 14.3 288 -35 -1 300 300 1.60 1.60 130 50.50 0.04 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 14 0.21 266 -1 -31 300 300 1.60 1.60 121 0.37 45.12 167 76 226 213 149 58 29 16 167 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
105 0 13.9 244 34 -1 300 300 1.60 1.60 112 49.76 0.13 162 62 226 213 145 45 29 16 162 162 62 63 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
106 14 0.21 266 -1 31 300 300 1.60 1.60 121 0.25 44.96 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0 14.3 288 -35 -1 300 300 1.60 1.60 130 50.38 0.04 180 79 226 213 163 62 29 16 180 180 79 79 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 266 -1 -31 300 300 1.60 1.60 121 0.25 45.12 166 76 226 213 149 58 29 16 166 76 76 166 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
109 0 13.9 244 35 -1 300 300 1.60 1.60 112 49.87 0.13 162 62 226 213 145 45 29 16 162 162 62 63 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 56 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.38 SAFE
29 101 0.1 0.2 312 1 1 300 300 1.60 1.60 139 0.63 0.23 140 138 184 170 122 121 29 16 140 139 138 138 450 0.65 39 622 394 0.06 0.14 12 200 0.65 39 585 382 0.06 0.15 12 200 47 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.32 SAFE
102 14 0.2 283 1 32 300 300 1.60 1.60 128 0.51 45.90 174 81 226 213 157 64 29 16 174 82 81 173 450 0.65 50 622 394 0.07 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.41 SAFE
103 0.1 13.8 260 -34 1 300 300 1.60 1.60 119 49.37 0.13 168 69 226 213 151 52 29 16 168 168 69 69 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 61 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
104 14 0.21 281 1 -32 300 300 1.60 1.60 127 0.52 45.49 173 81 226 213 156 64 29 16 173 82 81 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
105 0.1 14.2 304 35 1 300 300 1.60 1.60 136 50.40 0.28 187 85 226 213 169 68 29 16 187 186 85 86 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
106 14 0.2 312 1 32 300 300 1.60 1.60 139 0.62 45.92 186 93 226 213 168 75 29 16 186 94 93 184 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 65 24 0.29 3.45 0.16 68 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0.1 13.8 290 -34 1 300 300 1.60 1.60 130 49.25 0.15 180 81 226 213 162 64 29 16 180 179 81 81 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 14 0.21 311 1 -32 300 300 1.60 1.60 139 0.64 45.47 185 93 226 213 167 75 29 16 185 94 93 183 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.18 1.00 1.50 1.37 0.43 SAFE
109 0.1 14.2 334 35 1 300 300 1.60 1.60 148 50.51 0.30 198 97 226 213 181 79 29 16 198 198 97 97 450 0.65 57 622 394 0.09 0.14 12 200 0.65 57 585 382 0.09 0.15 12 200 69 24 0.29 3.45 0.18 73 24 0.29 3.45 0.19 1.00 1.50 1.37 0.47 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
30 101 0.1 0.21 263 -1 1 300 300 1.60 1.60 120 0.26 0.20 121 120 184 170 103 102 29 16 121 120 120 120 450 0.65 33 622 394 0.05 0.14 12 200 0.65 33 585 382 0.05 0.15 12 200 40 24 0.29 3.45 0.10 41 24 0.29 3.45 0.11 1.00 1.50 1.37 0.27 SAFE
102 14 0.21 264 -1 31 300 300 1.60 1.60 120 0.38 45.12 166 75 226 213 148 57 29 16 166 76 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0.1 14.2 285 -35 1 300 300 1.60 1.60 129 50.25 0.27 179 78 226 213 162 61 29 16 179 179 78 79 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
104 13 0.2 263 -1 -31 300 300 1.60 1.60 120 0.36 44.73 165 75 226 213 148 57 29 16 165 75 75 164 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 59 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
105 0.1 13.8 241 34 1 300 300 1.60 1.60 111 49.51 0.12 161 62 226 213 144 44 29 16 161 161 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 55 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.37 SAFE
106 14 0.21 264 -1 31 300 300 1.60 1.60 120 0.27 45.12 166 75 226 213 148 58 29 16 166 75 75 165 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0.1 14.2 286 -35 1 300 300 1.60 1.60 129 50.13 0.27 179 78 226 213 162 61 29 16 179 179 78 79 450 0.65 51 622 394 0.08 0.14 12 200 0.65 51 585 382 0.08 0.15 12 200 62 24 0.29 3.45 0.16 65 24 0.29 3.45 0.17 1.00 1.50 1.37 0.42 SAFE
108 13 0.2 263 -1 -31 300 300 1.60 1.60 120 0.25 44.73 165 75 226 213 147 57 29 16 165 75 75 164 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 59 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
109 0.1 13.8 241 34 1 300 300 1.60 1.60 111 49.62 0.12 161 62 226 213 144 44 29 16 161 161 62 62 450 0.65 46 622 394 0.07 0.14 12 200 0.65 46 585 382 0.07 0.15 12 200 55 24 0.29 3.45 0.14 58 24 0.29 3.45 0.15 1.00 1.50 1.37 0.37 SAFE
33 101 0.6 0.2 324 1 -1 300 300 1.60 1.60 144 0.61 1.38 146 142 184 170 129 125 29 16 146 143 142 145 450 0.65 41 622 394 0.06 0.14 12 200 0.65 41 585 382 0.06 0.15 12 200 49 24 0.29 3.45 0.13 52 24 0.29 3.45 0.14 1.00 1.50 1.37 0.33 SAFE
102 13 0.18 290 1 31 300 300 1.60 1.60 131 0.42 44.94 176 85 226 213 159 68 29 16 176 86 85 175 450 0.65 50 622 394 0.08 0.14 12 200 0.65 50 585 382 0.08 0.15 12 200 61 24 0.29 3.45 0.15 64 24 0.29 3.45 0.17 1.00 1.50 1.37 0.41 SAFE
103 0.6 13.5 272 -33 -1 300 300 1.60 1.60 123 48.29 1.36 173 74 226 213 156 56 29 16 173 170 74 76 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 63 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
104 15 0.23 297 1 -33 300 300 1.60 1.60 133 0.59 47.44 181 85 226 213 164 68 29 16 181 86 85 180 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 63 24 0.29 3.45 0.16 66 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
105 0.5 13.9 315 34 -1 300 300 1.60 1.60 140 49.31 1.14 191 90 226 213 173 72 29 16 191 188 90 92 450 0.65 55 622 394 0.08 0.14 12 200 0.65 55 585 382 0.09 0.15 12 200 67 24 0.29 3.45 0.17 70 24 0.29 3.45 0.18 1.00 1.50 1.37 0.45 SAFE
106 13 0.18 321 1 31 300 300 1.60 1.60 143 0.53 44.82 188 97 226 213 171 80 29 16 188 98 97 187 450 0.65 54 622 394 0.08 0.14 12 200 0.65 54 585 382 0.09 0.15 12 200 66 24 0.29 3.45 0.17 69 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
107 0.7 13.5 303 -33 -2 300 300 1.60 1.60 136 48.19 1.49 185 86 226 213 168 69 29 16 185 182 86 89 450 0.65 53 622 394 0.08 0.14 12 200 0.65 53 585 382 0.09 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.18 1.00 1.50 1.37 0.44 SAFE
108 15 0.22 328 1 -33 300 300 1.60 1.60 145 0.70 47.57 193 97 226 213 176 80 29 16 193 98 97 192 450 0.65 56 622 394 0.08 0.14 12 200 0.65 56 585 382 0.09 0.15 12 200 68 24 0.29 3.45 0.17 71 24 0.29 3.45 0.19 1.00 1.50 1.37 0.46 SAFE
109 0.6 13.9 346 34 -1 300 300 1.60 1.60 152 49.41 1.27 203 102 226 213 186 84 29 16 203 200 102 104 450 0.65 59 622 394 0.09 0.14 12 200 0.65 59 585 382 0.09 0.15 12 200 71 24 0.29 3.45 0.18 75 24 0.29 3.45 0.20 1.00 1.50 1.37 0.48 SAFE
34 101 0.5 0.21 274 -1 -1 300 300 1.60 1.60 124 0.27 1.19 126 123 184 170 108 106 29 16 126 123 123 125 450 0.65 34 622 394 0.05 0.14 12 200 0.65 34 585 382 0.05 0.15 12 200 42 24 0.29 3.45 0.11 44 24 0.29 3.45 0.11 1.00 1.50 1.37 0.28 SAFE
102 13 0.23 271 -1 31 300 300 1.60 1.60 123 0.46 44.24 168 78 226 213 150 61 29 16 168 79 78 167 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
103 0.5 13.9 296 -34 -1 300 300 1.60 1.60 133 49.17 1.07 183 82 226 213 166 65 29 16 183 181 82 85 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
104 14 0.18 277 -1 -32 300 300 1.60 1.60 126 0.29 46.59 172 79 226 213 155 61 29 16 172 79 79 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 62 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
105 0.6 13.5 253 34 -1 300 300 1.60 1.60 116 48.42 1.29 166 66 226 213 148 49 29 16 166 163 66 69 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.07 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.38 SAFE
106 13 0.23 271 -1 31 300 300 1.60 1.60 123 0.36 44.23 168 79 226 213 150 61 29 16 168 79 79 167 450 0.65 48 622 394 0.07 0.14 12 200 0.65 48 585 382 0.08 0.15 12 200 58 24 0.29 3.45 0.15 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
107 0.5 13.9 296 -34 -1 300 300 1.60 1.60 133 49.07 1.08 183 83 226 213 166 65 29 16 183 181 83 85 450 0.65 52 622 394 0.08 0.14 12 200 0.65 52 585 382 0.08 0.15 12 200 64 24 0.29 3.45 0.16 67 24 0.29 3.45 0.17 1.00 1.50 1.37 0.43 SAFE
108 14 0.19 278 -1 -32 300 300 1.60 1.60 126 0.19 46.60 172 79 226 213 155 61 29 16 172 79 79 172 450 0.65 49 622 394 0.07 0.14 12 200 0.65 49 585 382 0.08 0.15 12 200 60 24 0.29 3.45 0.15 62 24 0.29 3.45 0.16 1.00 1.50 1.37 0.40 SAFE
109 0.6 13.5 253 34 -1 300 300 1.60 1.60 116 48.52 1.30 166 66 226 213 148 49 29 16 166 163 66 69 450 0.65 47 622 394 0.07 0.14 12 200 0.65 47 585 382 0.08 0.15 12 200 57 24 0.29 3.45 0.14 60 24 0.29 3.45 0.16 1.00 1.50 1.37 0.39 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
37 101 2.8 0.21 255 1 5 300 300 1.45 1.45 138 0.85 8.10 147 129 184 170 130 112 24 13 147 131 129 146 450 0.58 32 622 394 0.05 0.14 12 200 0.58 32 585 382 0.05 0.15 12 200 35 24 0.29 3.45 0.09 38 24 0.29 3.45 0.10 1.00 1.50 1.37 0.33 SAFE
102 16 0.07 238 1 34 300 300 1.45 1.45 130 0.03 66.36 197 64 226 213 180 47 24 13 197 64 64 197 450 0.58 45 622 394 0.07 0.14 12 200 0.58 45 585 382 0.07 0.15 12 200 49 24 0.29 3.45 0.12 52 24 0.29 3.45 0.14 1.00 1.50 1.37 0.45 SAFE
103 2.5 12 211 -30 4 300 300 1.45 1.45 118 57.69 7.17 182 53 226 213 165 35 24 13 182 168 53 67 450 0.58 41 622 394 0.06 0.14 12 200 0.58 41 585 382 0.07 0.15 12 200 45 24 0.29 3.45 0.11 48 24 0.29 3.45 0.13 1.00 1.50 1.37 0.42 SAFE
104 10 0.35 223 1 -27 300 300 1.45 1.45 123 1.35 51.71 176 70 226 213 159 53 24 13 176 73 70 174 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
105 2.6 12.4 251 31 4 300 300 1.45 1.45 136 59.07 7.49 203 70 226 213 185 52 24 13 203 188 70 85 450 0.58 46 622 394 0.07 0.14 12 200 0.58 46 585 382 0.07 0.15 12 200 50 24 0.29 3.45 0.13 54 24 0.29 3.45 0.14 1.00 1.50 1.37 0.47 SAFE
106 16 0.07 263 1 35 300 300 1.45 1.45 142 0.18 67.14 209 75 226 213 192 57 24 13 209 75 75 209 450 0.58 48 622 394 0.07 0.14 12 200 0.58 48 585 382 0.08 0.15 12 200 52 24 0.29 3.45 0.13 56 24 0.29 3.45 0.15 1.00 1.50 1.37 0.49 SAFE
107 2.8 12 235 -30 5 300 300 1.45 1.45 129 57.53 7.94 195 64 226 213 177 46 24 13 195 179 64 79 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
108 10 0.35 248 1 -26 300 300 1.45 1.45 135 1.51 50.93 187 82 226 213 170 65 24 13 187 85 82 184 450 0.58 42 622 394 0.06 0.14 12 200 0.58 42 585 382 0.07 0.15 12 200 46 24 0.29 3.45 0.12 49 24 0.29 3.45 0.13 1.00 1.50 1.37 0.43 SAFE
109 2.8 12.4 275 31 5 300 300 1.45 1.45 148 59.23 8.27 215 80 226 213 198 63 24 13 215 199 80 97 450 0.58 49 622 394 0.07 0.14 12 200 0.58 49 585 382 0.08 0.15 12 200 54 24 0.29 3.45 0.14 57 24 0.29 3.45 0.15 1.00 1.50 1.37 0.50 SAFE
38 101 2.4 0.2 216 -1 4 300 300 1.45 1.45 120 0.34 6.91 127 112 184 170 110 95 24 13 127 113 112 126 450 0.58 27 622 394 0.04 0.14 12 200 0.58 27 585 382 0.04 0.15 12 200 30 24 0.29 3.45 0.08 32 24 0.29 3.45 0.08 1.00 1.50 1.37 0.28 SAFE
102 15 0.34 224 -1 33 300 300 1.45 1.45 123 1.16 64.90 189 57 226 213 172 40 24 13 189 60 57 187 450 0.58 43 622 394 0.06 0.14 12 200 0.58 43 585 382 0.07 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.44 SAFE
103 2.4 12.4 235 -30 4 300 300 1.45 1.45 129 58.87 7.03 195 63 226 213 178 46 24 13 195 181 63 77 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
104 10 0.06 208 1 -26 300 300 1.45 1.45 116 0.17 51.16 167 65 226 213 150 47 24 13 167 65 65 167 450 0.58 37 622 394 0.06 0.14 12 200 0.58 37 585 382 0.06 0.15 12 200 41 24 0.29 3.45 0.10 43 24 0.29 3.45 0.11 1.00 1.50 1.37 0.38 SAFE
105 2.3 12 196 30 4 300 300 1.45 1.45 110 57.88 6.71 175 46 226 213 158 29 24 13 175 162 46 59 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
106 15 0.34 224 -1 33 300 300 1.45 1.45 123 1.01 64.94 189 57 226 213 172 40 24 13 189 59 57 187 450 0.58 43 622 394 0.06 0.14 12 200 0.58 43 585 382 0.07 0.15 12 200 47 24 0.29 3.45 0.12 50 24 0.29 3.45 0.13 1.00 1.50 1.37 0.44 SAFE
107 2.4 12.4 235 -30 4 300 300 1.45 1.45 129 58.72 7.07 195 63 226 213 178 46 24 13 195 181 63 77 450 0.58 44 622 394 0.07 0.14 12 200 0.58 44 585 382 0.07 0.15 12 200 48 24 0.29 3.45 0.12 51 24 0.29 3.45 0.13 1.00 1.50 1.37 0.45 SAFE
108 10 0.06 208 1 -26 300 300 1.45 1.45 116 0.32 51.12 167 65 226 213 150 47 24 13 167 65 65 167 450 0.58 37 622 394 0.06 0.14 12 200 0.58 37 585 382 0.06 0.15 12 200 41 24 0.29 3.45 0.10 43 24 0.29 3.45 0.11 1.00 1.50 1.37 0.38 SAFE
109 2.4 12 196 30 4 300 300 1.45 1.45 110 58.03 6.75 175 46 226 213 158 28 24 13 175 162 46 59 450 0.58 39 622 394 0.06 0.14 12 200 0.58 39 585 382 0.06 0.15 12 200 43 24 0.29 3.45 0.11 46 24 0.29 3.45 0.12 1.00 1.50 1.37 0.40 SAFE
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., Plot No:943,54th Tiruppur City Municipal Corporation, New Tiruppur Area Development
street, TVS Colony, Anna Nagar West Ext, Chennai Tiruppur. Corporation Ltd (NTADCL), Tiruppur.
2 C1 2 300 300 1667.53 1.85 4 20 4 16 2061 2.29 0.81 SAFE 8 190 8 190 SAFE
3 C2 7 300 300 2087.17 2.32 4 20 4 20 2513 2.79 0.83 SAFE 8 190 8 190 SAFE
4 C2 8 300 300 2012.44 2.24 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
5 C2 13 300 300 2096.01 2.33 4 20 4 20 2513 2.79 0.83 SAFE 8 190 8 190 SAFE
6 C2 14 300 300 1993.45 2.21 4 20 4 20 2513 2.79 0.79 SAFE 8 190 8 190 SAFE
7 C2 19 300 300 2114.33 2.35 4 20 4 20 2513 2.79 0.84 SAFE 8 190 8 190 SAFE
8 C2 20 300 300 2011.01 2.23 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
9 C2 25 300 300 2110.93 2.35 4 20 4 20 2513 2.79 0.84 SAFE 8 190 8 190 SAFE
10 C2 26 300 300 2007.76 2.23 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
11 C2 31 300 300 2110.93 2.35 4 20 4 20 2513 2.79 0.84 SAFE 8 190 8 190 SAFE
12 C2 32 300 300 2007.76 2.23 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
13 C2 37 300 300 2114.33 2.35 4 20 4 20 2513 2.79 0.84 SAFE 8 190 8 190 SAFE
14 C2 38 300 300 2011.01 2.23 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
15 C2 43 300 300 2096.01 2.33 4 20 4 20 2513 2.79 0.83 SAFE 8 190 8 190 SAFE
16 C2 44 300 300 1993.45 2.21 4 20 4 20 2513 2.79 0.79 SAFE 8 190 8 190 SAFE
17 C2 49 300 300 2087.17 2.32 4 20 4 20 2513 2.79 0.83 SAFE 8 190 8 190 SAFE
15 C2 50 300 300 2012.44 2.24 4 20 4 20 2513 2.79 0.80 SAFE 8 190 8 190 SAFE
16 C1 55 300 300 1783.17 1.98 4 20 4 16 2061 2.29 0.87 SAFE 8 190 8 190 SAFE
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
1 FB1 70 x mid 369.01 0.21 2 20 628 0.35 0.59 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 300 2 8 150
600 end 683.75 0.38 2 20 1 20 942 0.52 0.73 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 300 2 8 150
300 Start 873.32 0.49 2 20 1 20 942 0.52 0.93 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
6000
2 FB1 5 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 613.04 0.341 2 20 1 16 829 0.46 0.74 SAFE 2 8í 170 2 8 150
600 end 1191.19 0.66 2 20 1 20 2 16 1345 0.75 0.89 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
300 Start 1153.42 0.64 2 20 1 20 2 16 1345 0.75 0.86 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
6000
3 FB1 11 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 476.05 0.264 2 20 1 12 741 0.41 0.64 SAFE 2 8í 170 2 8 150
600 end 1061.38 0.59 2 20 1 20 2 16 1345 0.75 0.79 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
300 Start 1081.30 0.60 2 20 1 20 2 16 1345 0.75 0.80 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
4 FB1 17 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 503.85 0.280 2 16 1 12 515 0.29 0.98 SAFE 2 8í 170 2 8 150
600 end 1095.96 0.61 2 20 1 20 2 16 1345 0.75 0.82 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 1092.66 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
5 FB1 23 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 497.74 0.277 2 16 1 12 515 0.29 0.97 SAFE 2 8í 170 2 8 150
600 end 1089.78 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 1090.54 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
6000
6 FB1 29 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 499.33 0.277 2 16 1 12 515 0.29 0.97 SAFE 2 8í 170 2 8 150
600 end 1090.54 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
300 Start 1089.78 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
7 FB1 35 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 497.74 0.277 2 16 1 12 515 0.29 0.97 SAFE 2 8í 170 2 8 150
600 end 1092.66 0.61 2 20 1 20 2 16 1345 0.75 0.81 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 1095.96 0.61 2 20 1 20 2 16 1345 0.75 0.82 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
8 FB1 41 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 503.85 0.280 2 16 1 12 515 0.29 0.98 SAFE 2 8í 170 2 8 150
600 end 1081.30 0.60 2 20 1 20 2 16 1345 0.75 0.80 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 1061.38 0.59 2 20 1 20 2 16 1345 0.75 0.79 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
6000
9 FB1 47 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 476.05 0.264 2 20 1 12 741 0.41 0.64 SAFE 2 8í 170 2 8 150
600 end 1153.42 0.64 2 20 1 20 2 16 1345 0.75 0.86 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
300 Start 1191.19 0.66 2 20 1 20 2 16 1345 0.75 0.89 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
6000
10 FB1 53 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 613.04 0.341 2 20 1 16 829 0.46 0.74 SAFE 2 8í 170 2 8 150
600 end 873.32 0.49 2 20 1 20 942 0.52 0.93 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 170 2 8 150
300 Start 683.74 0.38 2 20 1 20 942 0.52 0.73 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 300 2 8 150
2000
11 FB1 67 x mid 369.00 0.21 2 20 628 0.35 0.59 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 300 2 8 150
600 end 0.00 0.00 2 20 628 0.35 0.00 SAFE 0.00 0.000 2 20 628 0.35 0.00 SAFE 2 8í 300 2 8 150
300 Start 0.00 0.00 2 20 628 0.35 0.00 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
2000
1 FB2 69 x mid 308.52 0.17 2 20 628 0.35 0.49 SAFE 0.00 0.000 2 16 1 12 515 0.29 0.00 SAFE 2 8í 300 2 8 150
600 end 563.64 0.31 2 20 1 20 942 0.52 0.60 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
300 Start 825.02 0.46 2 20 1 20 942 0.52 0.88 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
6000
2 FB2 6 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 537.01 0.298 2 16 1 12 2 12 741 0.41 0.72 SAFE 2 8í 170 2 8 150
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
300 Start 1050.81 0.58 2 20 1 20 2 16 1345 0.75 0.78 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
3 FB2 12 x mid 279.99 0.16 2 20 628 0.35 0.45 SAFE 402.43 0.224 2 16 1 12 515 0.29 0.78 SAFE 2 8í 170 2 8 150
600 end 986.09 0.55 2 20 1 20 2 12 1169 0.65 0.84 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
300 Start 983.09 0.55 2 20 1 20 2 12 1169 0.65 0.84 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
6000
4 FB2 18 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 420.17 0.233 2 16 1 12 515 0.29 0.82 SAFE 2 8í 170 2 8 150
600 end 996.14 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 993.09 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
5 FB2 24 x mid 279.99 0.16 2 20 628 0.35 0.45 SAFE 413.80 0.230 2 16 1 12 515 0.29 0.80 SAFE 2 8í 170 2 8 150
600 end 990.51 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
300 Start 991.22 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
6000
6 FB2 30 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 414.84 0.230 2 16 1 12 515 0.29 0.81 SAFE 2 8í 170 2 8 150
600 end 991.22 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
300 Start 990.51 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
6000
7 FB2 36 x mid 279.99 0.16 2 20 628 0.35 0.45 SAFE 413.80 0.230 2 16 1 12 515 0.29 0.80 SAFE 2 8í 170 2 8 150
600 end 993.09 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 996.14 0.55 2 20 1 20 2 12 1169 0.65 0.85 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
8 FB2 42 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 420.17 0.233 2 16 1 12 515 0.29 0.82 SAFE 2 8í 170 2 8 150
600 end 983.09 0.55 2 20 1 20 2 12 1169 0.65 0.84 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
300 Start 986.09 0.55 2 20 1 20 2 12 1169 0.65 0.84 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
6000
9 FB2 48 x mid 279.99 0.16 2 20 628 0.35 0.45 SAFE 402.43 0.224 2 16 1 12 515 0.29 0.78 SAFE 2 8í 170 2 8 150
600 end 1050.81 0.58 2 20 1 20 2 16 1345 0.75 0.78 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
300 Start 1114.40 0.62 2 20 1 20 2 16 1345 0.75 0.83 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 170 2 8 150
6000
10 FB2 54 x mid 0.00 0.00 2 20 628 0.35 0.00 SAFE 537.01 0.298 2 16 1 12 2 12 741 0.41 0.72 SAFE 2 8í 170 2 8 150
600 end 825.02 0.46 2 20 1 20 942 0.52 0.88 SAFE 279.99 0.156 2 16 402 0.22 0.70 SAFE 2 8í 170 2 8 150
300 Start 563.64 0.31 2 20 1 20 942 0.52 0.60 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
2000
11 FB2 68 x mid 308.52 0.17 2 20 628 0.35 0.49 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
600 end 0.00 0.00 2 20 628 0.35 0.00 SAFE 0.00 0.000 2 16 402 0.22 0.00 SAFE 2 8í 300 2 8 150
300 Start 393.95 0.44 2 16 1 12 515 0.57 0.76 SAFE 376.85 0.419 2 16 1 12 515 0.57 0.73 SAFE 2 8í 100 2 8 100
2550
1 FB3 57 x mid 177.04 0.20 2 16 402 0.45 0.44 SAFE 194.86 0.217 2 16 1 12 515 0.57 0.38 SAFE 2 8í 100 2 8 100
300 end 394.71 0.44 2 16 1 12 515 0.57 0.77 SAFE 376.33 0.418 2 16 1 12 515 0.57 0.73 SAFE 2 8í 100 2 8 100
300 Start 427.90 0.48 2 16 1 12 515 0.57 0.83 SAFE 412.93 0.459 2 16 1 12 515 0.57 0.80 SAFE 2 8í 100 2 8 100
2550
1 FB3 58 x mid 192.68 0.21 2 16 402 0.45 0.48 SAFE 209.76 0.233 2 16 1 12 515 0.57 0.41 SAFE 2 8í 100 2 8 100
300 end 430.29 0.48 2 16 1 12 515 0.57 0.84 SAFE 411.41 0.457 2 16 1 12 515 0.57 0.80 SAFE 2 8í 100 2 8 100
300 Start 441.03 0.49 2 16 1 12 515 0.57 0.86 SAFE 425.58 0.473 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 59 x mid 198.17 0.22 2 16 402 0.45 0.49 SAFE 215.07 0.239 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
300 end 442.75 0.49 2 16 1 12 515 0.57 0.86 SAFE 424.48 0.472 2 16 1 12 515 0.57 0.82 SAFE 2 8í 100 2 8 100
300 Start 444.43 0.49 2 16 1 12 515 0.57 0.86 SAFE 428.96 0.477 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 60 x mid 199.63 0.22 2 16 402 0.45 0.50 SAFE 216.50 0.241 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
300 Start 444.95 0.49 2 16 1 12 515 0.57 0.86 SAFE 429.50 0.477 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 61 x mid 199.87 0.22 2 16 402 0.45 0.50 SAFE 216.74 0.241 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
300 end 446.66 0.50 2 16 1 12 515 0.57 0.87 SAFE 428.42 0.476 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
300 Start 444.95 0.49 2 16 1 12 515 0.57 0.86 SAFE 429.50 0.477 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 62 x mid 199.87 0.22 2 16 402 0.45 0.50 SAFE 216.74 0.241 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
300 end 446.66 0.50 2 16 1 12 515 0.57 0.87 SAFE 428.42 0.476 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
300 Start 444.43 0.49 2 16 1 12 515 0.57 0.86 SAFE 428.96 0.477 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 63 x mid 199.63 0.22 2 16 402 0.45 0.50 SAFE 216.50 0.241 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
300 end 446.13 0.50 2 16 1 12 515 0.57 0.87 SAFE 427.90 0.475 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
300 Start 441.03 0.49 2 16 1 12 515 0.57 0.86 SAFE 425.58 0.473 2 16 1 12 515 0.57 0.83 SAFE 2 8í 100 2 8 100
2550
1 FB3 64 x mid 198.17 0.22 2 16 402 0.45 0.49 SAFE 215.07 0.239 2 16 1 12 515 0.57 0.42 SAFE 2 8í 100 2 8 100
300 end 442.75 0.49 2 16 1 12 515 0.57 0.86 SAFE 424.48 0.472 2 16 1 12 515 0.57 0.82 SAFE 2 8í 100 2 8 100
300 Start 427.90 0.48 2 16 1 12 515 0.57 0.83 SAFE 412.93 0.459 2 16 1 12 515 0.57 0.80 SAFE 2 8í 100 2 8 100
2550
1 FB3 65 x mid 192.68 0.21 2 16 402 0.45 0.48 SAFE 209.76 0.233 2 16 1 12 515 0.57 0.41 SAFE 2 8í 100 2 8 100
300 end 430.30 0.48 2 16 1 12 515 0.57 0.84 SAFE 411.41 0.457 2 16 1 12 515 0.57 0.80 SAFE 2 8í 100 2 8 100
300 Start 393.95 0.44 2 16 1 12 515 0.57 0.76 SAFE 376.85 0.419 2 16 1 12 515 0.57 0.73 SAFE 2 8í 100 2 8 100
2550
1 FB3 66 x mid 177.04 0.20 2 16 402 0.45 0.44 SAFE 194.86 0.217 2 16 1 12 515 0.57 0.38 SAFE 2 8í 100 2 8 100
300 end 394.71 0.44 2 16 1 12 515 0.57 0.77 SAFE 376.33 0.418 2 16 1 12 515 0.57 0.73 SAFE 2 8í 100 2 8 100
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
INPUT DATA
LOAD CALCULATIONS
Seismic load
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 28.41 mm
2
fs = M/Ast1(d-x/3) = 140.16 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001099
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000306
The average surface strain em
em (e1-e2) = 0.000793
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 89.24
Cmin = 30
The design crack width W cr = 0.10
Hence Safe against cracking
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF OUTER WALL FOR INLET CHANNEL: (Along the length) Wall - W11
Properties of material
fck = 30 N/mm2
fy = 500 N/mm2
Dimensions
Thickness of Wall D = 200 mm
Clear cover to rebar C = 45 mm
Dia of main rebar = 10 mm
Eff. Thickness of Wall d = 150 mm
(200-45-10/2)
Height of Liquid /wall = 1900 mm (406.3-404.9+0.5)x1000
Unit weight of liquid = 9.81 kN/m3
Maximum Bending moment causing tension in the sewage / soilface = 16.28 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 42.18 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
2
fs = M/Ast1(d-x/3) = 190.6 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001395
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000291
The average surface strain em
em (e1-e2) = 0.001104
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 75.04
Cmin = 45
The design crack width W cr = 0.18
Hence Safe against cracking
Maximum Bending moment causing tension in the sewage / soilface = 7.66 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 42.18 mm
2
fs = M/Ast1(d-x/3) = 89.68 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000656
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000291
The average surface strain em
em (e1-e2) = 0.000365
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 75.04
Cmin = 45
The design crack width W cr = 0.06
Hence Safe against cracking
Bottom moment of base slab (Due to self weight of base slab &Liquid):
Unfactored moment = 19.21 kNm (Tension @ bottom)
Load factor = 1.5
Mu = 28.8 kNm
Percentage of steel required = 0.311 %
Area of steel reqd @ bottom = 467 mm2 (0.311x1000x150/100)
Depth of Surface Zone = 100 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ bottom = 350 mm2 (0.35x1000x100/100)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Spacing of reinft. Reqd. = 168 mm
Spacing of reinft. Provided = 100 mm
Maximum Bending moment causing tension in the sewage / soilface = 19.21 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.22 mm
2
fs = M/Ast1(d-x/3) = 181.77 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001347
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.001111
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.17
Hence Safe against cracking
Bottom moment of base slab (Fixed end moment of inlet channel wall):
Unfactored moment = 16.28 kNm (Tension @ Top)
Load factor = 1.5
Mu 24.4 kNm
Percentage of steel required = 0.260 %
Area of steel reqd @ Top = 390 mm2 (0.26x1000x150/100)
Depth of Surface Zone = 100.0 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ Top = 350 mm2
Spacing of reinft. Reqd. = 201 mm
Spacing of reinft. Provided = 150 mm
Area of steel provided @ Top = 524 mm2 Safe
(1000/150x0.7854x10^2)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 16.28 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 44.82 mm
2
fs = M/Ast1(d-x/3) = 207.2 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001338
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000216
The average surface strain em
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
em (e1-e2) = 0.001122
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 77.76
Cmin = 30
The design crack width W cr = 0.16
Hence Safe against cracking
Provide Y10 at 200mm c/c as horizontal steel on liquid face and outer face. Safe
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 18.03 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.06 mm
2
fs = M/Ast1(d-x/3) = 170.49 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001263
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.001027
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.16
Hence Safe against cracking
Maximum Bending moment causing tension in the sewage / soilface = 8.51 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.06 mm
2
fs = M/Ast1(d-x/3) = 80.47 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000596
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.00036
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.06
Hence Safe against cracking
Bottom moment of base slab (Due to self weight of base slab &Liquid):
Unfactored moment = 19.31 kNm (Tension @ bottom)
Load factor = 1.5
Mu = 29.0 kNm
Percentage of steel required = 0.312 %
Area of steel reqd @ bottom = 468 mm2 (0.312x1000x150/100)
Depth of Surface Zone = 100 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ bottom = 350 mm2 (0.35x1000x100/100)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 19.31 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.22 mm
2
fs = M/Ast1(d-x/3) = 182.64 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001353
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.001117
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.17
Hence Safe against cracking
Bottom moment of base slab (Fixed end moment of inlet channel wall):
Unfactored moment = 18.03 kNm (Tension @ Top)
Load factor = 1.5
Mu 27.0 kNm
Percentage of steel required = 0.290 %
Area of steel reqd @ Top = 435 mm2 (0.29x1000x150/100)
Depth of Surface Zone = 100.0 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ Top = 350 mm2
Spacing of reinft. Reqd. = 181 mm
Spacing of reinft. Provided = 150 mm
Area of steel provided @ Top = 524 mm2 Safe
(1000/150x0.7854x10^2)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 18.03 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 44.82 mm
2
fs = M/Ast1(d-x/3) = 229.47 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001481
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000216
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
fck = 30 N/mm2
fy = 500 N/mm2
Cover = 50 mm
Depth of excavation = 0.80 m from FGL
Depth of excavation = 0.75 m from FGL
gsoil = 18 kN/m3
gcon = 25 kN/m3
Net SBC = 170 kN/m2
Width assumed = 1.00 m
d/2 d
d/2
Column moment, My
Column moment, Mz
Bc Lc
Z L
Support Moment, Mz X
Support Moment, Mx
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
1 101 40 0.5 192 1 -61 300 450 1.75 2.40 63 0.67 36.03 100 26 184 170 82 9 47 26 100 27 26 98 450 0.73 32 622 394 0.05 0.14 12 200 0.98 59 585 382 0.09 0.20 12 150 41 24 0.29 3.45 0.10 73 18 0.33 3.45 0.19 0.67 1.17 1.37 0.24 SAFE
102 23 0.49 167 1 -21 300 450 1.75 2.40 57 0.64 12.32 70 44 226 213 53 27 47 26 70 45 44 69 450 0.73 21 622 394 0.03 0.14 12 200 0.98 37 585 382 0.06 0.20 12 150 26 24 0.29 3.45 0.07 47 18 0.33 3.45 0.12 0.67 1.17 1.37 0.16 SAFE
103 36 8.09 162 -22 -54 300 450 1.75 2.40 56 17.50 31.84 105 6 226 213 88 -11 47 26 105 41 6 70 450 0.73 35 622 394 0.05 0.14 12 200 0.98 63 585 382 0.10 0.20 12 150 44 24 0.29 3.45 0.11 78 18 0.33 3.45 0.20 0.67 1.17 1.37 0.26 SAFE
104 50 0.5 181 1 -89 300 450 1.75 2.40 60 0.59 52.51 113 7 226 213 96 -10 47 26 113 8 7 112 450 0.73 38 622 394 0.06 0.14 12 200 0.98 69 585 382 0.11 0.20 12 150 48 24 0.29 3.45 0.12 86 18 0.33 3.45 0.22 0.67 1.17 1.37 0.28 SAFE
105 37 9.08 186 23 -56 300 450 1.75 2.40 62 18.73 32.99 113 10 226 213 96 -7 47 26 113 47 10 76 450 0.73 38 622 394 0.06 0.14 12 200 0.98 68 585 382 0.11 0.20 12 150 48 24 0.29 3.45 0.12 85 18 0.33 3.45 0.22 0.67 1.17 1.37 0.28 SAFE
106 27 0.5 184 1 -27 300 450 1.75 2.40 61 0.70 15.93 78 44 226 213 60 27 47 26 78 46 44 76 450 0.73 24 622 394 0.04 0.14 12 200 0.98 43 585 382 0.07 0.20 12 150 30 24 0.29 3.45 0.08 54 18 0.33 3.45 0.14 0.67 1.17 1.37 0.18 SAFE
107 40 8.09 179 -22 -60 300 450 1.75 2.40 60 17.45 35.45 113 7 226 213 95 -10 47 26 113 42 7 78 450 0.73 38 622 394 0.06 0.14 12 200 0.98 68 585 382 0.11 0.20 12 150 47 24 0.29 3.45 0.12 85 18 0.33 3.45 0.22 0.67 1.17 1.37 0.28 SAFE
108 54 0.5 199 1 -95 300 450 1.75 2.40 65 0.64 56.12 121 8 226 213 104 -10 47 26 121 9 8 120 450 0.73 41 622 394 0.06 0.14 12 200 0.98 74 585 382 0.12 0.20 12 150 52 24 0.29 3.45 0.13 92 18 0.33 3.45 0.24 0.67 1.17 1.37 0.31 SAFE
109 41 9.09 204 24 -62 300 450 1.75 2.40 66 18.78 36.60 121 10 226 213 104 -7 47 26 121 48 10 84 450 0.73 41 622 394 0.06 0.14 12 200 0.98 74 585 382 0.12 0.20 12 150 52 24 0.29 3.45 0.13 92 18 0.33 3.45 0.24 0.67 1.17 1.37 0.31 SAFE
2 101 5.8 0.9 196 2 -10 300 300 1.25 1.25 141 4.22 28.65 174 108 184 170 158 92 12 13 174 117 108 165 300 0.48 27 239 244 0.10 0.23 12 200 0.48 27 216 232 0.12 0.24 12 200 55 15 0.36 3.45 0.22 58 14 0.36 3.45 0.25 1.00 1.50 1.37 0.51 SAFE
102 0.4 0.73 185 2 5 300 300 1.25 1.25 134 3.43 14.11 152 117 226 213 136 101 12 13 152 124 117 145 300 0.48 23 239 244 0.09 0.23 12 200 0.48 23 216 232 0.10 0.24 12 200 47 15 0.36 3.45 0.19 50 14 0.36 3.45 0.21 1.00 1.50 1.37 0.44 SAFE
103 6.2 6.8 189 -17 -11 300 300 1.25 1.25 137 50.28 31.81 219 55 226 213 203 39 12 13 219 155 55 118 300 0.48 34 239 244 0.14 0.23 12 200 0.48 34 216 232 0.15 0.24 12 200 70 15 0.36 3.45 0.29 74 14 0.36 3.45 0.32 1.00 1.50 1.37 0.65 SAFE
104 12 0.62 195 1 -23 300 300 1.25 1.25 141 2.79 70.26 214 68 226 213 198 52 12 13 214 73 68 208 300 0.48 33 239 244 0.13 0.23 12 200 0.48 33 216 232 0.15 0.24 12 200 69 15 0.36 3.45 0.28 72 14 0.36 3.45 0.31 1.00 1.50 1.37 0.63 SAFE
105 5.1 8.15 191 19 -8 300 300 1.25 1.25 138 56.50 24.35 219 57 226 213 203 41 12 13 219 170 57 106 300 0.48 34 239 244 0.14 0.23 12 200 0.48 34 216 232 0.15 0.24 12 200 70 15 0.36 3.45 0.29 74 14 0.36 3.45 0.32 1.00 1.50 1.37 0.65 SAFE
106 0.3 0.95 191 2 5 300 300 1.25 1.25 138 4.54 13.53 156 120 226 213 140 104 12 13 156 129 120 147 300 0.48 24 239 244 0.09 0.23 12 200 0.48 24 216 232 0.10 0.24 12 200 48 15 0.36 3.45 0.20 51 14 0.36 3.45 0.22 1.00 1.50 1.37 0.45 SAFE
107 6.3 6.58 195 -17 -11 300 300 1.25 1.25 140 49.17 32.39 222 59 226 213 206 43 12 13 222 157 59 124 300 0.48 35 239 244 0.14 0.23 12 200 0.48 35 216 232 0.15 0.24 12 200 71 15 0.36 3.45 0.29 75 14 0.36 3.45 0.32 1.00 1.50 1.37 0.66 SAFE
108 12 0.84 201 2 -24 300 300 1.25 1.25 144 3.90 70.83 219 69 226 213 203 53 12 13 219 77 69 211 300 0.48 34 239 244 0.14 0.23 12 200 0.48 34 216 232 0.15 0.24 12 200 70 15 0.36 3.45 0.29 74 14 0.36 3.45 0.32 1.00 1.50 1.37 0.65 SAFE
109 5.2 8.37 197 19 -9 300 300 1.25 1.25 142 57.61 24.92 224 59 226 213 208 43 12 13 224 174 59 109 300 0.48 35 239 244 0.14 0.23 12 200 0.48 35 216 232 0.15 0.24 12 200 72 15 0.36 3.45 0.30 76 14 0.36 3.45 0.33 1.00 1.50 1.37 0.67 SAFE
3 101 9.3 2.07 109 -3 -13 300 300 1.50 1.50 66 3.70 22.89 92 39 184 170 75 22 25 14 92 46 39 85 450 0.60 20 622 394 0.03 0.14 12 200 0.60 20 585 382 0.03 0.15 12 200 23 24 0.29 3.45 0.06 25 24 0.29 3.45 0.06 1.00 1.50 1.37 0.19 SAFE
102 2.6 1.66 91 -2 1 300 300 1.50 1.50 57 2.96 0.34 61 54 226 213 43 37 25 14 61 60 54 55 450 0.60 12 622 394 0.02 0.14 12 200 0.60 12 585 382 0.02 0.15 12 200 13 24 0.29 3.45 0.03 14 24 0.29 3.45 0.04 1.00 1.50 1.37 0.11 SAFE
103 9.2 12.1 112 -24 -14 300 300 1.50 1.50 67 41.56 23.41 132 2 226 213 114 -16 25 14 132 85 2 49 450 0.60 31 622 394 0.05 0.14 12 200 0.60 31 585 382 0.05 0.15 12 200 35 24 0.29 3.45 0.09 37 24 0.29 3.45 0.10 1.00 1.50 1.37 0.29 SAFE
104 15 2 104 -3 -25 300 300 1.50 1.50 63 3.86 42.86 110 17 226 213 93 -1 25 14 110 24 17 102 450 0.60 25 622 394 0.04 0.14 12 200 0.60 25 585 382 0.04 0.15 12 200 29 24 0.29 3.45 0.07 30 24 0.29 3.45 0.08 1.00 1.50 1.37 0.24 SAFE
105 8.1 8.48 83 20 -11 300 300 1.50 1.50 54 34.74 19.11 108 0 226 213 91 -17 25 14 108 70 0 38 450 0.60 24 622 394 0.04 0.14 12 200 0.60 24 585 382 0.04 0.15 12 200 28 24 0.29 3.45 0.07 30 24 0.29 3.45 0.08 1.00 1.50 1.37 0.23 SAFE
106 3.3 1.9 103 -2 -1 300 300 1.50 1.50 63 3.25 1.29 67 58 226 213 50 41 25 14 67 65 58 61 450 0.60 13 622 394 0.02 0.14 12 200 0.60 13 585 382 0.02 0.15 12 200 15 24 0.29 3.45 0.04 16 24 0.29 3.45 0.04 1.00 1.50 1.37 0.13 SAFE
107 9.9 12.4 124 -24 -15 300 300 1.50 1.50 72 41.85 25.04 139 5 226 213 122 -12 25 14 139 89 5 55 450 0.60 33 622 394 0.05 0.14 12 200 0.60 33 585 382 0.05 0.15 12 200 38 24 0.29 3.45 0.10 40 24 0.29 3.45 0.10 1.00 1.50 1.37 0.31 SAFE
108 15 2.24 116 -3 -26 300 300 1.50 1.50 69 4.15 44.49 117 20 226 213 100 3 25 14 117 28 20 109 450 0.60 27 622 394 0.04 0.14 12 200 0.60 27 585 382 0.04 0.15 12 200 31 24 0.29 3.45 0.08 33 24 0.29 3.45 0.09 1.00 1.50 1.37 0.26 SAFE
109 8.7 8.24 95 20 -12 300 300 1.50 1.50 59 34.45 20.74 115 4 226 213 97 -13 25 14 115 73 4 46 450 0.60 26 622 394 0.04 0.14 12 200 0.60 26 585 382 0.04 0.15 12 200 30 24 0.29 3.45 0.08 32 24 0.29 3.45 0.08 1.00 1.50 1.37 0.25 SAFE
6 101 37 1.54 211 2 53 300 450 1.75 2.40 68 1.16 31.27 100 35 184 170 83 18 47 26 100 37 35 98 450 0.73 33 622 394 0.05 0.14 12 200 0.98 59 585 382 0.09 0.20 12 150 41 24 0.29 3.45 0.10 73 18 0.33 3.45 0.19 0.67 1.17 1.37 0.24 SAFE
102 47 1.77 195 3 81 300 450 1.75 2.40 64 2.04 48.15 114 14 226 213 97 -4 47 26 114 18 14 110 450 0.73 38 622 394 0.06 0.14 12 200 0.98 69 585 382 0.11 0.20 12 150 48 24 0.29 3.45 0.12 86 18 0.33 3.45 0.22 0.67 1.17 1.37 0.29 SAFE
103 34 12.7 168 -35 49 300 450 1.75 2.40 57 27.96 28.59 114 1 226 213 96 -17 47 26 114 57 1 58 450 0.73 38 622 394 0.06 0.14 12 200 0.98 69 585 382 0.11 0.20 12 150 48 24 0.29 3.45 0.12 86 18 0.33 3.45 0.22 0.67 1.17 1.37 0.29 SAFE
104 19 0.64 179 -1 14 300 450 1.75 2.40 60 0.37 7.93 68 52 226 213 51 34 47 26 68 52 52 68 450 0.73 20 622 394 0.03 0.14 12 200 0.98 36 585 382 0.06 0.20 12 150 25 24 0.29 3.45 0.06 45 18 0.33 3.45 0.12 0.67 1.17 1.37 0.15 SAFE
105 33 15.1 207 37 47 300 450 1.75 2.40 66 29.63 27.49 124 9 226 213 106 -8 47 26 124 69 9 64 450 0.73 42 622 394 0.06 0.14 12 200 0.98 76 585 382 0.12 0.20 12 150 53 24 0.29 3.45 0.13 94 18 0.33 3.45 0.25 0.67 1.17 1.37 0.31 SAFE
106 51 2.11 219 3 87 300 450 1.75 2.40 69 2.37 51.38 123 16 226 213 106 -2 47 26 123 20 16 118 450 0.73 42 622 394 0.06 0.14 12 200 0.98 75 585 382 0.12 0.20 12 150 53 24 0.29 3.45 0.13 94 18 0.33 3.45 0.25 0.67 1.17 1.37 0.31 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
107 37 12.4 192 -34 54 300 450 1.75 2.40 63 27.63 31.82 122 3 226 213 105 -14 47 26 122 59 3 67 450 0.73 41 622 394 0.06 0.14 12 200 0.98 75 585 382 0.12 0.20 12 150 52 24 0.29 3.45 0.13 93 18 0.33 3.45 0.24 0.67 1.17 1.37 0.31 SAFE
108 23 0.97 203 -1 19 300 450 1.75 2.40 66 0.04 11.15 77 54 226 213 59 37 47 26 77 55 54 77 450 0.73 23 622 394 0.03 0.14 12 200 0.98 42 585 382 0.07 0.20 12 150 30 24 0.29 3.45 0.07 53 18 0.33 3.45 0.14 0.67 1.17 1.37 0.18 SAFE
109 37 15.5 231 37 52 300 450 1.75 2.40 72 29.95 30.71 133 11 226 213 115 -6 47 26 133 71 11 73 450 0.73 46 622 394 0.07 0.14 12 200 0.98 82 585 382 0.13 0.20 12 150 57 24 0.29 3.45 0.15 103 18 0.33 3.45 0.27 0.67 1.17 1.37 0.34 SAFE
8 101 5.5 0.49 78 3 6 300 300 1.25 1.25 66 6.69 15.40 88 44 184 170 72 28 12 13 88 57 44 74 300 0.48 12 239 244 0.05 0.23 12 200 0.48 12 216 232 0.05 0.24 12 200 25 15 0.36 3.45 0.10 26 14 0.36 3.45 0.11 1.00 1.50 1.37 0.23 SAFE
102 11 0.42 79 -1 17 300 300 1.25 1.25 66 1.39 50.04 118 15 226 213 102 -1 12 13 118 18 15 115 300 0.48 17 239 244 0.07 0.23 12 200 0.48 17 216 232 0.07 0.24 12 200 35 15 0.36 3.45 0.14 37 14 0.36 3.45 0.16 1.00 1.50 1.37 0.33 SAFE
103 4.4 3.41 71 -10 4 300 300 1.25 1.25 61 30.48 10.06 102 21 226 213 86 5 12 13 102 82 21 41 300 0.48 15 239 244 0.06 0.23 12 200 0.48 15 216 232 0.06 0.24 12 200 30 15 0.36 3.45 0.12 31 14 0.36 3.45 0.13 1.00 1.50 1.37 0.28 SAFE
104 0.8 1.37 65 5 -8 300 300 1.25 1.25 57 13.79 22.76 94 21 226 213 78 5 12 13 94 48 21 66 300 0.48 13 239 244 0.05 0.23 12 200 0.48 13 216 232 0.06 0.24 12 200 27 15 0.36 3.45 0.11 28 14 0.36 3.45 0.12 1.00 1.50 1.37 0.25 SAFE
105 5.5 4.36 73 14 6 300 300 1.25 1.25 62 42.87 17.22 122 2 226 213 106 -14 12 13 122 88 2 37 300 0.48 18 239 244 0.07 0.23 12 200 0.48 18 216 232 0.08 0.24 12 200 37 15 0.36 3.45 0.15 39 14 0.36 3.45 0.17 1.00 1.50 1.37 0.34 SAFE
106 11 0.41 85 -1 17 300 300 1.25 1.25 70 0.90 51.80 123 18 226 213 107 2 12 13 123 19 18 121 300 0.48 18 239 244 0.07 0.23 12 200 0.48 18 216 232 0.08 0.24 12 200 37 15 0.36 3.45 0.15 39 14 0.36 3.45 0.17 1.00 1.50 1.37 0.34 SAFE
107 5 3.4 78 -10 4 300 300 1.25 1.25 65 29.98 11.83 107 24 226 213 91 8 12 13 107 84 24 47 300 0.48 15 239 244 0.06 0.23 12 200 0.48 15 216 232 0.07 0.24 12 200 32 15 0.36 3.45 0.13 33 14 0.36 3.45 0.14 1.00 1.50 1.37 0.29 SAFE
108 0.3 1.38 71 5 -7 300 300 1.25 1.25 61 14.28 20.99 97 26 226 213 81 10 12 13 97 55 26 68 300 0.48 14 239 244 0.05 0.23 12 200 0.48 14 216 232 0.06 0.24 12 200 28 15 0.36 3.45 0.11 29 14 0.36 3.45 0.13 1.00 1.50 1.37 0.26 SAFE
109 6.1 4.37 79 15 7 300 300 1.25 1.25 66 43.37 18.98 129 4 226 213 113 -12 12 13 129 91 4 42 300 0.48 19 239 244 0.07 0.23 12 200 0.48 19 216 232 0.08 0.24 12 200 39 15 0.36 3.45 0.16 41 14 0.36 3.45 0.18 1.00 1.50 1.37 0.36 SAFE
9 101 12 1.9 145 3 14 300 300 1.25 1.25 109 7.01 41.99 158 60 184 170 142 44 12 13 158 74 60 144 300 0.48 24 239 244 0.09 0.23 12 200 0.48 24 216 232 0.10 0.24 12 200 49 15 0.36 3.45 0.20 52 14 0.36 3.45 0.22 1.00 1.50 1.37 0.45 SAFE
102 20 0.93 133 1 31 300 300 1.25 1.25 101 1.90 94.18 197 5 226 213 181 -11 12 13 197 9 5 193 300 0.48 31 239 244 0.12 0.23 12 200 0.48 31 216 232 0.13 0.24 12 200 63 15 0.36 3.45 0.26 66 14 0.36 3.45 0.28 1.00 1.50 1.37 0.58 SAFE
103 9.9 5.15 119 -12 12 300 300 1.25 1.25 92 35.84 34.38 162 21 226 213 146 5 12 13 162 93 21 90 300 0.48 25 239 244 0.10 0.23 12 200 0.48 25 216 232 0.11 0.24 12 200 51 15 0.36 3.45 0.21 53 14 0.36 3.45 0.23 1.00 1.50 1.37 0.47 SAFE
104 1.6 2.01 125 3 -6 300 300 1.25 1.25 96 8.71 15.94 120 71 226 213 104 55 12 13 120 88 71 103 300 0.48 18 239 244 0.07 0.23 12 200 0.48 18 216 232 0.08 0.24 12 200 36 15 0.36 3.45 0.15 38 14 0.36 3.45 0.16 1.00 1.50 1.37 0.33 SAFE
105 11 8.09 140 16 15 300 300 1.25 1.25 105 46.45 43.87 195 15 226 213 179 -1 12 13 195 108 15 102 300 0.48 30 239 244 0.12 0.23 12 200 0.48 30 216 232 0.13 0.24 12 200 62 15 0.36 3.45 0.25 65 14 0.36 3.45 0.28 1.00 1.50 1.37 0.57 SAFE
106 21 1.36 149 2 32 300 300 1.25 1.25 111 3.60 97.05 212 11 226 213 196 -5 12 13 212 18 11 205 300 0.48 33 239 244 0.13 0.23 12 200 0.48 33 216 232 0.15 0.24 12 200 68 15 0.36 3.45 0.28 71 14 0.36 3.45 0.31 1.00 1.50 1.37 0.63 SAFE
107 11 4.72 135 -12 13 300 300 1.25 1.25 102 34.14 37.25 173 30 226 213 157 15 12 13 173 99 30 105 300 0.48 27 239 244 0.10 0.23 12 200 0.48 27 216 232 0.12 0.24 12 200 55 15 0.36 3.45 0.22 57 14 0.36 3.45 0.25 1.00 1.50 1.37 0.50 SAFE
108 2.6 2.45 141 4 -5 300 300 1.25 1.25 106 10.41 13.06 129 83 226 213 113 67 12 13 129 103 83 109 300 0.48 19 239 244 0.08 0.23 12 200 0.48 19 216 232 0.08 0.24 12 200 39 15 0.36 3.45 0.16 41 14 0.36 3.45 0.18 1.00 1.50 1.37 0.36 SAFE
109 12 8.52 156 16 16 300 300 1.25 1.25 115 48.15 46.74 210 20 226 213 194 5 12 13 210 117 20 114 300 0.48 33 239 244 0.13 0.23 12 200 0.48 33 216 232 0.14 0.24 12 200 67 15 0.36 3.45 0.28 71 14 0.36 3.45 0.31 1.00 1.50 1.37 0.62 SAFE
10 101 7.8 2.25 107 -3 10 300 300 1.25 1.25 84 8.33 28.41 121 47 184 170 105 31 12 13 121 64 47 104 300 0.48 18 239 244 0.07 0.23 12 200 0.48 18 216 232 0.08 0.24 12 200 36 15 0.36 3.45 0.15 38 14 0.36 3.45 0.16 1.00 1.50 1.37 0.34 SAFE
102 12 2.51 102 -4 19 300 300 1.25 1.25 81 10.81 58.08 150 12 226 213 134 -4 12 13 150 34 12 128 300 0.48 23 239 244 0.09 0.23 12 200 0.48 23 216 232 0.10 0.24 12 200 46 15 0.36 3.45 0.19 49 14 0.36 3.45 0.21 1.00 1.50 1.37 0.43 SAFE
103 8.3 8.18 106 -16 11 300 300 1.25 1.25 84 47.02 33.47 164 3 226 213 148 -13 12 13 164 97 3 70 300 0.48 25 239 244 0.10 0.23 12 200 0.48 25 216 232 0.11 0.24 12 200 51 15 0.36 3.45 0.21 54 14 0.36 3.45 0.23 1.00 1.50 1.37 0.48 SAFE
104 2.1 1.16 88 -1 -2 300 300 1.25 1.25 72 3.02 5.54 80 63 226 213 64 47 12 13 80 69 63 74 300 0.48 11 239 244 0.04 0.23 12 200 0.48 11 216 232 0.05 0.24 12 200 22 15 0.36 3.45 0.09 23 14 0.36 3.45 0.10 1.00 1.50 1.37 0.21 SAFE
105 6 4.51 83 11 7 300 300 1.25 1.25 69 33.19 19.07 121 17 226 213 105 1 12 13 121 83 17 55 300 0.48 18 239 244 0.07 0.23 12 200 0.48 18 216 232 0.08 0.24 12 200 36 15 0.36 3.45 0.15 38 14 0.36 3.45 0.17 1.00 1.50 1.37 0.34 SAFE
106 13 2.92 114 -4 20 300 300 1.25 1.25 88 12.23 60.22 161 16 226 213 145 0 12 13 161 40 16 136 300 0.48 25 239 244 0.10 0.23 12 200 0.48 25 216 232 0.11 0.24 12 200 50 15 0.36 3.45 0.21 53 14 0.36 3.45 0.23 1.00 1.50 1.37 0.46 SAFE
107 8.9 8.59 118 -16 12 300 300 1.25 1.25 91 48.44 35.61 175 7 226 213 159 -9 12 13 175 104 7 79 300 0.48 27 239 244 0.11 0.23 12 200 0.48 27 216 232 0.12 0.24 12 200 55 15 0.36 3.45 0.23 58 14 0.36 3.45 0.25 1.00 1.50 1.37 0.51 SAFE
108 2.7 1.57 100 -2 -2 300 300 1.25 1.25 79 4.44 3.39 87 72 226 213 71 56 12 13 87 80 72 78 300 0.48 12 239 244 0.05 0.23 12 200 0.48 12 216 232 0.05 0.24 12 200 25 15 0.36 3.45 0.10 26 14 0.36 3.45 0.11 1.00 1.50 1.37 0.23 SAFE
109 6.6 4.1 95 11 7 300 300 1.25 1.25 76 31.77 21.21 129 23 226 213 113 7 12 13 129 87 23 66 300 0.48 19 239 244 0.08 0.23 12 200 0.48 19 216 232 0.08 0.24 12 200 39 15 0.36 3.45 0.16 41 14 0.36 3.45 0.18 1.00 1.50 1.37 0.36 SAFE
11 101 7.8 0.31 82 -1 -10 300 300 1.25 1.25 68 0.45 29.06 97 38 184 170 81 22 12 13 97 39 38 97 300 0.48 14 239 244 0.05 0.23 12 200 0.48 14 216 232 0.06 0.24 12 200 28 15 0.36 3.45 0.12 30 14 0.36 3.45 0.13 1.00 1.50 1.37 0.26 SAFE
102 1.8 0.58 68 3 3 300 300 1.25 1.25 59 6.50 6.18 72 47 226 213 56 31 12 13 72 60 47 59 300 0.48 10 239 244 0.04 0.23 12 200 0.48 10 216 232 0.04 0.24 12 200 19 15 0.36 3.45 0.08 20 14 0.36 3.45 0.09 1.00 1.50 1.37 0.18 SAFE
103 5.9 3.39 74 -10 -7 300 300 1.25 1.25 63 29.05 19.12 111 15 226 213 95 -1 12 13 111 73 15 53 300 0.48 16 239 244 0.06 0.23 12 200 0.48 16 216 232 0.07 0.24 12 200 33 15 0.36 3.45 0.13 35 14 0.36 3.45 0.15 1.00 1.50 1.37 0.30 SAFE
Contractor: Client: CMSC:
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
104 12 1.02 81 -3 -19 300 300 1.25 1.25 68 6.84 58.02 133 3 226 213 117 -13 12 13 133 17 3 119 300 0.48 20 239 244 0.08 0.23 12 200 0.48 20 216 232 0.09 0.24 12 200 40 15 0.36 3.45 0.17 43 14 0.36 3.45 0.18 1.00 1.50 1.37 0.37 SAFE
105 8.1 2.95 76 10 -11 300 300 1.25 1.25 64 28.71 32.72 126 3 226 213 110 -13 12 13 126 60 3 68 300 0.48 19 239 244 0.07 0.23 12 200 0.48 19 216 232 0.08 0.24 12 200 38 15 0.36 3.45 0.16 40 14 0.36 3.45 0.17 1.00 1.50 1.37 0.35 SAFE
106 2.6 0.49 75 3 1 300 300 1.25 1.25 64 6.22 3.04 73 55 226 213 57 39 12 13 73 67 55 61 300 0.48 10 239 244 0.04 0.23 12 200 0.48 10 216 232 0.04 0.24 12 200 20 15 0.36 3.45 0.08 21 14 0.36 3.45 0.09 1.00 1.50 1.37 0.18 SAFE
107 6.7 3.48 80 -10 -8 300 300 1.25 1.25 67 29.32 22.27 119 16 226 213 103 0 12 13 119 74 16 60 300 0.48 17 239 244 0.07 0.23 12 200 0.48 17 216 232 0.08 0.24 12 200 36 15 0.36 3.45 0.15 37 14 0.36 3.45 0.16 1.00 1.50 1.37 0.33 SAFE
108 13 1.11 88 -3 -20 300 300 1.25 1.25 72 7.11 61.17 140 4 226 213 124 -12 12 13 140 18 4 126 300 0.48 21 239 244 0.08 0.23 12 200 0.48 21 216 232 0.09 0.24 12 200 43 15 0.36 3.45 0.18 45 14 0.36 3.45 0.20 1.00 1.50 1.37 0.40 SAFE
109 8.8 2.86 83 10 -12 300 300 1.25 1.25 69 28.43 35.87 133 4 226 213 117 -12 12 13 133 61 4 76 300 0.48 20 239 244 0.08 0.23 12 200 0.48 20 216 232 0.09 0.24 12 200 41 15 0.36 3.45 0.17 43 14 0.36 3.45 0.18 1.00 1.50 1.37 0.38 SAFE
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., Plot No:943,54th Tiruppur City Municipal Corporation, New Tiruppur Area Development
street, TVS Colony, Anna Nagar West Ext, Chennai Tiruppur. Corporation Ltd (NTADCL), Tiruppur.
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
DESIGN OF COLUMN
2 C6 2 300 300 1292.94 1.44 4 20 4 12 1709 1.90 0.76 SAFE 8 190 8 175 SAFE
3 C5 3 300 450 3529.33 2.61 4 25 6 20 3848 2.85 0.92 SAFE 8 300 8 175 SAFE
4 C6 4 300 300 1582.60 1.76 4 20 4 12 1709 1.90 0.93 SAFE 8 190 8 175 SAFE
5 C6 5 300 300 1346.84 1.50 4 20 4 12 1709 1.90 0.79 SAFE 8 190 8 175 SAFE
6 C6 6 300 300 659.19 0.73 4 20 4 12 1709 1.90 0.39 SAFE 8 255 8 175 SAFE
7 C6 7 300 300 1468.33 1.63 4 20 4 12 1709 1.90 0.86 SAFE 8 255 8 175 SAFE
8 C6 8 300 300 1021.37 1.13 4 20 4 12 1709 1.90 0.60 SAFE 8 300 8 175 SAFE
9 C6 9 300 300 741.63 0.82 4 20 4 12 1709 1.90 0.43 SAFE 8 255 8 175 SAFE
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
Length (mm)
1 B2 10 x mid 0.00 0.00 3 20 942 0.52 0.00 SAFE 923.20 0.513 3 20 942 0.52 0.98 SAFE 2 8í 170 2 8 100
600 end 882.56 0.49 3 20 942 0.52 0.94 SAFE 0.00 0.000 3 20 942 0.52 0.00 SAFE 2 8í 170 2 8 100
300 Start 483.99 0.16 3 20 942 0.31 0.51 SAFE 480.68 0.160 3 20 942 0.31 0.51 SAFE 2 8í 200 2 8 100
7250
1 B5 11 x mid 483.99 0.16 3 20 942 0.31 0.51 SAFE 480.68 0.160 3 20 942 0.31 0.51 SAFE 2 8í 200 2 8 100
1000 end 656.42 0.22 3 20 942 0.31 0.70 SAFE 0.00 0.000 3 20 942 0.31 0.00 SAFE 2 8í 200 2 8 100
300 Start 923.80 0.68 3 20 942 0.70 0.98 SAFE 537.90 0.398 3 20 942 0.70 0.57 SAFE 2 8í 130 2 8 100
4845
1 B3 18 x mid 203.49 0.15 3 20 942 0.70 0.22 SAFE 681.67 0.505 3 20 942 0.70 0.72 SAFE 2 8í 130 2 8 100
450 end 414.72 0.31 3 20 942 0.70 0.44 SAFE 0.00 0.000 3 20 942 0.70 0.00 SAFE 2 8í 130 2 8 100
300 Start 440.82 0.49 3 20 942 1.05 0.47 SAFE 0.00 0.000 3 16 603 0.67 0.00 SAFE 2 8í 100 2 8 100
2595
1 B6 12 x mid 0.00 0.00 3 20 942 1.05 0.00 SAFE 292.62 0.325 3 16 603 0.67 0.49 SAFE 2 8í 100 2 8 100
300 end 367.56 0.41 3 20 942 1.05 0.39 SAFE 126.99 0.141 3 16 603 0.67 0.21 SAFE 2 8í 100 2 8 100
300 Start 415.35 0.46 3 20 942 1.05 0.44 SAFE 0.00 0.000 3 16 603 0.67 0.00 SAFE 2 8í 100 2 8 100
2595
1 B6 13 x mid 0.00 0.00 3 20 942 1.05 0.00 SAFE 468.83 0.521 3 16 603 0.67 0.78 SAFE 2 8í 100 2 8 100
300 end 351.99 0.39 3 20 942 1.05 0.37 SAFE 0.00 0.000 3 16 603 0.67 0.00 SAFE 2 8í 100 2 8 100
300 Start 369.47 0.41 3 20 942 1.05 0.39 SAFE 227.50 0.253 3 16 603 0.67 0.38 SAFE 2 8í 100 2 8 100
2300
1 B4 16 x mid 126.99 0.14 3 20 942 1.05 0.13 SAFE 221.17 0.246 3 16 603 0.67 0.37 SAFE 2 8í 100 2 8 100
300 end 268.46 0.30 3 20 942 1.05 0.28 SAFE 151.83 0.169 3 16 603 0.67 0.25 SAFE 2 8í 100 2 8 100
300 Start 333.31 0.37 3 20 942 1.05 0.35 SAFE 237.76 0.264 3 16 603 0.67 0.39 SAFE 2 8í 100 2 8 100
2400
1 B4 19 x mid 240.12 0.27 3 20 942 1.05 0.25 SAFE 252.31 0.280 3 16 603 0.67 0.42 SAFE 2 8í 100 2 8 100
300 end 367.61 0.41 3 20 942 1.05 0.39 SAFE 362.86 0.403 3 16 603 0.67 0.60 SAFE 2 8í 100 2 8 100
300 Start 536.86 0.60 3 20 942 1.05 0.57 SAFE 431.24 0.479 3 16 603 0.67 0.71 SAFE 2 8í 100 2 8 100
2400
1 B1 20 x mid 318.39 0.35 3 20 942 1.05 0.34 SAFE 259.51 0.288 3 16 603 0.67 0.43 SAFE 2 8í 100 2 8 100
300 end 659.80 0.73 3 20 942 1.05 0.70 SAFE 453.69 0.504 3 16 603 0.67 0.75 SAFE 2 8í 100 2 8 100
300 Start 313.78 0.35 3 20 942 1.05 0.33 SAFE 150.30 0.167 3 16 603 0.67 0.25 SAFE 2 8í 100 2 8 100
2300
1 B1 14 x mid 126.99 0.14 3 20 942 1.05 0.13 SAFE 184.36 0.205 3 16 603 0.67 0.31 SAFE 2 8í 100 2 8 100
300 end 277.63 0.31 3 20 942 1.05 0.29 SAFE 164.28 0.183 3 16 603 0.67 0.27 SAFE 2 8í 100 2 8 100
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
OUTLET TANK
3.600
FGL
Assuming
Water table at
H 3.000 FGL
Tank
a/b = 0.30
Moody's chart - Max. horizontal moment coeff. for P1 & P2 = 0.010
Fig 5 Max. vertical moment coeff. for P1 & P2 = 0.012
Horizontal Moment due to water + sub soil 0.0104 x 44.72 x 6.6^2 = 20.26 kNm
Vertical Moment due to water + sub soil 0.0121 x 44.72 x 6.6^2 = 23.57 kNm
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
27.77 41.66 300 1000 102 244 525 905 0.370 12 125 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 80.04 9.33 51 1131 55.31 4E+08 136.86 0.0003 0.057 SAFE - Wcr<0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
25.62 38.43 300 1000 98 232 525 1131 0.490 12 100 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 70.71 9.33 51 1131 58.61 4E+08 107.66 0.0002 0.045 SAFE - Wcr<0.2
Provide Y12 at 125 mm c/c upto FGL and provide Y10 at 200 mm c/c above ground level as
vertical reinforcement.
Provide Y12 at 100 mm c/c as horizontal reinforcement and Y10 at 200 mm c/c above FGL.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
0.00
WL
H1
6.60
Tank
Water
P1
Forces due to active pressure (per meter length of wall)
P1 - 9.81 x 6.6 = 64.75 kN/m
Moody's chart - Max. horizontal moment coeff. for P1 = 0.0154
Fig 4 Max. vertical moment coeff. for P1 = 0.0146
Vertical Moment due to water 0.0146 x 64.75 x 6.6^2 = 41.18 kNm
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
41.18 61.77 300 1000 124 249 594 1131 0.454 12 100 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
45 67.3 9.33 56 905 61.77 4E+08 160.3 0.0006 0.095 SAFE - Wcr<0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
43.44 65.15 300 1000 128 237 663 1257 0.530 12 90 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
45 63.6 9.33 56 1131 62.48 4E+08 161.13 0.0007 0.108 SAFE - Wcr<0.2
Provide Y12 at 100 mm c/c as vertical rein. and Y12 at 90 mm c/c as Horizontal reinforcement.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
OUTLET TANK
3.600
FGL
Assuming
Water table at
H 3.000 FGL
Tank
a/b = 0.46
Moody's chart - Max. horizontal moment coeff. for P1 & P2 = 0.016
Fig 5 Max. vertical moment coeff. for P1 & P2 = 0.020
Horizontal Moment due to water + sub soil 0.0161 x 44.72 x 6.6^2 = 31.36 kNm
Vertical Moment due to water + sub soil 0.02 x 44.72 x 6.6^2 = 38.96 kNm
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
46.89 70.34 300 1000 133 244 695 905 0.370 12 125 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 80.04 9.33 51 1131 55.31 4E+08 231.08 0.0009 0.172 SAFE - Wcr<0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
40.57 60.86 300 1000 124 232 631 1131 0.490 12 100 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 70.71 9.33 51 1131 58.61 4E+08 170.49 0.0007 0.122 SAFE - Wcr<0.2
Provide Y12 at 125 mm c/c upto FGL and provide Y10 at 200 mm c/c above ground level as
vertical reinforcement.
Provide Y12 at 100 mm c/c as horizontal reinforcement and Y10 at 200 mm c/c above FGL.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
0.00
WL
H1
6.60
Tank
Water
P1
Forces due to active pressure (per meter length of wall)
P1 - 9.81 x 6.6 = 64.75 kN/m
Moody's chart - Max. horizontal moment coeff. for P1 = 0.0268
Fig 4 Max. vertical moment coeff. for P1 = 0.0260
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
73.33 110.00 300 1000 166 249 1096 1131 0.454 12 100 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
45 67.3 9.33 56 905 61.77 4E+08 285.46 0.0013 0.227 UNSAFE-Wcr>0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
75.59 113.38 300 1000 169 237 1202 1257 0.530 12 90 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
45 63.6 9.33 56 1131 62.48 4E+08 280.4 0.0014 0.238 UNSAFE-Wcr>0.2
Provide Y12 at 100 mm c/c as vertical rein. and Y12 at 90 mm c/c as Horizontal reinforcement.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Tank
24.87 kN/m2
Height of water table from FGL at bottom of slab 3.0 + 0.3 = 3.300 m
2
Uplift pressure at the bottom of base slab 3.3 x 9.81 = 32.37 kN/m
2
Self wt of base slab 0.3 x 25 = 7.500 kN/m
2
Net Uplift pressure at the bottom of base slab 32.37 - 7.5 = 24.87 kN/m
a/b = 0.80
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.8 9.33 56 565 47.00 2E+08 257.54 0.0007 0.153 SAFE - Wcr<0.2
3
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.8 9.33 56 565 47.00 2E+08 197.79 0.0003 0.069 SAFE - Wcr<0.2
Minimum Reinforcement:
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
Top reinforcement:
Provide Y12 at 200 mm c/c along x axis and Y12 at 200 mm c/c along y axis as top reinforcement.
Bottom reinforcement:
4
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF FLASH MIXER
DESIGN OF WALKWAY SLAB (Platform Slab around external wall)
Mu/bd2 = 0.938
For M30 and Fe500, percentage of reinforcement,
pt = 0.5*Fck/Fy*(1-sqrt (1-(Mu/bd2)*4.589/Fck)* 100
= 0.224 %
Ast = Pt/100*b*d
= 201.6 mm2 0.224/100*1000*90
Assumed diameter of the slab reinft = 10 mm
Minimum % of reinforcement = 0.3 %
Depth of surface zone = 125
Minimum area of reinforcement = 375 mm2
Spacing of 10mm dia bars = 209.44 mm Af/Ast.*1000
Spacing of bars provided = 200 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 26.9 mm
2
fs = M/Ast1(d-x/3) = 159.19 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001237
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000347
The average surface strain em
em (e1-e2) = 0.00089
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 100.95
Cmin = 30
The design crack width W cr = 0.11
Hence Safe against cracking
Contractor: Client: CMSC:
Structural Data:
STAAD Results:
Contractor: Client: CMSC:
Ast Required =
2
Ast Required for Moment = 270 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Contractor: Client: CMSC:
(((11.39*10^6)/137.96)/392.7)
2
Concrete stress 'fc' = 4.57 N/mm
(2*11.39*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Contractor: Client: CMSC:
Ast Required =
2
Ast Required for Moment = 203 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/200*0.7854*0*0)
Hence Provided Ast is ok
(((8.636*10^6)/137.96)/392.7)
2
Concrete stress 'fc' = 3.46 N/mm
(2*8.636*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Strain Es in steel for the stress of = 0.00079705 mm
(159.41/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0011470 mm
(((200-36.134)/(150-36.134))*0.00079705)
Strain due to stiffening effect of concrete ε2
Structural Data:
STAAD Results:
Contractor: Client: CMSC:
Ast Required =
2
Ast Required for Moment = 199 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
Contractor: Client: CMSC:
(((8.48*10^6)/137.96)/392.7)
2
Concrete stress 'fc' = 3.4 N/mm
(2*8.48*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Strain Es in steel for the stress of = 0.00078265 mm
(156.53/200000)
Contractor: Client: CMSC:
Ast Required =
Contractor: Client: CMSC:
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/200*0.7854*0*0)
Hence Provided Ast is ok
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
(((11.435*10^6)/137.96)/392.7)
2
Concrete stress 'fc' = 4.59 N/mm
(2*11.435*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Strain Es in steel for the stress of = 0.00105535 mm
(211.07/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0015188 mm
(((200-36.134)/(150-36.134))*0.00105535)
Strain due to stiffening effect of concrete ε2
Crack Width
Structural Data:
Ast Required =
2
Ast Required for Moment = 348 mm
2
Ast Provided = 524 mm
(1000/150*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
(((9.5*10^6)/89.27)/523.6)
2
Concrete stress 'fc' = 6.61 N/mm
(2*9.5*10^6)/(1000*32.197*89.27)
Distance 'a' = 150 mm
Strain Es in steel for the stress of = 0.00101625 mm
(203.25/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0017657 mm
(((150-32.197)/(100-32.197))*0.00101625)
Strain due to stiffening effect of concrete ε2
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire
EPE/196MLD/DC/STR/DC, FM, FL&IPS - 112A 01.02.2020
project on design build, operate and transfer basis for new water supply
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
2
Maximum actual base pressure below base slab = 35.41 kN/m SAFE
(SBC after compaction is considered to be 50 kN/Sqm on the conservative side)
WALL FOUNDATION:
Check for Base Pressure: (Footing is designed for per meter length)
2
Base Pressure Pmax (P/A + M/Z) = 144.12 kN/m B.PR < SBC
2
Base Pressure Pmin (P/A - M/Z) = 37.20 kN/m SAFE
Reinforcement Details:
2
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Mu/bd2 = 0.938
For M30 and Fe500, percentage of reinforcement,
pt = 0.5*Fck/Fy*(1-sqrt (1-(Mu/bd2)*4.589/Fck)* 100
= 0.224 %
Ast = Pt/100*b*d
= 201.6 mm2 0.224/100*1000*90
Assumed diameter of the slab reinft = 10 mm
Minimum % of reinforcement = 0.35 %
Depth of surface zone = 125
Minimum area of reinforcement = 437.5 mm2
Spacing of 10mm dia bars = 179.52 mm Af/Ast.*1000
Spacing of bars provided = 100 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 35.39 mm
2
fs = M/Ast1(d-x/3) = 82.47 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000677
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000183
The average surface strain em
em (e1-e2) = 0.000494
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 56.03
Cmin = 30
The design crack width W cr = 0.05
Hence Safe against cracking
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
IPS OUTLET CHAMBER
DESIGN OF UPPER PLATFORM SLAB PS2
Additional moment due to point load = 3.375 kN-m (Equipment load - 5 kN)
Additional moment due to point load = 2.295 kN-m (Parapet load - 1.7 kN/m)
Maximum Bending Moment at support = M + Wd*l^2/2 + Wl*l^2/2
= 14.213 KN-m (4.375*1.35^2/2+5*1.35^2/2)+2.295)
Mu/bd2 = 1.088
Maximum Bending moment causing tension in the sewage / soilface = 14.213 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.35 mm
2
fs = M/Ast1(d-x/3) = 145.37 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000998
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000153
The average surface strain em
em (e1-e2) = 0.000845
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 56.03
Cmin = 30
The design crack width W cr = 0.10
Hence Safe against cracking
Contractor: Client: CMSC:
Structural Data:
Ast Required =
2
Ast Required for Moment = 170 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
(((3.5625*10^6)/66.95)/392.7)
2
Concrete stress 'fc' = 4.41 N/mm
(2*3.5625*10^6)/(1000*24.148*66.95)
Distance 'a' = 125 mm
Strain Es in steel for the stress of = 0.00067750 mm
(135.5/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0013436 mm
(((125-24.148)/(75-24.148))*0.0006775)
Strain due to stiffening effect of concrete ε2
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
0.500
FGL
Assuming
Water table at
H 1.500 FGL
Tank
a/b = 0.375
Moody's chart - Max. horizontal moment coeff. for P1 & P2 = 0.021
Fig 4 Max. vertical moment coeff. for P1 & P2 = 0.020
Horizontal Moment due to water + sub soil 0.0208 x 22.36 x 2^2 = 1.86 kNm
Vertical Moment due to water + sub soil 0.02 x 22.36 x 2^2 = 1.79 kNm
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
2.86 4.29 200 1000 33 145 350 393 0.270 10 200 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.80 9.33 45 0 29.15 6E+07 53.79 0.000 SAFE - Wcr<0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
2.81 4.22 200 1000 33 135 350 393 0.290 10 200 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.80 9.33 45 0 28.01 5E+07 56.9 0.000 SAFE - Wcr<0.2
Provide Y10 at 200 mm c/c upto FGL and provide Y10 at 200 mm c/c above ground level as
vertical reinforcement.
Provide Y10 at 200 mm c/c as horizontal reinforcement and Y10 at 200 mm c/c above FGL.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
0.500
FGL
Assuming
Water table at
H 1.500 FGL
Tank
a/b = 0.750
Moody's chart - Max. horizontal moment coeff. for P1 & P2 = 0.043
Fig 4 Max. vertical moment coeff. for P1 & P2 = 0.058
Horizontal Moment due to water + sub soil 0.0433 x 22.36 x 2^2 = 3.87 kNm
Vertical Moment due to water + sub soil 0.0584 x 22.36 x 2^2 = 5.22 kNm
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
7.64 11.46 200 1000 54 145 350 393 0.270 10 200 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.80 9.33 45.001 0 29.15 6E+07 143.7 0.000 SAFE - Wcr<0.2
Reinforcement Details:
Design - LSM M Mu D b dreq dpro Ast,req Ast,pro pt pro f s
IS: 456 kNm/m kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro > Astreq
7.45 11.18 200 1000 53 135 350 393 0.290 10 200 SAFE
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.80 9.33 45.001 0 28.01 5E+07 150.85 4E-05 0.000 SAFE - Wcr<0.2
Provide Y10 at 200 mm c/c upto FGL and provide Y10 at 200 mm c/c above ground level as
vertical reinforcement.
Provide Y10 at 200 mm c/c as horizontal reinforcement and Y10 at 200 mm c/c above FGL.
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Tank
11.68 kN/m2
Height of water table from FGL at bottom of slab 1.5 + 0.2 = 1.700 m
2
Uplift pressure at the bottom of base slab 1.7 x 9.81 = 16.68 kN/m
2
Self wt of base slab 0.2 x 25 = 5.000 kN/m
2
Net Uplift pressure at the bottom of base slab 16.68 - 5 = 11.68 kN/m
a/b = 0.50
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.8 9.33 55 393 32.48 6E+07 99.443 0.000 SAFE - Wcr<0.2
3
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Crack Width:
IS 3370 - II Annex Cmin acr m=280/ Asc,pro X Icr fst W cr
d' em
B mm mm 3scbc mm2 mm mm4 N/mm2 mm
50 111.8 9.33 55 393 32.48 6E+07 37.661 0.000 SAFE - Wcr<0.2
Minimum Reinforcement:
ptreq ptpro f s
% % mm mm
0.12 0.20 10 200
Top reinforcement:
Provide Y10 at 200 mm c/c along x axis and Y10 at 200 mm c/c along y axis as top reinforcement.
Bottom reinforcement:
Provide Y10 at 200 mm c/c along x axis and Y10 at 200 mm c/c along y axis as bottom
reinforcement.
4
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
W8
W7 0.00 MWL
W2 W1
3.50
W 2a
H
W5 q1
W9 W3 Soil pressure
1.1 W6 considered
2.20
conservatively
Heel W4 Toe
q2 q3
1.425 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.77 m
27.3 77.44
20.71
32.45
6.6 158.10 27.50 80.66
Net Soil Pressure acting on Base Slab
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Moment, M1
32.45 x 0.5 x 0.5 x 0.5 x 1/3 = 1.35 kNm
Shear force @ rear face of stem, V1
(0.5 x 32.45 x 0.5) = 8.11 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
2.03 300 1000 23 245 19 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 22.257 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
27.5x(0.925-0.425)^2/2 + (80.66-27.5)x0.5x(0.925-0.425)^2x2/3 = 7.87 kNm
Shear force @ rear face of stem, V2
(27.5 + 80.66) / 2 x (0.925 - 0.425) = 27.04 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
11.80 300 1000 54 245 112 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 129.51 0.0016 0.1587 38.87 0.00 SAFE - Wcr<0.2
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
114.60 425 1000 169 374 744 1131 0.302 12 100 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 67.3 1E+09 291.44 0.003 0.211 78.93 0.0011 0.194 SAFE - Wcr<0.2
46
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
14.36 320 1000 60 269 560 565 0.210 12 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 109.7 3E+08 100.44 0.0021 0.1794 48.27 0.000 SAFE - Wcr<0.2
47
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
MWL
W2
W1 3.50
W 2b W 2a
W 5b W 5a q1
W3
W 6b W 6a
2.20
Heel W4 Toe
q2 q3
1.425 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Force (kN) Distance from Heel (m) Moment (kNm)
W 1 - 9.81 x 0.5 x 3.5 - 17.17 1.175 20.17
W 2 - 25 x 0.25 x 3.5 - 21.88 0.713 15.60
W 2a - 25 x 0.5 x 0.0875 x 3.5 - 3.83 0.867 3.32
W 2b - 25 x 0.5 x 0.0875 x 3.5 - 3.83 0.529 2.03
W 3 - 25 x 0.425 x 1.9 - 20.19 0.713 14.40
W 4 - 25 x 1.425 x 0.3 - 10.69 0.713 7.62
W 5a - 25 x 0.5 x 0.2 - 2.5 1.175 2.94
W 5b - 25 x 0.5 x 0.2 - 2.5 0.250 0.63
W 6a - 18 x 0.5 x 1.7 - 15.3 1.175 17.98
W 6b - 18 x 0.5 x 1.7 - 15.3 0.250 3.83
W 7 - 25 x 1 x 0 - 0 1.250 0.00
W8 - 0 x 1 - 0 1.250 0.00
W - 113.19 Mw - 88.52
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.78 m
53.43
-10.33 9.56
28.76 91.75
169.2 Net Soil Pressure acting on Base Slab
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Moment, M1
0.5 x 0.5 x 53.43 x (2/3) x 0.5 = 4.45 kNm Conservatively
Shear force @ distance d from the face of stem, V1
0.5 x 0.5 x 53.43 = 13.36 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
6.68 300 1000 41 245 63 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 73.294 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
28.76x(0.925-0.425)^2/2 + (91.75-28.76)x0.5x(0.925-0.425)^2x2/3 = 8.84 kNm
Shear force @ rear face of stem, V2
(28.76 + 91.75) / 2 x (0.925 - 0.425) = 30.13 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
13.27 300 1000 58 245 126 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 145.59 0.0016 0.1587 38.87 0.00 SAFE - Wcr<0.2
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
For reinforcement details on both the faces of Wall 6, follow the same
reinforcement details adopted in the water face of Wall W5.
46
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF WALKWAY SLAB (Platform Slab around external wall) PS2
Mu/bd2 = 0.828
For M30 and Fe500, percentage of reinforcement,
pt = 0.5*Fck/Fy*(1-sqrt (1-(Mu/bd2)*4.589/Fck)* 100
= 0.197 %
Ast = Pt/100*b*d
= 226.55 mm2 0.197/100*1000*115
Assumed diameter of the slab reinft = 10 mm
Minimum % of reinforcement = 0.35 %
Depth of surface zone = 150
Minimum area of reinforcement = 525 mm2
Spacing of 10mm dia bars = 149.60 mm Af/Ast.*1000
Spacing of bars provided = 125 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 7.300 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 37.67 mm
2
fs = M/Ast1(d-x/3) = 113.47 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000824
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000202
The average surface strain em
em (e1-e2) = 0.000622
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 66.63
Cmin = 30
The design crack width W cr = 0.08
Hence Safe against cracking
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF LAUNDER WALL: Wall - W12
Properties of material
fck = 30 N/mm2
fy = 500 N/mm2
Dimensions
Thickness of Wall D = 200 mm
Clear cover to rebar C = 45 mm
Dia of main rebar = 10 mm
Eff. Thickness of Wall d = 150 mm
(200-45-10/2)
Height of Liquid /wall = 1500 mm (406.1-405.1+0.5)x1000
3
Unit weight of liquid = 9.81 kN/m
Maximum Bending moment causing tension in the sewage / soilface = 5.52 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 35.13 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete scada
EPE/196MLD/DC/STR/DC, FM,
system for the entire project on design build, operate and 01.02.2020
FL&IPS - 112A
transfer basis for new water supply scheme in tiruppur city
municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
2
fs = M/Ast1(d-x/3) = 101.65 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000729
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000457
The average surface strain em
em (e1-e2) = 0.000272
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 106.8
Cmin = 45
The design crack width W cr = 0.05
Hence Safe against cracking
Title: Design Calculation for PTU at 196 MLD - WTP SVK JTP MGK 0
Mu/bd2 = 0.299
For M30 and Fe500, percentage of reinforcement,
pt = 0.5*Fck/Fy*(1-sqrt (1-(Mu/bd2)*4.589/Fck)* 100
= 0.070 %
Ast = Pt/100*b*d
Title: Design Calculation for PTU at 196 MLD - WTP SVK JTP MGK 0
2
Ast provided = 392.5 mm Safe
Provide Y10 at 200mm c/c as main reinforcement at liquid face and Y10 at 200mm c/c as distribution reinforcement.
Provide Y10 at 200mm c/c as bottom reinforcement at both faces.
Title: Design Calculation for PTU at 196 MLD - WTP SVK JTP MGK 0
Maximum Bending moment causing tension in the sewage / soilface = 4.492 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 35.95 mm
2
fs = M/Ast1(d-x/3) = 82.92 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000596
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000458
The average surface strain em
em (e1-e2) = 0.000138
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 106.8
Cmin = 45
The design crack width W cr = 0.03
Hence Safe against cracking
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
W8 W9 W 10 0.00
MWL
W7
W2 W1
3.50
H
W 2a
W5 q1
W3 Soil pressure
1.1 W8 W6 considered
2.20
conservatively
Heel W4 Toe
q2 q3
1.20 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Stability against Overturning:
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.68 m
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Pressure Diagram: (kN/m2)
27.30 77.44
45.71
#### 46.33
202.49 51.42 125.05
Moment, M1
45.71 x 0.5^2 /2 + (46.33 - 45.71) x 0.5 x 0.5^2 x 1/3 = 5.74 kNm
Shear force @ distance d from the face of stem, V1
(45.71 + 46.33) / 2 x (0.5 - 0.245) = 11.74 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
8.61 300 1000 46 245 81 393 0.160 10 200 SAFE
Moment, M2
51.42 x (0.7-0.3)^2 /2 + (125.05-51.42) x 0.5 x (0.7-0.3)^2 x 2/3 = 8.04 kNm
Shear force @ rear face of stem, V2
(51.42 + 125.05) / 2 x (0.7 - 0.3) = 35.29 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
12.06 300 1000 55 245 114 393 0.160 10 200 SAFE
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt New Tiruppur
Tiruppur City Municipal
Ltd., Plot No:943,54th street, TVS Area Development
Corporation, Tiruppur.
Colony, Anna Nagar West Ext, Corpo. Ltd
Name of the Project: Construction of water treatment plant DOCUMENT NO. DATE
of capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM, FL&IPS
scada system for the entire project on design build, 01.02.2020
- 112A
operate and transfer basis for new water supply scheme in
tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution
Chamber, Flash Mixer, Flocculator and Inclined Plate SVK JTP MGK 0
Settler
Structural Data:
STAAD Results:
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt New Tiruppur
Tiruppur City Municipal
Ltd., Plot No:943,54th street, TVS Area Development
Corporation, Tiruppur.
Colony, Anna Nagar West Ext, Corpo. Ltd
Name of the Project: Construction of water treatment plant DOCUMENT NO. DATE
of capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM, FL&IPS
scada system for the entire project on design build, 01.02.2020
- 112A
operate and transfer basis for new water supply scheme in
tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution
Chamber, Flash Mixer, Flocculator and Inclined Plate SVK JTP MGK 0
Settler
Service Moment @ bottom of wall = 35 kN-m
Shear stress @ bottom of wall = 0.19 N/mm
2
Ast Required =
2
Ast Required for Moment = 491 mm
2
Ast Provided = 754 mm
(1000/150*0.7854*12*12) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck) = 27386.1279 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt New Tiruppur
Tiruppur City Municipal
Ltd., Plot No:943,54th street, TVS Area Development
Corporation, Tiruppur.
Colony, Anna Nagar West Ext, Corpo. Ltd
Name of the Project: Construction of water treatment plant DOCUMENT NO. DATE
of capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM, FL&IPS
scada system for the entire project on design build, 01.02.2020
- 112A
operate and transfer basis for new water supply scheme in
tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution
Chamber, Flash Mixer, Flocculator and Inclined Plate SVK JTP MGK 0
Settler
Modulur Ratio, m, Es/Ec = 14.6
(((35*10^6)/232.47)/753.98)
2
Concrete stress 'fc' = 4.66 N/mm
(2*35*10^6)/(1000*64.578*232.47)
Distance 'a' = 300 mm
Strain Es in steel for the stress of = 0.00099840 mm
(199.68/200000)
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt New Tiruppur
Tiruppur City Municipal
Ltd., Plot No:943,54th street, TVS Area Development
Corporation, Tiruppur.
Colony, Anna Nagar West Ext, Corpo. Ltd
Name of the Project: Construction of water treatment plant DOCUMENT NO. DATE
of capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM, FL&IPS
scada system for the entire project on design build, 01.02.2020
- 112A
operate and transfer basis for new water supply scheme in
tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution
Chamber, Flash Mixer, Flocculator and Inclined Plate SVK JTP MGK 0
Settler
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0012409 mm
(((300-64.578)/(254-64.578))*0.0009984)
Strain due to stiffening effect of concrete ε2
Ast Required =
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt New Tiruppur
Tiruppur City Municipal
Ltd., Plot No:943,54th street, TVS Area Development
Corporation, Tiruppur.
Colony, Anna Nagar West Ext, Corpo. Ltd
Name of the Project: Construction of water treatment plant DOCUMENT NO. DATE
of capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM, FL&IPS
scada system for the entire project on design build, 01.02.2020
- 112A
operate and transfer basis for new water supply scheme in
tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution
Chamber, Flash Mixer, Flocculator and Inclined Plate SVK JTP MGK 0
Settler
2
Ast Required for Moment = 623 mm
2
Ast Provided = 754 mm
(1000/150*0.7854*12*12) +(1000/200*0.7854*0*0)
Hence Provided Ast is ok
Check for Crack width
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck) = 27386.1279 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
(((44*10^6)/232.47)/753.98)
2
Concrete stress 'fc' = 5.86 N/mm
(2*44*10^6)/(1000*64.578*232.47)
Distance 'a' = 300 mm
Strain Es in steel for the stress of = 0.00125515 mm
(251.03/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0015600 mm
(((300-64.578)/(254-64.578))*0.00125515)
Strain due to stiffening effect of concrete ε2
Crack Width
2
Maximum actual base pressure below base slab = 39.34 kN/m SAFE
(SBC after compaction is considered to be 50 kN/Sqm on the conservative side)
LOAD CALCULATIONS
Outlet channel:
Seismic load
Seismic zone = III
Zone factor = 0.16
Category = III
Importance factor = 1.25
Response reduction factor = 3
Type of soil (SS - Medium soil) = 2
Type of Structure (ST - RCC frame) = 1
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF WALKWAY SLAB (Platform Slab around external wall) PS1
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 35.39 mm
2
fs = M/Ast1(d-x/3) = 82.47 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.000677
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000183
The average surface strain em
em (e1-e2) = 0.000494
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 56.03
Cmin = 30
The design crack width W cr = 0.05
Hence Safe against cracking
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
DESIGN OF OUTER WALL FOR OUTLET CHANNEL: (Along the length) Wall - W15
Properties of material
fck = 30 N/mm2
fy = 500 N/mm2
Dimensions
Thickness of Wall D = 200 mm
Clear cover to rebar C = 45 mm
Dia of main rebar = 10 mm
Eff. Thickness of Wall d = 150 mm
(200-45-10/2)
Height of Liquid /wall = 2000 mm (405.1-403.6+0.5)x1000
Unit weight of liquid = 9.81 kN/m3
Maximum Bending moment causing tension in the sewage / soilface = 18.14 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 46.06 mm
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
2
fs = M/Ast1(d-x/3) = 171.53 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.00127
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000236
The average surface strain em
em (e1-e2) = 0.001034
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 65.71
Cmin = 45
The design crack width W cr = 0.16
Hence Safe against cracking
Bottom moment of base slab (Due to self weight of base slab &Liquid):
Unfactored moment = 14.23 kNm (Tension @ bottom)
Load factor = 1.5
Mu = 21.3 kNm
Percentage of steel required = 0.227 %
Area of steel reqd @ bottom = 341 mm2 (0.227x1000x150/100)
Depth of Surface Zone = 100 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 14.23 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 39.77 mm
2
fs = M/Ast1(d-x/3) = 198.69 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001444
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000347
The average surface strain em
em (e1-e2) = 0.001097
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 85.14
Cmin = 45
The design crack width W cr = 0.19
Hence Safe against cracking
Bottom moment of base slab (Fixed end moment of inlet channel wall):
Unfactored moment = 18.14 kNm (Tension @ Top)
Load factor = 1.5
Mu 27.2 kNm
Percentage of steel required = 0.290 %
Area of steel reqd @ Top = 435 mm2 (0.29x1000x150/100)
Depth of Surface Zone = 100.0 mm As per IS 3370 - Part 2
Min. percentage of steel = 0.35 %
Area of steel reqd @ Top = 350 mm2
Spacing of reinft. Reqd. = 181 mm
Spacing of reinft. Provided = 150 mm
Area of steel provided @ Top = 524 mm2 Safe
(1000/150x0.7854x10^2)
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
Maximum Bending moment causing tension in the sewage / soilface = 18.14 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 44.37 mm
2
fs = M/Ast1(d-x/3) = 230.64 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.001488
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000216
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corpo. Ltd
Chennai
(NTADCL)
Name of the Project: Construction of water treatment plant of DOCUMENT NO. DATE
capacity 196 MLD expandable to 270 MLD with complete
EPE/196MLD/DC/STR/DC, FM,
scada system for the entire project on design build, operate 01.02.2020
FL&IPS - 112A
and transfer basis for new water supply scheme in tiruppur
city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber,
SVK JTP MGK 0
Flash Mixer, Flocculator and Inclined Plate Settler
fck = 30 N/mm2
fy = 500 N/mm2
Cover = 50 mm
Depth of excavation = 0.80 m from FGL
Depth of excavation = 0.75 m from FGL
gsoil = 18 kN/m3
gcon = 25 kN/m3
Net SBC = 170 kN/m2
Width assumed = 1.00 m
d/2 d
d/2
Column moment, My
Column moment, Mz
Bc Lc
Z L
Support Moment, Mz X
Support Moment, Mx
L/C Fx Fz Fy Mx Mz Lc Bc L B Fy/A Mx/Z Mz/Z qmax,g qmin,g qgross,m qnet,m qmax,n qmin,n Wf Ws q1 q2 q3 q4 h y Mu,x Mux,lim dx ptx,cal pt,pro f1 s1 x Mu,z Muz,lim dy pty,cal pt,pro f2 s2 V b tc,1 tc,max tv,1 V b tc,1 tc,max tv,1 bc ks tc,2 tv,2 qb,net kN/m2
kN kN kN kNm kNm mm mm m m kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2 kN kN kN/m2 kN/m2 kN/m2 kN/m2 mm m kNm kNm mm % % mm mm m kNm kNm mm % % mm mm kN N/mm2 N/mm2 N/mm2 kN N/mm2 N/mm2 N/mm2 N/mm2 N/mm2 170
2 101 3.6 0 175 0 -4 300 300 1.40 1.40 106 0.00 8.15 114 98 184 170 97 81 22 12 114 98 98 114 450 0.55 22 625 395 0.03 0.10 10 200 0.55 22 594 385 0.03 0.10 10 200 23 35 0.24 3.45 0.06 24 34 0.25 3.45 0.06 1.00 1.50 1.37 0.24 SAFE
102 5.8 0 152 0 12 300 300 1.40 1.40 95 0.00 25.38 120 69 226 213 103 52 22 12 120 69 69 120 450 0.55 23 625 395 0.03 0.10 10 200 0.55 23 594 385 0.04 0.10 10 200 24 35 0.24 3.45 0.06 25 34 0.25 3.45 0.07 1.00 1.50 1.37 0.26 SAFE
103 3.2 8.73 156 -29 -4 300 300 1.40 1.40 97 62.01 7.23 166 27 226 213 149 10 22 12 166 151 27 42 450 0.55 34 625 395 0.05 0.10 10 200 0.55 34 594 385 0.05 0.10 10 200 35 35 0.24 3.45 0.09 37 34 0.25 3.45 0.10 1.00 1.50 1.37 0.37 SAFE
104 12 0 160 0 -19 300 300 1.40 1.40 99 0.00 39.83 139 59 226 213 121 42 22 12 139 59 59 139 450 0.55 28 625 395 0.04 0.10 10 200 0.55 28 594 385 0.04 0.10 10 200 28 35 0.24 3.45 0.07 30 34 0.25 3.45 0.08 1.00 1.50 1.37 0.31 SAFE
105 3.2 8.73 156 29 -4 300 300 1.40 1.40 97 62.01 7.23 166 27 226 213 149 10 22 12 166 151 27 42 450 0.55 34 625 395 0.05 0.10 10 200 0.55 34 594 385 0.05 0.10 10 200 35 35 0.24 3.45 0.09 37 34 0.25 3.45 0.10 1.00 1.50 1.37 0.37 SAFE
106 5.4 0 171 0 12 300 300 1.40 1.40 104 0.00 24.46 129 80 226 213 111 62 22 12 129 80 80 129 450 0.55 25 625 395 0.04 0.10 10 200 0.55 25 594 385 0.04 0.10 10 200 26 35 0.24 3.45 0.07 28 34 0.25 3.45 0.07 1.00 1.50 1.37 0.28 SAFE
107 3.6 8.73 175 -29 -4 300 300 1.40 1.40 106 62.01 8.15 176 36 226 213 159 19 22 12 176 160 36 52 450 0.55 36 625 395 0.05 0.10 10 200 0.55 36 594 385 0.06 0.10 10 200 37 35 0.24 3.45 0.09 39 34 0.25 3.45 0.10 1.00 1.50 1.37 0.40 SAFE
108 13 0 179 0 -19 300 300 1.40 1.40 109 0.00 40.75 149 68 226 213 132 51 22 12 149 68 68 149 450 0.55 30 625 395 0.04 0.10 10 200 0.55 30 594 385 0.05 0.10 10 200 31 35 0.24 3.45 0.08 33 34 0.25 3.45 0.08 1.00 1.50 1.37 0.33 SAFE
109 3.6 8.73 175 29 -4 300 300 1.40 1.40 106 62.01 8.15 176 36 226 213 159 19 22 12 176 160 36 52 450 0.55 36 625 395 0.05 0.10 10 200 0.55 36 594 385 0.06 0.10 10 200 37 35 0.24 3.45 0.09 39 34 0.25 3.45 0.10 1.00 1.50 1.37 0.40 SAFE
6 101 0 0 250 0 0 300 300 1.50 1.50 128 0.00 0.00 128 128 184 170 111 111 25 14 128 128 128 128 450 0.60 30 625 395 0.04 0.10 10 200 0.60 30 594 385 0.05 0.10 10 200 34 35 0.24 3.45 0.09 36 34 0.25 3.45 0.09 1.00 1.50 1.37 0.28 SAFE
102 10 0 222 0 17 300 300 1.50 1.50 116 0.00 28.46 144 87 226 213 127 70 25 14 144 87 87 144 450 0.60 34 625 395 0.05 0.10 10 200 0.60 34 594 385 0.05 0.10 10 200 39 35 0.24 3.45 0.10 41 34 0.25 3.45 0.11 1.00 1.50 1.37 0.32 SAFE
103 0 10.7 222 -33 0 300 300 1.50 1.50 116 57.10 0.00 173 59 226 213 156 42 25 14 173 173 59 59 450 0.60 42 625 395 0.06 0.10 10 200 0.60 42 594 385 0.07 0.10 10 200 48 35 0.24 3.45 0.12 50 34 0.25 3.45 0.13 1.00 1.50 1.37 0.40 SAFE
104 10 0 222 0 -17 300 300 1.50 1.50 116 0.00 28.46 144 87 226 213 127 70 25 14 144 87 87 144 450 0.60 34 625 395 0.05 0.10 10 200 0.60 34 594 385 0.05 0.10 10 200 39 35 0.24 3.45 0.10 41 34 0.25 3.45 0.11 1.00 1.50 1.37 0.32 SAFE
105 0 10.7 222 33 0 300 300 1.50 1.50 116 57.10 0.00 173 59 226 213 156 42 25 14 173 173 59 59 450 0.60 42 625 395 0.06 0.10 10 200 0.60 42 594 385 0.07 0.10 10 200 48 35 0.24 3.45 0.12 50 34 0.25 3.45 0.13 1.00 1.50 1.37 0.40 SAFE
106 10 0 250 0 17 300 300 1.50 1.50 128 0.00 28.46 157 100 226 213 139 82 25 14 157 100 100 157 450 0.60 38 625 395 0.06 0.10 10 200 0.60 38 594 385 0.06 0.10 10 200 43 35 0.24 3.45 0.11 45 34 0.25 3.45 0.12 1.00 1.50 1.37 0.35 SAFE
107 0 10.7 250 -33 0 300 300 1.50 1.50 128 57.10 0.00 185 71 226 213 168 54 25 14 185 185 71 71 450 0.60 45 625 395 0.07 0.10 10 200 0.60 45 594 385 0.07 0.10 10 200 52 35 0.24 3.45 0.13 54 34 0.25 3.45 0.14 1.00 1.50 1.37 0.43 SAFE
108 10 0 250 0 -17 300 300 1.50 1.50 128 0.00 28.46 157 100 226 213 139 82 25 14 157 100 100 157 450 0.60 38 625 395 0.06 0.10 10 200 0.60 38 594 385 0.06 0.10 10 200 43 35 0.24 3.45 0.11 45 34 0.25 3.45 0.12 1.00 1.50 1.37 0.35 SAFE
109 0 10.7 250 33 0 300 300 1.50 1.50 128 57.10 0.00 185 71 226 213 168 54 25 14 185 185 71 71 450 0.60 45 625 395 0.07 0.10 10 200 0.60 45 594 385 0.07 0.10 10 200 52 35 0.24 3.45 0.13 54 34 0.25 3.45 0.14 1.00 1.50 1.37 0.43 SAFE
10 101 3.6 0 175 0 4 300 300 1.40 1.40 106 0.00 8.15 114 98 184 170 97 81 22 12 114 98 98 114 450 0.55 22 625 395 0.03 0.10 10 200 0.55 22 594 385 0.03 0.10 10 200 23 35 0.24 3.45 0.06 24 34 0.25 3.45 0.06 1.00 1.50 1.37 0.24 SAFE
102 12 0 160 0 19 300 300 1.40 1.40 99 0.00 39.83 139 59 226 213 121 42 22 12 139 59 59 139 450 0.55 28 625 395 0.04 0.10 10 200 0.55 28 594 385 0.04 0.10 10 200 28 35 0.24 3.45 0.07 30 34 0.25 3.45 0.08 1.00 1.50 1.37 0.31 SAFE
103 3.2 8.73 156 -29 4 300 300 1.40 1.40 97 62.01 7.23 166 27 226 213 149 10 22 12 166 151 27 42 450 0.55 34 625 395 0.05 0.10 10 200 0.55 34 594 385 0.05 0.10 10 200 35 35 0.24 3.45 0.09 37 34 0.25 3.45 0.10 1.00 1.50 1.37 0.37 SAFE
104 5.8 0 152 0 -12 300 300 1.40 1.40 95 0.00 25.38 120 69 226 213 103 52 22 12 120 69 69 120 450 0.55 23 625 395 0.03 0.10 10 200 0.55 23 594 385 0.04 0.10 10 200 24 35 0.24 3.45 0.06 25 34 0.25 3.45 0.07 1.00 1.50 1.37 0.26 SAFE
105 3.2 8.73 156 29 4 300 300 1.40 1.40 97 62.01 7.23 166 27 226 213 149 10 22 12 166 151 27 42 450 0.55 34 625 395 0.05 0.10 10 200 0.55 34 594 385 0.05 0.10 10 200 35 35 0.24 3.45 0.09 37 34 0.25 3.45 0.10 1.00 1.50 1.37 0.37 SAFE
106 13 0 179 0 19 300 300 1.40 1.40 109 0.00 40.75 149 68 226 213 132 51 22 12 149 68 68 149 450 0.55 30 625 395 0.04 0.10 10 200 0.55 30 594 385 0.05 0.10 10 200 31 35 0.24 3.45 0.08 33 34 0.25 3.45 0.08 1.00 1.50 1.37 0.33 SAFE
107 3.6 8.73 175 -29 4 300 300 1.40 1.40 106 62.01 8.15 176 36 226 213 159 19 22 12 176 160 36 52 450 0.55 36 625 395 0.05 0.10 10 200 0.55 36 594 385 0.06 0.10 10 200 37 35 0.24 3.45 0.09 39 34 0.25 3.45 0.10 1.00 1.50 1.37 0.40 SAFE
108 5.4 0 171 0 -12 300 300 1.40 1.40 104 0.00 24.46 129 80 226 213 111 62 22 12 129 80 80 129 450 0.55 25 625 395 0.04 0.10 10 200 0.55 25 594 385 0.04 0.10 10 200 26 35 0.24 3.45 0.07 28 34 0.25 3.45 0.07 1.00 1.50 1.37 0.28 SAFE
109 3.6 8.73 175 29 4 300 300 1.40 1.40 106 62.01 8.15 176 36 226 213 159 19 22 12 176 160 36 52 450 0.55 36 625 395 0.05 0.10 10 200 0.55 36 594 385 0.06 0.10 10 200 37 35 0.24 3.45 0.09 39 34 0.25 3.45 0.10 1.00 1.50 1.37 0.40 SAFE
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt Ltd., Plot No:943,54th Tiruppur City Municipal Corporation, New Tiruppur Area Development
street, TVS Colony, Anna Nagar West Ext, Chennai Tiruppur. Corporation Ltd (NTADCL), Tiruppur.
2 C7 8 300 300 1035.21 1.15 4 20 1257 1.40 0.82 SAFE 8 300 8 175 SAFE
3 C7 14 300 300 823.85 0.92 4 20 1257 1.40 0.66 SAFE 8 190 8 175 SAFE
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
1 B7 69 x mid 279.99 0.16 3 20 942 0.52 0.30 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
600 end 325.27 0.18 3 20 942 0.52 0.35 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
300 Start 425.58 0.24 3 20 942 0.52 0.45 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
5000
2 B7 6 x mid 0.00 0.00 3 20 942 0.52 0.00 SAFE 368.22 0.205 3 16 603 0.34 0.61 SAFE 2 8í 170 2 8 150
600 end 739.43 0.41 3 20 942 0.52 0.78 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
300 Start 739.43 0.41 3 20 942 0.52 0.78 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
5000
3 B7 12 x mid 0.00 0.00 3 20 942 0.52 0.00 SAFE 368.22 0.205 3 16 603 0.34 0.61 SAFE 2 8í 170 2 8 150
600 end 425.58 0.24 3 20 942 0.52 0.45 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
300 Start 325.27 0.18 3 20 942 0.52 0.35 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
1500
4 B7 68 x mid 279.99 0.16 3 20 942 0.52 0.30 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
600 end 0.00 0.00 3 20 942 0.52 0.00 SAFE 0.00 0.000 3 16 603 0.34 0.00 SAFE 2 8í 300 2 8 150
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943, 54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corporation Ltd
Chennai
(NTADCL),
Tiruppur.
Name of the Project: Construction of water treatment plant of capacity DOCUMENT NO. DATE
196 MLD expandable to 270 MLD with complete scada system for the EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
entire project on design build, operate and transfer basis for new water 112A
supply scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash
JMK SVK / JTP 0
Mixer, Flocculator and Inclined Plate Settler
Proflex system roofing or equivalent is provided above the IPS tank. For load data the same is
modelled in STAAD Pro and reactions at supports are taken and applied as UDL on tie beams.
Dead Load:
Live Load:
Live load acting on curved roof as per IS 875 - Part 2 (Table 2) = 0.40 kN/sqm
Live load per meter run = 0.40 kN/m
The support reactions are applied as per meter run on the RCC supporting structure.
Contractor: Client: CMSC:
New Tiruppur
M/s.Eco Protection Engineers Pvt
Area
Ltd., Plot No:943, 54th street, TVS Tiruppur City Municipal
Development
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Corporation Ltd
Chennai
(NTADCL),
Tiruppur.
Name of the Project: Construction of water treatment plant of capacity DOCUMENT NO. DATE
196 MLD expandable to 270 MLD with complete scada system for the EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
entire project on design build, operate and transfer basis for new water 112A
supply scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash
JMK SVK / JTP 0
Mixer, Flocculator and Inclined Plate Settler
Seismic load
M/s.Eco Protection Engineers Pvt Ltd., Plot No:943,54th Tiruppur City Municipal Corporation, New Tiruppur Area Development
street, TVS Colony, Anna Nagar West Ext, Chennai Tiruppur. Corporation Ltd (NTADCL), Tiruppur.
2 C8 2 300 450 3342.68 2.48 12 20 3770 2.79 0.89 SAFE 8 300 8 190 SAFE
3 C8 3 300 450 3661.53 2.71 12 20 3770 2.79 0.97 SAFE 8 300 8 190 SAFE
4 C8 9 300 450 3625.26 2.69 12 20 3770 2.79 0.96 SAFE 8 300 8 190 SAFE
5 C8 4 300 450 2023.84 1.50 12 20 3770 2.79 0.54 SAFE 8 190 8 190 SAFE
Contractor: Client: CMSC:
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer, Flocculator and Inclined Plate Settler SVK JTP MGK 0
1 B8 5 x mid 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
450 end 219.66 0.16 3 20 942 0.70 0.23 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
300 Start 254.39 0.19 3 20 942 0.70 0.27 SAFE 254.39 0.188 3 20 942 0.70 0.27 SAFE 2 8d 160 2 10 100
3600
2 B8 8 x mid 254.39 0.19 3 20 942 0.70 0.27 SAFE 254.39 0.188 3 20 942 0.70 0.27 SAFE 2 8d 160 2 10 100
450 end 254.39 0.19 3 20 942 0.70 0.27 SAFE 254.39 0.188 3 20 942 0.70 0.27 SAFE 2 8d 160 2 10 100
300 Start 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
3600
3 B8 6 x mid 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
450 end 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
300 Start 215.68 0.16 3 20 942 0.70 0.23 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
3500
4 B8 7 x mid 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
450 end 211.14 0.16 3 20 942 0.70 0.22 SAFE 211.14 0.156 3 20 942 0.70 0.22 SAFE 2 8d 160 2 10 100
Contractor: Client: CMSC:
Structural Data:
Ast Required =
2
Ast Required for Moment = 3 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
Check for Crack width
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
(((0.128*10^6)/118.9)/392.7)
2
Concrete stress 'fc' = 0.06 N/mm
(2*0.128*10^6)/(1000*33.299*118.9)
Distance 'a' = 180 mm
Strain Es in steel for the stress of = 0.00001370 mm
(2.74/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0000208 mm
(((180-33.299)/(130-33.299))*0.0000137)
Strain due to stiffening effect of concrete ε2
Ast Required =
2
Ast Required for Moment = 5 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/200*0.7854*0*0)
Hence Provided Ast is ok
Contractor: Client: CMSC:
(((0.199*10^6)/118.9)/392.7)
Contractor: Client: CMSC:
(2*0.199*10^6)/(1000*33.299*118.9)
Distance 'a' = 180 mm
Strain Es in steel for the stress of = 0.00002130 mm
(4.26/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0000323 mm
(((180-33.299)/(130-33.299))*0.0000213)
Strain due to stiffening effect of concrete ε2
Crack Width
Structural Data:
Ast Required =
2
Ast Required for Moment = 32 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/150*0.7854*0*0)
Hence Provided Ast is ok
Check for Crack width
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
(((1.382*10^6)/137.96)/392.7)
2
Concrete stress 'fc' = 0.55 N/mm
(2*1.382*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Strain Es in steel for the stress of = 0.00012755 mm
(25.51/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0001836 mm
(((200-36.134)/(150-36.134))*0.00012755)
Strain due to stiffening effect of concrete ε2
Ast Required =
2
Ast Required for Moment = 4 mm
2
Ast Provided = 393 mm
(1000/200*0.7854*10*10) +(1000/200*0.7854*0*0)
Hence Provided Ast is ok
Contractor: Client: CMSC:
2
Characteristic cube strength of concrete, fck = M30 N/mm
Yield Strength of steel, fy = 500 N/mm2
Modulus Elasticity of concrete Ec= 5000xSQRT(fck = 27386.12788 N/mm2
Modulus Elasticity of Steel Es = 200000 N/mm2
Modulur Ratio, m, Es/Ec = 14.6
(((0.159*10^6)/137.96)/392.7)
Contractor: Client: CMSC:
(2*0.159*10^6)/(1000*36.134*137.96)
Distance 'a' = 200 mm
Strain Es in steel for the stress of = 0.00001465 mm
(2.93/200000)
Strain at the level considered ε1 = (h-x)/(d-x)*εs
Strain at the level considered ε1 = 0.0000211 mm
(((200-36.134)/(150-36.134))*0.00001465)
Strain due to stiffening effect of concrete ε2
Crack Width
Maximum Bending moment causing tension in the sewage / soilface = 5.063 kN-m
The depth of neutral axis (x) from the comp face is found bysolving the below equation
(bx2/2)+(1.5m-1)Asc(x-d`)-mAst(d-x) = 0
Modulur ratio m (2Es/Ec) = 14.61
Depth of neutral axis x = 30.23 mm
2
fs = M/Ast1(d-x/3) = 121.05 N/mm
The strain associated with fs
e1 = (h-x)fs/Es(d-x) = 0.00096
e2 = 1.5b(h-x)(a-x)/(3EsAs(d-x)) = 0.000265
The average surface strain em
em (e1-e2) = 0.000695
acr distance from the point considered to the surface of the nearest longitudinal bar,
acr (Sqrt{(s/2)2+(a+Ø/2)2}-Ø/2) = 77.76
Cmin = 30
The design crack width W cr = 0.08
Hence Safe against cracking
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
W8
W7 0.00 MWL
W2 W1
4.00
W 2a
H
W5 q1
W9 W3 Soil pressure
1.1 W6 considered
1.40
conservatively
Heel W4 Toe
q2 q3
1.300 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.68 m
27.3 67.94
28.36
45.01
55.7 98.95 14.36 31.01
Net Soil Pressure acting on Base Slab
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Moment, M1
28.36 x 0.5^2 /2 + (45.01 - 28.36) x 0.5 x 0.5 x 0.5 x 1/3 = 4.24 kNm
Shear force @ distance d from the face of stem, V1
(28.36 + 45.01) / 2 x (0.5 - 0.245) = 9.35 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
6.36 300 1000 40 245 60 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 69.775 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
14.36x(0.8-0.3)^2/2 + (31.01-14.36)x0.5x(0.8-0.3)^2x2/3 = 3.18 kNm
Shear force @ rear face of stem, V2
(14.36 + 31.01) / 2 x (0.8 - 0.3) = 11.34 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
4.77 300 1000 35 245 45 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 52.388 0.0016 0.1587 38.87 0.00 SAFE - Wcr<0.2
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
30.64 300 1000 88 249 525 754.0 0.303 12 150 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 87.5 3E+08 175.55 0.003 0.2112 52.58 0.0004 0.079 SAFE - Wcr<0.2
Horizontal Reinforcement:
ptreq ptpro f s
% % mm mm
0.175 0.175 10 150
46
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
22.45 300 1000 75 249 525 754 0.303 12 150 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 87.5 3E+08 128.61 0.003 0.2112 52.58 0.0001 0.023 SAFE - Wcr<0.2
47
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
W8
W7 0.00 MWL
W2 W1
4.00
W 2a
H
W5 q1
W9 W3 Soil pressure
1.1 W6 considered
1.40
conservatively
Heel W4 Toe
q2 q3
1.300 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.68 m
27.3 67.94
28.36
45.01
55.7 98.95 14.36 31.01
Net Soil Pressure acting on Base Slab
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Moment, M1
28.36 x 0.5^2 /2 + (45.01 - 28.36) x 0.5 x 0.5 x 0.5 x 1/3 = 4.24 kNm
Shear force @ distance d from the face of stem, V1
(28.36 + 45.01) / 2 x (0.5 - 0.245) = 9.35 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
6.36 300 1000 40 245 60 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 69.775 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
14.36x(0.8-0.3)^2/2 + (31.01-14.36)x0.5x(0.8-0.3)^2x2/3 = 3.18 kNm
Shear force @ rear face of stem, V2
(14.36 + 31.01) / 2 x (0.8 - 0.3) = 11.34 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
4.77 300 1000 35 245 45 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 52.388 0.0016 0.1587 38.87 0.00 SAFE - Wcr<0.2
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
30.64 300 1000 88 249 525 754.0 0.303 12 150 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 87.5 3E+08 175.55 0.003 0.2112 52.58 0.0004 0.079 SAFE - Wcr<0.2
Horizontal Reinforcement:
ptreq ptpro f s
% % mm mm
0.175 0.175 10 150
46
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
22.45 300 1000 75 249 525 754 0.303 12 150 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 87.5 3E+08 128.61 0.003 0.2112 52.58 0.0001 0.023 SAFE - Wcr<0.2
47
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
MWL
W2
W1 4.00
W 2b W 2a
W 5b W 5a q1
W3
W 6b W 6a
1.40
Heel W4 Toe
q2 q3
1.300 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Force (kN) Distance from Heel (m) Moment (kNm)
W 1 - 9.81 x 0.5 x 4 - 19.62 1.050 20.60
W 2 - 25 x 0.3 x 4 - 30 0.650 19.50
W 2a - 25 x 0.5 x 0 x 4 - 0 0.800 0.00
W 2b - 25 x 0.5 x 0 x 4 - 0 0.500 0.00
W 3 - 25 x 0.3 x 1.1 - 8.25 0.650 5.36
W 4 - 25 x 1.3 x 0.3 - 9.75 0.650 6.34
W 5a - 25 x 0.5 x 0.2 - 2.5 1.050 2.63
W 5b - 25 x 0.5 x 0.2 - 2.5 0.250 0.63
W 6a - 18 x 0.5 x 0.9 - 8.1 1.050 8.51
W 6b - 18 x 0.5 x 0.9 - 8.1 0.250 2.03
W 7 - 25 x 1 x 0 - 0 1.300 0.00
W8 - 0 x 1 - 0 1.300 0.00
W - 88.82 Mw - 65.60
W
Mo Distance of resultant vertical force from heel
Xw
Xw = Mw / W = 0.74 m
7.52
28.75 47.53
21.18 11.26
115.5 Net Soil Pressure acting on Base Slab
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Moment, M1
0.5 x 0.4 x 28.75 x (1/3) x 0.4 = 0.77 kNm
Shear force from the face of stem, V1
0.5 x 28.75 x 0.4 = 5.75 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
1.15 300 1000 17 245 11 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 12.62 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
11.26x(0.8-0.3)^2/2 + (47.53-11.26)x0.5x(0.8-0.3)^2x2/3 = 4.43 kNm
Shear force @ rear face of stem, V2
(11.26 + 47.53) / 2 x (0.8 - 0.3) = 14.70 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
6.65 300 1000 41 245 63 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 72.923 0.0016 0.1587 38.87 0.00 SAFE - Wcr<0.2
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
32.48 300 1000 90 249 525 754.0 0.303 12 150 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 87.5 3E+08 186.1 0.003 0.2112 52.58 0.0005 0.092 SAFE - Wcr<0.2
Horizontal Reinforcement:
ptreq ptpro f s
% % mm mm
0.175 0.175 10 150
46
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title:Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
Preliminary proportions:
W 11
W 10 MWL
W8 W9 W2
W7 W1 4.00
W 5b
W 5a q1
W3
1.7
W 6b W 6a 0.9
1.40
W4
q2 q3
1.300 Water Soil
43
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title:Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
44
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title:Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
43.1 67.94
6.68
Moment, M1
47.48 x 0.5^2 /2 + (65.8 - 47.48) x 0.5 x 0.5^2 x 2/3 = 7.46 kNm
Shear force @ distance d from the face of stem, V1
(65.8 + 47.48) / 2 x (0.5 - 0.245) = 14.44 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
11.19 300 1000 53 245 106 393 0.160 10 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
50 111.8 2E+08 122.83 0.0016 0.1587 38.87 - 0.000 SAFE - Wcr<0.2
Moment, M2
11.64 x (0.8-0.3)^2 /2 + (6.68-11.64) x 0.5 x (0.8-0.3)^2 x 2/3 = 7.17 kNm
Shear force @ rear face of stem, V2
(11.64 + 6.68) / 2 x (0.8 - 0.3) = 4.58 kN
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
kNm/m mm mm mm mm mm2 mm2 % mm mm Astpro < Astreq
10.75 300 1000 52 245 102 393 0.160 10 200 SAFE
45
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title:Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
ptreq ptpro f s
% % mm mm
0.12 0.13 10 200
Reinforcement Details:
Mu D b dreq dpro Ast,req Ast,pro pt f s
2 2
kNm/m mm mm mm mm mm mm % mm mm Astpro < Astreq
10.62 300 1000 52 249 525 565 0.227 12 200 SAFE
Crack Width:
Cmin acr Icr fst X = kd W cr
r k em
mm mm mm4 N/mm2 mm mm
45 109.7 2E+08 80.413 0.0023 0.1858 46.26 0.00 SAFE - Wcr<0.2
46
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
Ltd (NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire EPE/196MLD/DC/STR/DC, FM, FL&IPS -
01.02.2020
project on design build, operate and transfer basis for new water supply 112A
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title:Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
47
Contractor: Client: CMSC:
M/s.Eco Protection Engineers Pvt
New Tiruppur Area
Ltd., Plot No:943,54th street, TVS Tiruppur City Municipal
Development Corporation Ltd
Colony, Anna Nagar West Ext, Corporation, Tiruppur.
(NTADCL), Tiruppur.
Chennai
Name of the Project: Construction of water treatment plant of capacity 196 DOCUMENT NO. DATE
MLD expandable to 270 MLD with complete scada system for the entire
EPE/196MLD/DC/STR/DC, FM, FL&IPS - 112A 01.02.2020
project on design build, operate and transfer basis for new water supply
scheme in tiruppur city municipal corporation DESIGNED CHECKED APPROVED REV
Title: Structural Design Calculation of Distribution Chamber, Flash Mixer,
SVK JTP MGK 0
Flocculator and Inclined Plate Settler
2
Maximum actual base pressure below base slab = 44.24 kN/m SAFE
(SBC after compaction is considered to be 50 kN/Sqm on the conservative side)
Hence Provided steel is more than the steel required for temperature. Hence Ok.
Contractor: Client : CMSC :
M/s.Eco Protection Engineers Pvt Ltd., Tiruppur City Municipal New Tiruppur Area
Plot No:943,54th street, TVS Colony, Corporation, Tiruppur. Development Corporation
Anna Nagar West Ext, Chennai Ltd (NTADCL), Tiruppur.
1.WEIGHT CALCULATION
mi/m = 0.32
Hence mi = 265420.92 kg
mc/m = 0.67
Hence mc = 555725.05 kg
hi/h = 0.7
Hence hi/h = 0.38 m
hi = 1.52 m
hc/h = 0.53
hc = 2.12
hi*/h = 1.44
hi* = 5.76
hc*/h = 1.69
hc* = 6.76
Contractor: Client : CMSC :
M/s.Eco Protection Engineers Pvt Ltd., Tiruppur City Municipal New Tiruppur Area
Plot No:943,54th street, TVS Colony, Corporation, Tiruppur. Development Corporation
Anna Nagar West Ext, Chennai Ltd (NTADCL), Tiruppur.
Mass of one tank wall is obtained by considering itys inner dimension only,
= 52844.0367 kg
= 1.66 m
2
= 31.6 kN/m
As per section 4.3.1.2 , a strip of unit width of wall is considered as cantilever and subjected
to a concentrated force
P = q*h*1
= 126.4 kN
Length of the cantilever is h' = 1.66 m
Hence d =
2
= 2.50E+07 kN/m
4
= 2.25E-03 m
Contractor: Client : CMSC :
M/s.Eco Protection Engineers Pvt Ltd., Tiruppur City Municipal New Tiruppur Area
Plot No:943,54th street, TVS Colony, Corporation, Tiruppur. Development Corporation
Anna Nagar West Ext, Chennai Ltd (NTADCL), Tiruppur.
= 0m
Multiplying factor of 1.75 is used to obtain sa/g values for 0.5% damping from that
for 5% damping
Contractor: Client : CMSC :
M/s.Eco Protection Engineers Pvt Ltd., Tiruppur City Municipal New Tiruppur Area
Plot No:943,54th street, TVS Colony, Corporation, Tiruppur. Development Corporation
Anna Nagar West Ext, Chennai Ltd (NTADCL), Tiruppur.
5.BASE SHEAR
Mi = 869.58 kN.m
Mc = 231.15 kN.m
Circumferential angle φ = 0
Where Qiw,
= 0.86
Where Qib,
= 0.09
Contractor: Client : CMSC :
M/s.Eco Protection Engineers Pvt Ltd., Tiruppur City Municipal New Tiruppur Area
Plot No:943,54th street, TVS Colony, Corporation, Tiruppur. Development Corporation
Anna Nagar West Ext, Chennai Ltd (NTADCL), Tiruppur.
At base wall, y =0 ;
Where Qcw,
= 0.295
Where Qcb,
= 0.3
Av = 0.03
Pv = 1.18 kN/m2
From the above calculation, maximum hydrodynamic pressure is about 10% of the hydrostatic
pressure. Hence hydrostatic pressure is considered for the design.