ExTR Reference No.

PRD-2019-SU82

TEST REPORT OF
Explosion-proof Power Distribution Equipment

models EGKP-T Series

ErGong Explosion Protection Technology Co., Ltd.

EN 60079-0:2018,
EN 60079-1:2014,
EN60079-7:2015+A1:2018,
EN 60079-31:2014

ANNEX 01 OF
ASSESSMENT REPORT N°PRD-2019-SU82

REVISION 0
ExTR Reference No. PRD-2019-SU82

Ex TEST REPORT COVER

ExTR Free Reference Number……:

Compiled by + signature .............. : Gavin Li

Reviewed by + signature .............. : Konstantin Zhao

Date of issue ................................. : 2019-11-04

Ex Testing Laboratory ................... : Ente Certificazione Macchine

Address ........................................ : Via Cà Bella, 243 - 40050- Italia

Applicant’s name ........................... : ErGong Explosion Protection Technology Co., Ltd.

Address ........................................ : No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province

Standards associated with this EN IEC 60079-0:2018, EN 60079-1:2014, EN60079-7:2015+A1:2018,


ExTR package .............................. : EN 60079-31:2014

Clauses considered ....................... : All clauses considered

Test procedure .............................. : IECEx System

Test Report Form Number ............. : ExTR Cover_4 (released 2010-12)

Test item description ..................... : Explosion-proof Power Distribution Equipment

Model/type reference..................... : EGKP-T Series

Code (e.g. Ex II T ) ............ : II 2G Ex db II B+H2T4/T5/T6 Gb


II 2G Ex eb[ia Ga]or[ib Gb] II B+H2T4/T5/T6 Gb
II 2D Ex tb III C T130°C/T95°C/T80°C Db IP66/IP67
All testing fully performed by Testing (Yes / No, See below for additional details.)
laboratory
Instructions for Intended Use of ExTR Cover:
An ExTR Cover is the sole top-level document to associate together all other parts of an IECEx Test Report
(ExTR) package. An ExTR package is comprised of an ExTR Cover and one or more associated ExTR
documents (which may include Ex Test Reports, ExTR Addendums and ExTR of National Differences). All ExTR
package documents are compiled and reviewed by the ExTL. The Issuing ExCB indicates final approval of the
overall ExTR package on this ExTR Cover.
Copyright © 2010 International Electrotechnical Commission System for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx System), Geneva, Switzerland. All
rights reserved.
This blank publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx System is acknowledged as copyright owner and source of the material. The IECEx system takes no
responsibility for, and will not assume liability for, damages resulting from the reader's interpretation of the
reproduced material due to its placement and context.

TRF No. ExTR Cover_4 Page 1 of 4


ExTR Reference No. PRD-2019-SU82

Manufacturer’s name..................... : ErGong Explosion Protection Technology Co., Ltd.

Address ........................................ : No. 285 Shenghua Road, Huaishang District, Handan City, Anhui Province

Trademark .................................... : N/A


Particulars: Test item vs. Test requirements
Classification of installation and use .................................... : Stationary
Ingress protection ................................................................ : IP66or IP67
Rated ambient temperature range (°C) ................................. : -60℃ ≤Ta≤60℃
Rated service temperature range (°C) for Ex Components.... : --
General remarks:
The test results presented in this ExTR package relate only to the item or product tested.
▪ "(see Attachment #)" refers to additional information appended to the ExTR package.
▪ "(see appended table)" refers to a table appended to the ExTR package.
▪ Throughout this ExTR package, a point is used as the decimal separator.
▪ Where the term “N/A” appears in any part of an ExTR package, it indicates that the associated issue
was considered “Not applicable” to the involved evaluation.
▪ In accordance with IECEx 02, a Receiving ExCB may request a sample of the Ex equipment and
copies of the documentation referred to in an ExTR Cover.
The technical content of this ExTR package shall not be reproduced except in full without the written approval
of the Issuing ExCB and ExTL.
Copy of Marking Plate:

General product information:


1. This report covers the following types: EGKP-T Series
II 2G Ex db II B+H2T4/T5/T6 Gb
II 2G Ex eb[ia Ga]or[ib Gb] II B+H2T4/T5/T6 Gb
II 2D Ex tb III C T130°C/T95°C/T80°C Db IP66/IP67

2. Main Structures of the product:


2.1. ENAC-AlSi12 (b) (ZL102) low pressure die-casting aluminium alloy enclosure. The enclosure is also
welded by quality carbon steel and stainless steel plate. The content of Mg, Ti and Zr: ≤7.5%; high-
pressure electrostatic powder coated; with strong corrosion-proof performance.
2.2 Cover plate components are with button, indicator light, selector switch, breaker, potentiometer, glass
window and operating actuators (including handle, shaft, copper bush & other accessories according to

TRF No. ExTR Cover_4 Page 2 of 4


ExTR Reference No. PRD-2019-SU82

flameproof requirements), inner components are Power meter, tachometer, temperature controlled meter,
etc. kinds of meters, Disconnecting switch, DC power, Current transformer, Surge protector, MCCB, MCB,
AC contactor, thermorelay, Time relay, intermediate relay, fuse, control transformer, PLC, soft starter,
frequency converter, terminal, Light-operated switch, Time control machine, etc., see the instruction;
2.3. Thread specifications: NPT thread and Metric thread of ISO standard; please specify thread
specification when ordering. Both steel pipe wiring and cable wiring are suitable for this product.

3. The detailed information and original record related to this product and sample are recorded in the test
record, SN: PRD-2019-SU82

Note:(1) The sample types of temperature test: see clause 26.5.1 of IEC60079-0:2011.
(2) The sample types of other tests are: EGKP-T

4. The sample photos:

In accordance with OD 024, testing not fully performed by ExTL staff at the above ExTL address:
N/A
National differences considered as part of this evaluation, if any: N/A

“Conditions of Use” for Ex Equipment or “Schedule of Limitations” for Ex Components, if any:


1. Service ambient temperature: -60℃ to +60℃.
2. When assembly, operation and maintenance, the operator should follow the requirements of IEC 60079-
14:2007 Explosive atmospheres - Part 14: Electrical installations design, selection and erection, beside
Of BXM(D)81 Series Explosion-proof Power Distribution Equipment Instruction Manual.
3. If needed, repair of the flameproof joints must be made in compliance with the structural specifications
provided by the manufacturer.
4. Repair of the threaded joints must be made in compliance with the specifications provided by the
manufacturer. Repairs must not be made on the basis of values specified in table 4 of IEC60079-1:2014.
5. The entries shall be equipped with Ex certified cable glands with a compatible mode of protection for the
intended use if need.
WARNING - POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS.
CAUTION- USE FASTENERS WITH YIELD STRESS ≥ 450MPa.

TRF No. ExTR Cover_4 Page 3 of 4


ExTR Reference No.: PRD-2019-SU82.

Ex TEST REPORT
EN 60079-0
Explosive atmospheres – Part 0:
Equipment – General requirements

ExTR Reference Number............... :


ExTR Free Reference Number ...... :

Compi by + signature .... : Gavin Li


Reviewed by + signature .... : Konstantin Zhao

Approved by + signature .... : Li Tao

Ex Testing Laboratory ........ : Ente Certificazione Macchine

Address .......................................... : Via Cà Bella, 243 - 40050- Italia

Applicant’s name............................ : ErGong Explosion Protection Technology Co., Ltd.


Address .......................................... : No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province
Standard......................................... : EN 60079-0:2018
Test procedure ............................... : EXTR
Test Report Form Number ............. : ExTR60079-0_6B (released 2011-08)
Instructions for Intended Use of Ex Test Report:
An Ex Test Report provides a clause-by-clause documentation of the initial evaluation and testing that verified
compliance of an item or product with an IEC Ex standard. This Ex Test Report is part of an ExTR package
that may include other Ex Test Report, Addendum, National Differences and Partial Testing documents, along
with a single ExTR Cover. An Ex Test Report is to be compi and reviewed by the ExTL. The Issuing ExCB
indicates final approval of the Ex Test Report as part of the overall ExTR package on the associated ExTR
Cover.
Copyright © 2011 International Electrotechnical Commission System for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx System), Geneva, Switzerland. All
rights reserved.
This blank publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx System is acknow ged as copyright owner and source of the material. The IECEx system takes no
responsibility for, and will not assume liability for, damages resulting from the reader's interpretation of the
reproduced material due to its placement and context.

Possible test case verdicts:


- test case does not apply to the test item ..................... :N / A
- test item does meet the requirement ........................... :Pass
General remarks:
The test results presented in this Ex Test Report relate only to the item or product tested.
▪ "(see Attachment #)" refers to additional information appended to this document.
▪ "(see appended table)" refers to a table appended to this document.
▪ Throughout this document, a point “.” is used as the decimal separator.
The technical content of this Ex Test Report shall not be reproduced except in full without the written approval
of the Issuing ExCB and ExTL.

TRF No. ExTR60079-0_6B Page 1 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict

1 Scope

2 Normative references

3 Terms and definitions

4 Equipment grouping

4.1 Group I Not Group I N/A

4.2 Group II IIB T5 or T6 Pass

4.3 Group III IIIC T130℃ or T95℃ or T80℃. Pass

Equipment for a particular Not intend to be used in a particular explosive


4.4 N/A
explosive atmosphere atmosphere.

5 Temperatures

5.1 Environmental influences


5.1.1 Ambient temperature -60℃ to +60℃ Pass
External source of heating or
5.1.2 No external source of heating or cooling. N/A
cooling

Use maximum surface temperature instead of


5.2 Service temperature service temperature. Refer to IEC60079-0 Pass
clause 26.5.1.

5.3 Maximum surface temperature


Determination of maximum Refer to IEC60079-0 clause 26.5.1 for
5.3.1 Pass
surface temperature determination of maximum surface temperature.
5.3.2 Limitation of maximum surface temperature
5.3.2.1 Group I electrical equipment group II and group III. N/A
5.3.2.2 Group II electrical equipment Refer to Cl. 26.5.1 in test report IEC60079-0. Pass
5.3.2.3 Group III electrical equipment
Maximum surface temperature Refer to Cl. 26.5.1 in test report IEC60079-0.
5.3.2.3.1 Pass
determined without a dust layer
Maximum surface temperature Maximum surface temperature was measured
5.3.2.3.2 N/A
with respect to dust layers without dust layers.

TRF No. ExTR60079-0_6B Page 2 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Small component temperature Not a small component.
5.3.3 for Group I or Group II electrical N/A
equipment

6 Requirements for all electrical equipment

The Power Distribution Equipment comply with


6.1 General Pass
the requirements of
IEC 60079-0, IEC 60079-1 and IEC 60079-31.

Mechanical strength of The impact test was made on the Explosion-


6.2 Pass
equipment proof Power Distribution Equipment. Refer to
report IEC 60079-0 clause 26.4.2.

6.3 Opening times No capacitors or hot components N/A

Circulating currents in
6.4 enclosures (e.g. of large No circulating current. N/A
electrical machines)

6.5 Gasket retention No gaskets for protection of ingress. N/A

Electromagnetic and ultrasonic No electromagnetic and ultrasonic energy


6.6 N/A
energy radiating equipment radiating equipment.
No electromagnetic and ultrasonic energy
6.6.1 Radio frequency sources N/A
radiating equipment.
Lasers or other continuous wave No electromagnetic and ultrasonic energy
6.6.2 N/A
sources radiating equipment.
No electromagnetic and ultrasonic energy
6.6.3 Ultrasonic sources N/A
radiating equipment.

7 Non-metallic enclosures and non-metallic parts of enclosures

7.1 General
7.1.1 Applicability Spraying layer. Pass
7.1.2 Specification of materials
Refer to the documents provided by the
7.1.2.1 General Pass
manufacturer.
7.1.2.2 Plastic materials No plastic materials. N/A
The type of protection does not depend on
7.1.2.3 Elastomers the sealing gasket between the glass and the N/A
clamping ring .

7.2 Thermal endurance


The thermal endurance test was carried out. For
7.2.1 Tests for thermal endurance more details, see clause 26.8, 26.9 in Pass
IEC60079-0.

TRF No. ExTR60079-0_6B Page 3 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
7.2.2 Material selection No plastic material N/A
Alternative qualification of Alternative qualification of elastomeric sealing
7.2.3 N/A
elastomeric sealing O-rings O-ring is not used.

7.3 Resistance to light No non metallic enclosure. N/A

7.4 Electrostatic charges on external non-metallic materials


The enclosure is made of metal. The
Pass
7.4.1 Applicability spraying layer is covered the
enclosure.
The thickness of spraying layer for
metallic enclosure surface is less
Avoidance of a build-up than 2mm.
of electrostatic
Marking the certificate with symbol “X” Pass
7.4.2 charge on Group I
or Group II electrical and add warning marking:
equipment “WARNING – POTENTIAL
ELECTROSTATIC CHARGING
HAZARD – SEE INSTRUCTIONS”.
Avoidance of a build-up The enclosure is not made of plastic N /A
of electrostatic material.
7.4.3 charge on
equipment for
Group III

7.5 Accessible metal parts No accessible metal parts on the enclosure. N/A

8 Metallic enclosures and metallic parts of enclosures

The material of enclosure is cast aluminum


8.1 Material composition Pass
ENAC-AlSi12 (b) (ZL102)

8.2 Group I Group II and Group III equipment N/A

The enclosure of Power Distribution


Equipment contents 0.3% in total of Mg and
8.3 Group II Pass
Ti. Refer to the documents provided by the
manufacturer. The content of Mg, Ti and Zr of
it is less than 7.5%.

The enclosure of Power Distribution


Equipment contents 0.3% in total of Mg and
8.4 Group III Pass
Ti. Refer to the documents provided by the
manufacturer. The content of Mg, Ti and Zr of
it is less than 7.5%.

9 Fasteners

TRF No. ExTR60079-0_6B Page 4 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Ten M6x25 hexagon socket screws are used to
fasten the shell body and the cover. These
hexagon socket screws can only be removed by
the Allen wrench.
Ten M6x25 hexagon socket screws are used to
9.1 General Pass
fasten the shell body and clamping ring. These
hexagon socket screws can only be removed by
the Allen wrench.
All fasteners are made of stainless steel
0Cr18Ni9

All hexagon socket screws comply with


9.2 Special fasteners GB 70.1 (ISO4762). The thread is Pass
of a tolerance fit of 6g/6H.

9.3 Holes for special fasteners


The depth of the threaded through holes used Pass
9.3.1 Thread engagement for the screw M6×20 is 8mm, it is greater than
the major diameter of the thread of the fastener.
The thread holes for M6×20 have a tolerance Pass
class 6H.
9.3.2 Tolerance and clearance
The holes under the head of the screws have a
medium tolerance class of H13.
9.3.3 Hexagon socket set screws No hexagon socket set screws. N/A

10 Interlocking devices No interlocking devices N/A

Wires go through light source compartment and


11 Bushings power compartment encapsulated with epoxy Pass
resin E44.

1. The cementing material on glass cover is XP-


1132 silicone resin sealant. The temperature
scope of XP-1132A silicone resin sealant is from
-65℃ to +300℃. The maximum service
temperature during the test is 79℃.
12 Materials used for cementing 2. The cementing material of bushing between Pass
the light source compartment and the power
compartment is used to encapsulate the wires.
The cementing material is E44 epoxy resin. The
COT of it is from -60℃ to +180℃. The maximum
service temperature during the test is 81℃.

13 Ex Components

13.1 General No Ex components N/A

13.2 Mounting No Ex components N/A

TRF No. ExTR60079-0_6B Page 5 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict

13.3 Internal mounting No Ex components N/A

13.4 External mounting No Ex components N/A

13.5 Ex Component certificate No Ex components N/A

14 Connection facilities and terminal compartments

The terminals are located in the power


14.1 General Pass
compartment.

The opening dimensions of the power


14.2 Termination compartment compartment is 180mm×110mm. The Pass
conductor can be readily connected.

The power compartment is of type “d” and


14.3 Type of protection Pass
“tb”.

14.4 Creepage and clearance Type of protection “d” and “tb”. N/A

15 Connection facilities for earthing or bonding conductors

15.1 Equipment requiring earthing


Two M5 earthing Hexagon head bolts are
located in the power compartment, refer to the
15.1.1 Internal Pass
drawing 1HRW 000 059 and 1HRW 000
072.
An M5 earthing Hexagon head bolt is located on
15.1.2 External the shell body, refer to the drawing 1HRW 000 Pass
059 and 1HRW 000 072.

Equipment not requiring


15.2 The equipment requires earthing. N/A
earthing

15.3 Size of conductor connection See part IEC 60079-0 clause 15.1. Pass

The material of earthing bolts and washers is


15.4 Protection against corrosion Pass
stainless steel (0Cr18Ni9).

Spring washers and flat washers are used for


Secureness of electrical
15.5 connecting the earthing facilities against Pass
connections
loosening and twisting.

TRF No. ExTR60079-0_6B Page 6 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
16 Entries into enclosures

Two entry holes are provided to the equipment.


16.1 General They are located in enclosure of power Pass
compartment

Thread specification of the entry hole is


16.2 Identification of entries Pass
specified in the manual

16.3 Cable glands Cable glands are not included. N/A

The unused entry holes should be blanked by


16.4 Blanking elements suitably certificated plugs. The dimension of Pass
entry is specified in the manual.

16.5 Thread adapters No thread adapters N/A

See clause 26.5.1.3. A guidance to the user


Temperature at branching point
16.6 “only use cables suitable for 80℃” is provided in Pass
and entry point
the instruction and the nameplate.

Electrostatic charges of cable


16.7 Reference only. Pass
sheaths

17 Supplementary requirements for rotating machines

17.1 Ventilation
17.1.1 Ventilation openings No rotating machines. N/A
17.1.2 Materials for external fans No rotating machines. N/A
17.1.3 Cooling fans of rotating machines
17.1.3.1 Fans and fan hoods No rotating machines. N/A
Construction and mounting of
17.1.3.2 No rotating machines. N/A
the ventilating systems
Clearances for the ventilating
17.1.3.3 No rotating machines. N/A
system
17.1.4 Auxiliary motor cooling fans No rotating machines. N/A
17.1.5 Ventilating fans
17.1.5.1 Applicability No rotating machines. N/A
17.1.5.2 General No rotating machines. N/A
17.1.5.3 Fan and fan hoods No rotating machines. N/A
17.1.5.4 Construction and mounting No rotating machines. N/A
17.1.5.5 Clearances for rotating parts No rotating machines. N/A

TRF No. ExTR60079-0_6B Page 7 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
17.2 Bearings No rotating machines. N/A

18 Supplementary requirements for switbhgear

18.1 Flammable dielectric No switbhgear N/A

18.2 Disconnectors No switbhgear N/A

18.3 Group I – Provisions for locking No switbhgear N/A

18.4 Doors and covers No switbhgear N/A

Supplementary requirements for


19 Fuses are not included. N/A
fuses

20 Supplementary requirements for plugs, sockets outlets and connectors

Plugs, socket outlets and connectors are not


20.1 General N/A
included.

Plugs, socket outlets and connectors are not


20.2 Explosive gas atmospheres N/A
included.

Plugs, socket outlets and connectors are not


20.3 Explosive dust atmospheres N/A
included.

Plugs, socket outlets and connectors are not


20.4 Energized plugs N/A
included.

21 Supplementary requirements for luminaires

No protection guard. Refer to Cl. 26.4.2 for Pass


relevant tests.
21.1 General
The mounting of the Explosion-proof Power
Distribution Equipment depends on the two
M10 screws and a mounting bracket.

The Power Distribution Equipment have


Covers for luminaires of EPL
21.2 warning words “W ARNING- DO NOT OPEN Pass
Mb, EPL Gb, or EPL Db
WHEN ENERGIZED” in the nameplate.

Covers for luminaires of EPL Gc


21.3 Gb and Db equipment. N/A
or EPL Dc

TRF No. ExTR60079-0_6B Page 8 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict

21.4 Sodium lamps Not applicable N/A

22 Supplementary requirements for caplights and handlights

22.1 Group I caplights Not a caplight or handlight. N/A

Group II and Group III caplights


22.2 Not a caplight or handlight. N/A
and handlights

23 Apparatus incorporating cells and batteries

23.1 General No cells or batteries. N/A

23.2 Batteries No cells or batteries. N/A

23.3 Cell types No cells or batteries. N/A

23.4 Cells in a battery No cells or batteries. N/A

23.5 Ratings of batteries No cells or batteries. N/A

23.6 Interchangeability No cells or batteries. N/A

23.7 Charging of primary batteries No cells or batteries. N/A

23.8 Leakage No cells or batteries. N/A

23.9 Connections No cells or batteries. N/A

23.10 Orientation No cells or batteries. N/A

Replacement of cells or
23.11 No cells or batteries. N/A
batteries

23.12 Replaceable battery pack No cells or batteries. N/A

Relevant documentation which was provided by


24 Documentation the manufacturer complies with IEC60079- Pass
0,IEC60079-1 and IEC60079-31.

TRF No. ExTR60079-0_6B Page 9 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Compliance of prototype or The samples which were provided by
25 Pass
sample with documents manufacturer complay with the documents.
26 Type tests
The tests were carried out on the samples
26.1 General according to the standards IEC 60079-0,IEC Pass
60079-1 and IEC60079-31.
Tests were carried out under the most
26.2 Test configuration Pass
unfavourable consideration.
Explosive test mixtures used in tests comply
26.3 Tests in explosive test mixtures with the requirements of standard in Pass
IEC60079-1.
26.4 Tests of enclosures
26.4.1 Order of tests
The shell body and cover of enclosure is made Pass
of aluminium alloy. Test sequence of metallic
enclosure were as follows:
1. impact test
Metallic enclosures, metallic
26.4.1.1 parts of enclosures and glass 2. pressure test
parts of enclosures 3. IP test
4. tests of ability of the enclosure to withstand
pressure
5. test for non-transmission of an internal ignition
1.Encapsulation in the leading sheath. Pass
Non-metallic enclosures or non-
26.4.1.2 2.Cementing material between glass plate and
metallic parts of enclosures
shell body.
26.4.1.2.1 Group I electrical equipment Group II and group III equipment. N/A
Tests were performed in the following order:
1. thermal endurance to heat
2. thermal endurance to cold
3. impact test
Group II and Group III electrical 4. pressure test
26.4.1.2.2 Pass
equipment 5. IP test
6. tests of ability of the enclosure to withstand
pressure
7. test for non-transmission of an internal ignition
1. Place of impact: cover and shell body
Impact energy: 7J
Temperature: 23℃
Number of samples: 2
Times of impact: 1 for each place Pass
26.4.2 Resistance to impact
2. Place of impact: glass plate
Impact energy: 4J
Temperature:-45℃
Number of samples: 2
Times of impact: 1 for each sample

TRF No. ExTR60079-0_6B Page 10 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
26.4.3 N /A
Drop test The equipment is stationary installed.

26.4.4 No damage affecting the explosion- Pass


Acceptance criteria
proof performance has been found.
26.4.5
Degree of protection (IP) by enclosures

26.4.5.1 The enclosure was opened and closed


after the thermal endurance test. Pass
Test procedure
The samples were tested according to
IEC60529. The protection degree is IP65.
26.4.5.2
No ingress of dust or water after tests
Pass
Acceptance criteria for degree of protection by
enclosure.

26.5 Thermal tests


26.5.1 Temperature measurement
The Explosion-proof Power Distribution
26.5.1.1 General Equipment was measured upward 60°and Pass
downward 60°respectively.
Use maximum surface temperature instead of
26.5.1.2 Service temperature Pass
service temperature.

TRF No. ExTR60079-0_6B Page 11 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
1. Power: 60W; test voltage: AC330V;
direction: upward 60° .
Position Temperature rise
(K)
Light-transmitting part 23
Branching point 11
Entry point 4
Surface on the LED 16
power body
bushing 15
Cementing material on 10
light-transmitting part
When the ambient temperature is 55℃, the
maximum surface temperature is 78℃,comply
with class T6.
When the ambient temperature is 40℃, the
maximum surface temperature is 63℃,comply
with class T6.
The temperature 55℃ at branching point is
66℃.
26.5.1.3 Maximum surface temperature The temperature 55℃ at entry point is 59℃. Pass
2. Power: 60W; test voltage: AC330V;
direction: downward 60°.
Position Temperature rise
(K)
Light-transmitting part 27
Branching point 12
Surface on the LED 20
power body
Bushing 17
Cementing material on 11
light-transmitting part

When the ambient temperature is 55℃, the


maximum surface temperature is 82℃,comply
with class T5.
When the ambient temperature is 40℃, the
maximum surface temperature is 67℃,comply
with class T6.
The temperature 55℃ at branching point
is ℃.The temperature 55℃ at entry point is
67℃.

TRF No. ExTR60079-0_6B Page 12 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
3 Power: 90W ; test voltage: AC330V;
direction: upward 60° .
Position Temperature rise
(K)
Light-transmitting part 31
Branching point 22
Surface on the LED 34
power body
Bushing 26
Cementing material on 24
light-transmitting part
When the ambient temperature is 55℃, the
maximum surface temperature is 86℃,comply
with class T5.
When the ambient temperature is 40℃, the
maximum surface temperature is 71℃,comply
with class T6.
The temperature 55℃ at branching point is
77℃.

4. Power: 90W; test voltage: AC330V;


direction: downward 60°.
Position Temperature rise
(K)
Light-transmitting part 31
Branching point 23
Surface on the LED 34
power body
Bushing 26
Cementing material on 24
light-transmitting part
When the ambient temperature is 55℃, the
maximum surface temperature is 86℃,comply
with class T5.
When the ambient temperature is 40℃,
the maximum surface temperature
is 71℃,comply with class T6.
The temperature 55℃at branching point
is78℃.

After the measurement of maximum surface


temperature, use a jet of water of about 1 mm
diameter at a temperature 11℃ to spray on the
26.5.2 Thermal shock test light transmitting part of Explosion-proof Pass
Power Distribution Equipment with
temperature 86℃(under the environment
temperature 55℃). No breaking on the light
transmitting part.
26.5.3 Small component ignition test (Group I and Group II)
26.5.3.1 General No small component N/A
26.5.3.2 Procedure No small component N/A
26.5.3.3 Acceptance criteria No small component N/A

TRF No. ExTR60079-0_6B Page 13 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
26.6 Torque test for bushings
The wires go through the bushing and
26.6.1 Test procedure encapsulated by the epoxy resin. So the bushing N / A
can’t to subject to a torque test.
26.6.2 Acceptance criteria No torque applies on the bushing. N/A

26.7 Non-metallic enclosures or non-metallic parts of enclosures


Non-metallic parts of enclosure include
26.7.1 General Pass
cemented material and encapsulated material.
26.7.2 Test temperatures The enclosure is made by metal and glass. N/A

The Power Distribution Equipment were stored


26.8 Thermal endurance to heat for 336 hours at Pass
95℃ and 90% relative humidity , and then were
stored for 336 hours at 101℃.

After thermal endurance to heat the Power


Distribution Equipment were subjected to
26.9 Thermal endurance to cold 20 ° C at 50 % relative humidity for 24 hours, Pass
and then
immediately were stored for 24 hours at -45℃.

26.10 Resistance to light


26.10.1 Test procedure
The non-metallic materials are not exposed to
26.10.2 Acceptance criteria N/A
light.

Resistance to chemical agents


26.11 Group II and Group III N/A
for Group I electrical equipment

The materials of enclosureare metallic and


26.12 Earth continuity N/A
glass.

Surface resistance test of parts The materials of enclosure are metallic and
26.13 of parts of enclosures of non- glass. N/A
metallic materials

26.14 Measurement of capacitance


26.14.1 General Measurement of capacitance is not required. N/A
26.14.2 Test procedure Measurement of capacitance is not required. N/A

Verification of ratings of
26.15 Ventilating fans are not included. N/A
ventilating fans

Alternative qualification of Alternative qualification of elastomeric sealing


26.16 N/A
elastomeric sealing O-rings O-ring is not used.

TRF No. ExTR60079-0_6B Page 14 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
1. The over pressure test was carried on the
enclosure of light source compartment.
Test pressure: 0.83MPa.
Duration: 10s~12s.
27 Routine tests Pass
2. The over pressure test was carried on the
enclosure of power.
Test pressure: 1.3MPa.
Duration: 10s~12s.

28 Manufacturer's responsibility

The manufacturer carries out the verifications or


Conformity with the
28.1 tests. The sample conforms to the Pass
documentation
documentation.

The manufacturer has prepared a certificate


confirming that the equipment is in conformity
28.2 Certificate with the requirements of the standards IEC Pass
60079-0, IEC 60079-1 and IEC 60079-31. This
point shall be checked during QAR assessment.

The Power Distribution Equipment are


designed and manufactured, assessed and
28.3 Responsibility for marking Pass
tested according to IEC 60079-0, IEC 60079-1,
and IEC 60079-31. The sample complies with the
documentation.

29 Marking

The nameplate complies with the requirements


29.1 Applicability Pass
of IEC 60079-0, IEC 60079-1 and IEC 60079-31.

The nameplate is made of 2Cr13 and fixed on


29.2 Location Pass
the cover with rivets.

29.3 General For the nameplate, see the cover of this report. Pass

Ex db IIB T□ Gb, for the □, see general


Ex marking for explosive gas
29.4 product information in the report cover. Includes Pass
atmospheres
Ex marking.

Ex marking for explosive dust Ex tb IIIC T□ Db IP65, for the □, see general
29.5 Pass
atmospheres product information in the report cover.

Combined types (or levels) of The enclosure of EGKP-T- series is protected


29.6 N/A
protection by “d” and “tb” .

TRF No. ExTR60079-0_6B Page 15 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
The enclosure of EGKP-T- series is protected
29.7 Multiple types of protection Pass
by “d” and “tb” .

Ga equipment using two


29.8 independent Gb types (or levels) Gb equipment N/A
of protection

29.9 Ex Components No Ex components N/A

Small equipment and small Ex


29.10 No small Ex components. N/A
Components

Extremely small equipment and


29.11 No small Ex components. N/A
extremely small Ex Components

The Power Distribution Equipment have


warning words”DO NOT OPEN W HEN
ENERGIZED” , “POTENTIAL ELECTROSTATIC
29.12 Warning markings Pass
CHARGING HAZARD – SEE INSTRUCTIONS”,”
WARNING-DO NOT OPEN LIGHT SOURCE
COMPARTMENT” on the nameplate.

Alternate marking of equipment


29.13 No alternate marking. N/A
protection levels (EPLs)
Alternate marking of type of
29.13.1 protection for explosive gas No alternate marking. N/A
atmospheres
Alternate marking of type of
29.13.2 protection for explosive dust No alternate marking. N/A
atmospheres

29.14 Cells and batteries Cells or batteries are not included. N/A

Converter-fed electrical
29.15 No converter-fed electrical machines. N/A
machines

29.16 Examples of marking Reference only N/A

30 Instructions

The instruction manual includes application


range, model implication, compliances, working
conditions, technical parameters, installation,
30.1 General Pass
usage and maintenance, outline and installation
dimension, electric schematic diagram,
transportation, storage and ordering information.

30.2 Cells and batteries No cells or batteries. N/A

TRF No. ExTR60079-0_6B Page 16 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
30.3 Electrical machines No electrical machines. N/A

30.4 Ventilating fans No ventilating fans. N/A

Annex A
Supplementary requirements for cable glands N/A
(Normative)
A.1 General The Power Distribution Equipment do not N/A
contain cable glands.
A.2 Constructional requirements
A.2.1 Cable sealing The Power Distribution Equipment do not N/A
contain cable glands.
A.2.2 Filling compounds The Power Distribution Equipment do not N/A
contain cable glands.
A.2.3 Clamping
A.2.3.1 General The Power Distribution Equipment do not N/A
contain cable glands.
A.2.3.2 Group II or III cable glands The Power Distribution Equipment do not N/A
contain cable glands.
A.2.4 Lead-in of cable
A.2.4.1 Sharp edges The Power Distribution Equipment do not N/A
contain cable glands.
A.2.4.2 Point of entry The Power Distribution Equipment do not N/A
contain cable glands.
A.2.5 Released by a tool The Power Distribution Equipment do not N/A
contain cable glands.
A.2.6 Fixing The Power Distribution Equipment do not N/A
contain cable glands.
A.2.7 Degree of protection The Power Distribution Equipment do not N/A
contain cable glands.
A.3 Type tests
A.3.1 Tests of clamping of non-armoured and braided cables
A.3.1 Cable glands with
. clamping by the The Power Distribution Equipment do not N/A
1 sealing ring contain cable glands.
Cable glands with clamping by
A.3.1.2 The Power Distribution Equipment do not N/A
filling compound
contain cable glands.
Cable glands with clamping by
A.3.1.3 The Power Distribution Equipment do not N/A
means of a clamping device
contain cable glands.
A.3.1.4 Tensile test The Power Distribution Equipment do not N/A
contain cable glands.
A.3.1.5 Mechanical strength The Power Distribution Equipment do not N/A
contain cable glands.
A.3.2 Tests of clamping of armoured cables N/A
Tests of clamping where the
A.3.2.1 armourings are clamped by a The Power Distribution Equipment do not N/A
device within the gland contain cable glands.
A.3.2.1.1 Tensile test The Power Distribution Equipment do not N/A
contain cable glands.
A.3.2.1.2 Mechanical strength The Power Distribution Equipment do not N/A
contain cable glands.

TRF No. ExTR60079-0_6B Page 17 of 18


ExTR Reference No.: PRD-2019-SU82.

Tests of clamping where the


A.3.2.2 armourings are not clamped by The Power Distribution Equipment do not N/A
a device within the gland contain cable glands.
Type test for resistance to
A.3.3 The Power Distribution Equipment do not N/A
impact
contain cable glands.
Test for degree of protection (IP)
A.3.4 The Power Distribution Equipment do not N/A
of cable glands
contain cable glands.
A.4 Marking

TRF No. ExTR60079-0_6B Page 18 of 18


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
A.4.1 Marking of cable glands The Power Distribution Equipment do not N/A
contain cable glands.
Marking of cable-sealing
A.4.2 The Power Distribution Equipment do not N/A
rings
contain cable glands.

Annex B
Requirements for Ex Components N/A
(Normative)

Annex C
Example of rig for resistance to impact test
(Informative)

Annex D
Motors supplied by converters
(Informative)

Annex E
Temperature rise testing of electric machines
(Informative)

Annex F
Guideline flowchart for tests of non-metallic enclosures or non-metallic parts of enclosures (26.4)
(Informative)

Measurement Section, including Additional Narrative Remarks (as deemed applicable)


N/A

TRF No. ExTR60079-0_6B Page 19 of 18


Ex TEST REPORT
EN 60079-1
Explosive atmospheres – Part 1: Equipment protection by flameproof enclosures "d"

ExTR Reference Number .............. :


ExTR Free Reference Number...... :
Compi by + signature ).... : Gavin Li
Reviewed by + signature ...: Konstantin Zhao

Approved by + signature .... : Li Tao


Nov, 4 . 2019
Date of issue.................................. : th

Ex Testing Laboratory ....... : Ente Certificazione Macchine


Address ......................................... : Via Cà Bella, 243 - 40050- Italia

Applicant’s name ..... . ErGong Explosion Protection Technology Co., Ltd.


Address ..................................... . No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province

Standard ........................................ : EN 60079-1:2014,


Test procedure .............................. : EXTR
Test Report Form Number............. : ExTR60079-1_7A (released 2014-07)
Instructions for Intended Use of Ex Test Report:
An Ex Test Report provides a clause-by-clause documentation of the initial evaluation and testing that verified
compliance of an item or product with an IEC Ex standard. This Ex Test Report is part of an ExTR package that
may include other Ex Test Report, Addendum, National Differences and Partial Testing documents, along with a
single ExTR Cover. An Ex Test Report is to be compi and reviewed by the ExTL. The Issuing ExCB
indicates final approval of the Ex Test Report as part of the overall ExTR package on the associated ExTR Cover.

Copyright © 2014 International Electrotechnical Commission System for Certification to Standards


Relating to Equipment for use in Explosive Atmospheres (IECEx System), Geneva, Switzerland. All
rights reserved.
This blank publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx System is acknow ged as copyright owner and source of the material. The IECEx system takes no
responsibility for, and will not assume liability for, damages resulting from the reader's interpretation of the
reproduced material due to its placement and context.

Possible test case verdicts:


- test case does not apply to the test item ..................... : N/A
- test item does meet the requirement........................... : PASS
General remarks:
The test results presented in this Ex Test Report relate only to the item or product tested.
▪ "(see Attachment #)" refers to additional information appended to this document.
▪ "(see appended table)" refers to a table appended to this document.
▪ Throughout this document, a point “.” is used as the decimal separator.
The technical content of this Ex Test Report shall not be reproduced except in full without the written approval
of the Issuing ExCB and ExTL.

Page 1 of 19
ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

1 Scope

2 Normative references

3 Terms and definitions

4 Level of protection (equipment protection level, EPL)

4.1 General EPL of explosion-proof Power Distribution Pass


Equipment is Gb.

4.2 Requirements for level of The explosion-proof Power Distribution N/A


protection “da” Equipment with EPL Gb.

4.3 Requirements for level of The explosion-proof Power Distribution Pass


protection “db” Equipment with EPL Gb.

4.4 Requirements for level of protection “dc”


4.4.1 General The explosion-proof Power Distribution N/A
Equipment with EPL Gb.
4.4.2 Construction of “dc” devices
4.4.2.1 General The explosion-proof Power Distribution N/A
Equipment with EPL Gb.
4.4.2.2 Free internal volume The explosion-proof Power Distribution N/A
Equipment with EPL Gb.
4.4.2.3 Seal protection The explosion-proof Power Distribution N/A
Equipment with EPL Gb.
4.4.2.4 Continuous operating The explosion-proof Power Distribution N/A
temperature (COT) Equipment with EPL Gb.
requirements
4.4.2.5 Ratings The explosion-proof Power Distribution N/A
Equipment with EPL Gb.
4.4.3 Tests for “dc” devices The explosion-proof Power Distribution N/A
Equipment with EPL Gb.

5 Flameproof joints

5.1 General requirements The joints of The Power Distribution Equipment Pass
comply with requirements of Clause
5 and are smeared with T039(A)wide –
temperature aircraft grease. Refer to technical
document provided by the manufacturer.

TRF No. ExTR60079-1_7A Page 2 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

5.2 Non-threaded joints


5.2.1 Width of joints (L) The net volume of power compartment is Pass
3
1420cm .
Flanged joint between the shell body and the
cover.
Measured value: L=25mm, i=0.04mm.
Required value: L=25mm, i=0.20mm.
Roughness: 1.6μm/1.6μm.
5.2.2 Gap (i) Refer to Cl. 5.2.1 of this report Pass
5.2.3 Spigot joints No spigot joints N/A
5.2.4 Holes in joint surfaces
5.2.4.1 General The joint between enclosure and cover is a Pass
flanged joint.
Measured value: l=14mm
Required value: l=9mm
5.2.4.2 Flanged joints with holes The distance l is measured between each hole Pass
outside the enclosure (see and the inside of the enclosure.
Figures 3 and 5)
5.2.4.3 Flanged joints with holes See 5.2.4.2. N/A
inside the enclosure (see
Figure 4)
5.2.4.4 Spigot joints where, to the The explosion-proof Power Distribution N/A
edges of the holes, the joint Equipment do not contain spigot joints.
consists of a cylindrical part
and a plane part (see Figure
6)
5.2.4.5 Spigot joints where, to the The explosion-proof Power Distribution N/A
edges of the holes, the joint Equipment do not contain spigot joints.
consists only of the plane
part (see Figures 7 and 8), in
so far as plane joints are
permitted (see 5.2.7)
5.2.5 Conical joints No conical joints. N/A
5.2.6 Joints with partial cylindrical No joints with partial cylindrical surfaces. N/A
surfaces (not permitted for
Group IIC)
5.2.7 Flanged joints for acetylene No flanged joints. N/A
atmospheres
5.2.8 Serrated joints No serrated joints. N/A
5.2.9 Multi-step joints No multi-step joints. N/A

TRF No. ExTR60079-1_7A Page 3 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

5.3 Threaded joints Position: two thread entries for cable gland(no Pass
plug)
Thread specification: M25
Thread pitbh: 1.5mm
Length of thread: 25mm
Number of full thread: 16
Metric thread complies with the requirements of
6g/6H fit tolerance and fulfils the requirements
of medium tolerance in ISO965-1 and ISO965-
3.

5.4 Gaskets (including O-rings) No gaskets. N/A

5.5 Equipment using capillaries No capillaries. N/A

6 Sea joint

6.1 Cemented joints


6.1.1 General The cemented joints were submitted to thermal Pass
endurance tests. Refer to Cl. 26.8 and Cl. 26.9
in test report IEC60079-0.
1. The wires going through between two
compartments are encapsulated by E44.
2. The glass cover and the shell body are
cemented by XP-1132A silicone resin sealant.
6.1.2 Mechanical strength 1.W ires going through part between two Pass
compartments use E44 epoxy resin , M8 and
M12 thread joints to enhance mechanical.
For pressure test see part IEC 60079-1 clause
15.1.3.
2. A pressing ring and ten M6 screws are used
to be provided to ensure the mechanical
strength of the cemented joint between glass
cover and enclosure ring.
6.1.3 Width of cemented joints 1. The length of encapsulated wires between Pass
two compartments is 20mm.
2. The width of cemented joint between the
glass plate and shell body of Power
Distribution Equipment is 10mm.

6.2 Fused glass joints


6.2.1 General No fused glass joints. N/A
6.2.2 Width of fused glass joints No fused glass joints. N/A

TRF No. ExTR60079-1_7A Page 4 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

7 Operating rods No operating rods. N/A


8 Supplementary requirements for shafts and bearings

8.1 Joints of shafts


8.1.1 General No shafts or bearings. N/A
8.1.2 Cylindrical joints No shafts or bearings. N/A
8.1.3 Labyrinth joints No shafts or bearings. N/A
8.1.4 Joints with floating glands No shafts or bearings. N/A

8.2 Bearings
8.2.1 Sleeve Bearings No shafts or bearings. N/A
8.2.2 Rolling-element bearings No shafts or bearings. N/A

9 Light-transmitting parts The light-transmitting part is made of toughened Pass


glass and no internal mechanical stress is
produced during the glass plate installation

10 Breathing and draining devices which form part of a flameproof enclosure

10.1 General No breathing or draining device. N/A

10.2 Openings for breathing or No breathing or draining device. N/A


draining

10.3 Composition limits No breathing or draining device. N/A

10.4 Dimensions No breathing or draining device. N/A

10.5 Elements with measurable No breathing or draining device. N/A


paths

10.6 Elements with non- No breathing or draining device. N/A


measurable paths

10.7 Removable devices


10.7.1 General No breathing or draining device. N/A
10.7.2 Mounting arrangements of No breathing or draining device. N/A
the elements

10.8 Mechanical strength No breathing or draining device. N/A

TRF No. ExTR60079-1_7A Page 5 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

10.9 Breathing devices and draining devices when used as Ex components


10.9.1 General No breathing or draining device. N/A
10.9.2 Mounting arrangements of No breathing or draining device. N/A
the elements and
components
10.9.3 Type tests for breathing and draining devices used as Ex components
10.9.3.1 General No breathing or draining device. N/A
10.9.3.2 Thermal tests
10.9.3.2.1 General No breathing or draining device. N/A
10.9.3.2.2 Test procedure No breathing or draining device. N/A
10.9.3.2.3 Acceptance criteria No breathing or draining device. N/A
10.9.3.3 Test for non-transmission of an internal ignition
10.9.3.3.1 General No breathing or draining device. N/A
10.9.3.3.2 Test procedure No breathing or draining device. N/A
10.9.3.3.3 Acceptance criteria No breathing or draining device. N/A
10.9.3.4 Test of the ability of the breathing and draining device to withstand pressure
10.9.3.4.1 Test procedure No breathing or draining device. N/A
10.9.3.4.2 Acceptance criteria No breathing or draining device. N/A
10.9.4 Ex component certificate No breathing or draining device. N/A

11 Fasteners and openings

11.1 Type of fastener See part IEC 60079-0 clauses 9.1 and 9.2. Pass

11.2 Plastic material or light alloys Plastic material or light alloys fasteners are not N/A
included.

11.3 Yield stress The property class of the M6 screws is A*-70. Pass
The warning words “CAUTION-USE
FASTENER W ITH YIELD STRESS≥
2
450N/mm ” are located in the nameplate.

11.4 Studs Studs are not included. N/A

11.5 Fasteners through walls No fasteners through walls. N/A

11.6 Blind holes No blind holes. N/A

11.7 Screws into blind holes No blind holes. N/A

TRF No. ExTR60079-1_7A Page 6 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

11.8 Closing of through holes Through holes in the wall are not included. N/A

11.9 Separate fastening No threaded doors or covers. N/A


arrangements for threaded
doors/covers

12 Materials

12.1 Tests prescribed by Clauses The Explosion-proof Power Distribution Pass


14 to 16 Equipment was submitted to the tests
specified from Cl. 14 to Cl.16.

12.2 Assembly of multiple The Explosion-proof Power Pass


flameproof enclosures Distribution Equipment includes two
flameproof compartments.

12.3 Intercommunicating No intercommunicating enclosure N/A


enclosure compartments compartments

12.4 Use of cast iron No use of cast iron. N/A

12.5 Use of liquids No use of liquids. N/A

12.6 Insulating materials for Group Group II N/A


I apparatus

12.7 Zinc content The enclosure is made of aluminium alloy Pass


ENAC-AlSi12(b) which contains 0.15% Zn.

12.8 Copper or copper alloys in No copper or copper alloys. N/A


explosive gas atmospheres
containing acetylene

13 Entries for flameproof enclosures

13.1 General There are two entries in the enclosure. The Pass
thread specification of entry is M25×1.5-6H,
which complies with the requirements of
tolerance. The thread specification of entry is
marked in the manual.

13.2 Threaded holes See clause 13.1 of this report. Pass

TRF No. ExTR60079-1_7A Page 7 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

13.3 Non-threaded holes (for Group II. N/A


Group I only)

13.4 Cable glands No cable gland. N/A

13.5 Conduit sealing devices


13.5.1 Conduit sealing devices, No conduit sealing device. N/A
whether integral or separate,
13.5.2 Permitted for Group II only No conduit sealing device. N/A
13.5.3 Sealing device such as a No conduit sealing device. N/A
stopping box with setting
compound

13.6 Plugs and sockets and cable couplers


13.6.1 Construction & mounting No plugs, sockets or cable couplers. N/A
13.6.2 Flameproof joints of contact No plugs, sockets or cable couplers. N/A
parts
13.6.3 Flameproof properties in the No plugs, sockets or cable couplers. N/A
event of internal explosion
13.6.4 Not connected to an No plugs, sockets or cable couplers. N/A
interlocking switbh
13.6.5 Exemption & warning label No plugs, sockets or cable couplers. N/A

13.7 Bushings Bushing between light source compartment and Pass


the power compartment is sea by Epoxy resin
E44.
For the length of the compound and test, see
clause 6.3 and annex C.

13.8 Blanking elements No blanking elements. Pass

14 Verification and tests The maximum surface temperature was Pass


measured under the most unfavourable
condition. See part IEC 60079-0 clause
26.5.1.3.

15 Type tests

TRF No. ExTR60079-1_7A Page 8 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

15.1 General Carry out test on sample which has been Pass
subjected to the tests of enclosures in
accordance with IEC 60079-0. Samples were
tested according to the following sequence:
1.reference pressure measurement,
2.overpressure test,
3.test for non-transmission of an internal
ignition.

15.2 Tests of ability of the enclosure to withstand pressure


15.2.1 General Tests of ability of the enclosure to withstand Pass
pressure are carried out according to Cl.15.1.2
and Cl.15.1.3. After the tests, no permanent
damage or deformation has been found.
15.2.2 Determination of explosion pressure (reference pressure)
15.2.2.1 General The reference pressure is measured under the Pass
condition of 20℃. The test factor is considered
during the test.
15.2.2.2 Test procedure 1.The explosive gas mixture used in test is (8± Pass
0.5)% ethylene in volume. The explosion
pressure are as follows:
Test position ethylene
(8±0.5)%
Light source
147kPa
compartment
LED power
565 kPa
compartment
2. The explosive gas mixture used in test is (31
±1)% hydrogen in volume. The power
compartment of EGKP-T- has the same size
with BAT86-160, The explosion pressure are as
follows:
Test position hydrogen
(31±1)%
Light source
383 kPa
compartment
LED power
608 kPa
compartment
According to Cl.15.1.2 of IEC60079-1, the
reference pressure should multiply 1.45 when
the minimum ambient temperature is -40℃.
So the maximum reference pressure of the light
source compartment of EGKP-T- is 555kPa.
So the maximum reference pressure of the
power compartment is 882kPa.
15.2.2.3 Rotating electrical machines Rotating electrical machines are not included. N/A
15.2.2.4 Pressure-piling Pressure-piling does not happen. N/A

TRF No. ExTR60079-1_7A Page 9 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

15.2.2.5 Apparatus intended for use in IIB+H2, for the nameplate, see the cover of this N/A
a single gas report.
15.2.3 Overpressure test
15.2.3.1 General 1. Test pressure for light source compartment Pass
was 0.84MPa.
Duration: 12s.
2. Test pressure for the power
compartment was 1.33MPa.
Duration: 11s.
No damage to the enclosure affecting the
explosion-proof performance has been found
after the tests.
15.2.3.2 Overpressure test - First See clause 15.2.3.1. Pass
method (static)
15.2.3.3 Overpressure test - Second First method N/A
method (dynamic)

15.3 Test for non-transmission of an internal ignition


15.3.1 General Tests were carried out on the light source Pass
compartment and power compartment.
15.3.2 Electrical equipment of groups I, IIA and IIB
15.3.2.1 Test gap and test gas See CI.15.3.3.3 N/A

15.3.2.2 Increasing of gaps for test See CI.15.3.3.3 N/A


15.3.2.3 Number of tests and See CI.15.3.3.3 N/A
acceptance criterion
15.3.3 Electrical apparatus of group IIC
15.3.3.1 General See CI.15.3.3.3 Pass
15.3.3.2 First method – Testing by See CI.15.3.3.3 N/A
increased test gap
15.3.3.3 Second method – Testing by During the tests, the gap between body and Pass
increased pressure connecting cover equals to the value specified
in drawing.
Test was carried out under the 1.5 times
atmospheric pressure, the explosive gas
mixture used in tests is (27.5±1.5)% hydrogen
in volume. Tests were carried out on light
compartment and ballast compartment. Test
five times for each gas mixture and each
compartment. The explosion was not
transmitted.
15.3.3.4 Third method – Testing by See CI.15.3.3.3 N/A
oxygen enrichment of test
gases

TRF No. ExTR60079-1_7A Page 10 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

15.3.3.5 Number of tests for single Test five times for the power compartment and Pass
piece production other five for light source compartment. The
explosions were not transmitted.

15.4 Tests of flameproof enclosures with breathing and draining devices


15.4.1 General Breathing and draining devices are not N/A
included.
15.4.2 Tests of ability of the enclosure to withstand pressure
15.4.2.1 General Breathing and draining devices are not N/A
included.
15.4.2.2 Replacement of breathing Breathing and draining devices are not N/A
and draining devices included.
15.4.2.3 Overpressure test Breathing and draining devices are not N/A
included.
15.4.3 Thermal tests
15.4.3.1 Test procedure Breathing and draining devices are not N/A
included.

15.4.3.2 Acceptance criterion Breathing and draining devices are not N/A
included.
15.4.4 Tests for non-transmission of an internal ignition
15.4.4.1 General Breathing and draining devices are not N/A
included.
15.4.4.2 Test procedure Breathing and draining devices are not N/A
included.
15.4.4.3 Non-transmission test for breathing and draining devices
15.4.4.3.1 General Breathing and draining devices are not N/A
included.
15.4.4.3.2 Method A – Testing by Breathing and draining devices are not N/A
increased pressure included.
15.4.4.3.3 Method B – Testing by Breathing and draining devices are not N/A
oxygen enrichment of test included.
gases
15.4.4.4 Acceptance criterion Breathing and draining devices are not N/A
included.

15.5 Tests for “dc” devices


15.5.1 General IIB equipment N/A
15.5.2 Preparation of “dc” samples IIB equipment N/A
15.5.3 Test conditions for “dc” devices
15.5.3.1 General IIB equipment N/A
15.5.3.2 Test procedure IIB equipment N/A

16 Routine tests

TRF No. ExTR60079-1_7A Page 11 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

16.1 General
16.1.1 Overview The Power Distribution Equipment are Pass
submitted to static
16.1.2 Routine overpressure test – overpressure
The test.
enclosures of the Power Distribution Pass
first method Equipment are submitted
to static overpressure test. Test pressure for
light source compartment is 0.84MPa. Test
pressure for the power compartment is
1.3MPa.
Test duration: 10s to 12s.
The routine test is considered satisfactory if the
enclosure suffers no permanent deformation or
damage affecting the explosion-proof
performance and the joints in no place are
permanently
First method enlarged.
was used.
16.1.3 Routine test – second N/A
method

16.1.4 Routine test – empty Routine overpressure test is carried out on the Pass
enclosure & parts of enclosure empty.
enclosure

16.2 Enclosures not incorporating Power Distribution Equipment doesn’t Pass


a welded construction incorporating a welded construction.

16.3 Enclosures incorporating a Enclosures not incorporating a welded N/A


welded construction construction

16.4 Bushings not specific to one See 2.1.4. Pass


flameproof enclosure

16.5 Acceptance criteria After water pressure test, there is no damage to Pass
enclosure or permanent deformation on joints
that affecting the flameproof performance or no
leakage through the enclosure wall.

16.6 Batbh testing Each part of enclosure has been tested of Pass
pressure test, see drawing 1HRW 020 062,
1HRW 050 063, 1HRW 050 033

17 Switbhgear for Group I

17.1 General Switbhgear is not included. N/A

17.2 Means of isolation


17.2.1 General Switbhgear is not included. N/A

TRF No. ExTR60079-1_7A Page 12 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

17.2.2 Fitted inside Ex d enclosure Switbhgear is not included. N/A


17.2.3 Fitted inside another Switbhgear is not included. N/A
enclosure
17.2.4 Plug and socket or a cable Switbhgear is not included. N/A
coupler – Compliance with
13.3

17.3 Doors or covers


17.3.1 Quick-acting doors or covers No doors or covers. N/A
17.3.2 Doors or covers fixed by No doors or covers. N/A
screws
17.3.3 Threaded doors or covers No doors or covers. N/A

18 Lampholders and lamp caps

18.1 General Lamp holders or lamp caps are not parts of N/A
enclosure.

18.2 Device preventing lamps Lamp holders or lamp caps are not parts of N/A
working loose enclosure.

18.3 Holders and caps for lamps with cylindrical caps


18.3.1 Holders and caps for tubular Lamp holders or lamp caps are not parts of N/A
fluorescent lamps enclosure.
18.3.2 Other holders Lamp holders or lamp caps are not parts of N/A
enclosure.

18.4 Holders for lamps with threaded caps


18.4.1 Resistant to corrosion Lamp holders or lamp caps are not parts of N/A
enclosure.
18.4.2 Contact separation Lamp holders or lamp caps are not parts of N/A
enclosure.
18.4.3 E26/E27 and E39/E40 Lamp holders or lamp caps are not parts of N/A
threaded lampholders enclosure.

19 Non-metallic enclosures and non-metallic parts of enclosures

19.1 General A bushing is formed by moulding insulation on Pass


the shell body. The insulation material is E44. 3
wires go through the bushing.

TRF No. ExTR60079-1_7A Page 13 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

19.2 Resistance to tracking and No non-metalic material supporting live bare N/A
creepage distances on parts.
internal surfaces of the
enclosure walls

19.3 Requirements for type tests The explosion-proof Power Distribution N/A
Equipment is made by metal.

19.4 Test of erosion by flame The explosion-proof Power Distribution N/A


Equipment is made by metal.

20 MARKING

20.1 General The marking complies with the additional Pass


requirements for flameproof enclosure specified
in IEC 60079-1. For more details, see clause 29
in IEC60079-0 of this report.

20.2 Caution and warning The nameplate has the warning “Warning-after Pass
markings energizing, delay 15 minutes before opening”
and “CAUTION-USE FASTENER W ITH YIELD
2
STRESS≥450N/mm ”.

20.3 Informative markings The thread specification of entry is marked in Pass


the nameplate and the manual.

21 Instructions Refer to clause 30.1 of report IEC 60079-0 and Pass


clause 5.1 of report IEC60079-1.

Annex A Additional requirements for crimped ribbon elements and multiple screen elements of breathing
(Normative) and draining devices
A.1 Crimped ribbon and multiple No crimped ribbon elements or multiple screen N/A
screen elements elements.
A.2 Path dimensions No crimped ribbon elements or multiple screen N/A
elements.
A.3 Annex B requirements No crimped ribbon elements or multiple screen N/A
elements.
A.4 Type tests No crimped ribbon elements or multiple screen N/A
elements.

Annex B Additional requirements for elements, with non-measurable paths, of breathing and draining
(Normative) devices
B.1 Sintered metal elements
B.1.1 Construction Non-measurable paths are not included. N/A

TRF No. ExTR60079-1_7A Page 14 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

B.1.2 Bubble test pore size Non-measurable paths are not included. N/A
B.1.3 Density Non-measurable paths are not included. N/A
B.1.4 Open porosity and/or fluid Non-measurable paths are not included. N/A
permeability
B.1.5 Identification Non-measurable paths are not included. N/A
B.2 Pressed metal wire elements
B.2.1 Construction Non-measurable paths are not included. N/A
B.2.2 Specifications Non-measurable paths are not included. N/A
B.2.3 Bubble test pore size Non-measurable paths are not included. N/A
B.2.4 Density Non-measurable paths are not included. N/A
B.2.5 Open porosity and or fluid Non-measurable paths are not included. N/A
permeability
B.2.6 Identification Non-measurable paths are not included. N/A
B.3 Metal foam elements
B.3.1 Construction Non-measurable paths are not included. N/A
B.3.2 Chromium content Non-measurable paths are not included. N/A
B.3.3 Bubble test pore size Non-measurable paths are not included. N/A
B.3.4 Density Non-measurable paths are not included. N/A
B.3.5 Open porosity and/or fluid Non-measurable paths are not included. N/A
permeability
B.3.6 Identification Non-measurable paths are not included. N/A

Annex C Additional requirements for flameproof entry devices


(Normative)
C.1 General The bushing is formed by moulding insulation Pass
on the shell body. 3 wires go through the
bushing.
C.2 Constructional requirements
C.2.1 Sealing methods
C.2.1.1 Cable glands with elastomeric sealing rings
C.2.1.1.1 Minimum uncompressed No cable gland. N/A
axial height
C.2.1.1.2 Cable glands with only one No cable gland N/A
specific elastomeric sealing
ring
C.2.1.2 Cable glands sea with No cable gland N/A
setting compound
C.2.1.3 Conduit sealing devices with No cable gland N/A
setting compound

TRF No. ExTR60079-1_7A Page 15 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

C.2.1.4 Bushings Wires between light source compartment and Pass


power compartment are sea by
compound (E44). For the length of the
compound refer to clause 6.3.
Thermal endurance tests were carried out on
the sample.
For test pressure of static pressure test, refer to
15.1.3.1.
C.2.2 Flameproof joints Reference only Pass
C.2.2.1 Threaded joints Position: two thread entries for cable gland(no Pass
plug)
Thread specification: M25
Thread pitbh: 1.5mm
Length of thread: 25mm
Number of full thread: 16
Metric thread complies with the requirements of
6g/6H fit tolerance and fulfils the requirements
of medium tolerance in ISO965-1 and ISO965-
3.
C.2.2.2 Non-threaded joints (Group I Group II. N/A
only)
C.2.3 Constructional requirements for Ex blanking elements
C.2.3.1 General requirements No Ex blanking elements. The unused holes N/A
should be closed by the Ex blanking elements
suitably certified by users.
C.2.3.2 Metric Ex blanking elements No Ex blanking elements. The unused holes N/A
should be closed by the Ex blanking elements
suitably certified by users.
C.2.3.3 NPT Ex blanking elements No Ex blanking elements. The unused holes N/A
should be closed by the Ex blanking elements
suitably certified by users.
C.2.3.4 Non-threaded Ex blanking No Ex blanking elements. The unused holes N/A
elements (Group I only) should be closed by the Ex blanking elements
suitably certified by users.
C.2.4 Constructional requirements for Ex thread adapters
C.2.4.1 Compliance of threads No Ex thread adapters. N/A
C.2.4.2 Threads co-axial No Ex thread adapters. N/A
C.2.4.3 Length and internal volume No Ex thread adapters. N/A
C.3 Type tests
C.3.1 Sealing test
C.3.1.1 General No cable glands. N/A
C.3.1.2 Cable glands and conduit No cable glands. N/A
sealing devices with sealing
ring
C.3.1.3 Cable glands sea with No cable glands. N/A
setting compound
C.3.1.4 Conduit sealing devices sea No cable glands. N/A
with setting compound

TRF No. ExTR60079-1_7A Page 16 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

C.3.2 Test of mechanical strength


C.3.2.1 Cable glands with a threaded No cable glands. N/A
compression element
C.3.2.2 Cable glands with a No cable glands. N/A
compression element fixed
by screws
C3.2.3 Cable glands sea with No cable glands. N/A
setting compound
C3.2.4 Acceptance criteria No cable glands. N/A
C.3.3 Type tests for Ex blanking elements
C.3.3.1 Torque test No Ex blanking elements. The unused holes N/A
should be closed by the Ex blanking elements
suitably certified by users.
C.3.3.2 Over-pressure test No Ex blanking elements. The unused holes N/A
should be closed by the Ex blanking elements
suitably certified by users.
C.3.4 Type tests for Ex thread adapters
C.3.4.1 Torque test No Ex thread adapters. N/A
C.3.4.2 Impact test No Ex thread adapters. N/A
C.3.4.3 Over-pressure test No Ex thread adapters. N/A

Annex D Empty flameproof enclosures as ex components


(Normative)
D.1 General Not an empty flameproof enclosure. N/A
D.2 Introductory remarks Not an empty flameproof enclosure. N/A
D.3 Ex component enclosure requirements
D.3.1 Compliance with IEC 60079- Not an empty flameproof enclosure. N/A
0 & 60079-1
D.3.2 Geometry of enclosure Not an empty flameproof enclosure. N/A
D.3.3 Rotating machines Not an empty flameproof enclosure. N/A
D.3.4 Means of mounting Not an empty flameproof enclosure. N/A
D.3.5 Dril holes Not an empty flameproof enclosure. N/A
D.3.6 Reference pressure Not an empty flameproof enclosure. N/A
D.3.7 Overpressure Not an empty flameproof enclosure. N/A
D.3.8 Marking internally Not an empty flameproof enclosure. N/A
D.3.9 External marking provision Not an empty flameproof enclosure. N/A
D.3.10 Information in certificate Not an empty flameproof enclosure. N/A
D.4 Utilization of an Ex component enclosure certificate to prepare an equipment certificate
D.4.1 Procedure Not an empty flameproof enclosure. N/A
D.4.2 Application of the schedule of Not an empty flameproof enclosure. N/A
limitations

TRF No. ExTR60079-1_7A Page 17 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

Annex E Cells and batteries used in flameproof “d” enclosures


(Normative)
E.1 Introductory remarks No cells or batteries. N/A
E.2 Acceptable electrochemical No cells or batteries. N/A
systems
E.3 General requirements for cells (or batteries) inside flameproof enclosures
E.3.1 Restrictions No cells or batteries. N/A
E.3.2 Warning label No cells or batteries. N/A
E.3.3 Mounting No cells or batteries. N/A
E.3.4 Relative movement No cells or batteries. N/A
E.3.5 Verification before and after No cells or batteries. N/A
the tests of enclosures
E.4 Arrangement of safety devices
E.4.1 Prevention of excessive temperature and cell damage
E.4.1.1 Short circuit condition No cells or batteries. N/A
E.4.1.2 Infallible components No cells or batteries. N/A
E.4.2 Prevention of cell polarity reversal or reverse charging by another cell in the same battery
E.4.2.1 Additional protection No cells or batteries. N/A
E.4.2.2 Protection against polarity No cells or batteries. N/A
reversal or revere charging
E.4.3 Prevention of inadvertent No cells or batteries. N/A
charging of a battery by other
voltage sources in the
enclosure
E.5 Recharging of secondary cells inside flameproof enclosures
E.5.1 Allowable cell type No cells or batteries. N/A
E.5.2 Charging condition and No cells or batteries. N/A
safety devices
E.5.3 Reverse charging No cells or batteries. N/A
E.5.4 Additional safety device(s) No cells or batteries. N/A
E.5.5 Recharging within enclosure No cells or batteries. N/A
E.6 Rating of protection diodes and reliability of protection devices
E.6.1 Voltage rating & compliance No cells or batteries. N/A
with E.4.2
E.6.2 Voltage rating & compliance No cells or batteries. N/A
with E.4.3
E.6.3 Current rating No cells or batteries. N/A
E.6.4 Safety integrity No cells or batteries. N/A

Annex F Mechanical properties for screws and nuts


(Informative)

TRF No. ExTR60079-1_7A Page 18 of 19


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-1
Clause Requirement – Test Result – Remark Verdict

Annex G Additional requirements for flameproof enclosures with an internal source of release
(Normative) (containment system)
G.1 General No internal source of release. N/A
G.2 Release conditions
G.2.1 No release No internal source of release. N/A
G.2.2 Limited release of a gas or No internal source of release. N/A
vapour
G.2.3 Limited release of a liquid No internal source of release. N/A
G.3 Design requirements for the containment system
G.3.1 General design requirements No internal source of release. N/A
G.3.2 Infallible containment system No internal source of release. N/A
G.3.3 Containment system with a No internal source of release. N/A
limited release
G.4 Type tests for the containment system
G.4.1 Overpressure test No internal source of release. N/A
G.4.2 Leakage test for an infallible No internal source of release. N/A
containment system
G.4.3 Leakage test for a No internal source of release. N/A
containment system with a
limited release

Annex H Requirements for machines with flameproof “d” enclosures fed from converters
(Normative)
H.1 General Not fed from converters. N/A
H.2 Construction requirements for Not fed from converters. N/A
bearings
H.3 Temperature requirements Not fed from converters. N/A

Measurement Section, including Additional Narrative Remarks (as deemed applicable)


N/A

TRF No. ExTR60079-1_7A Page 19 of 19


Ex TEST REPORT
EN 60079-7
Electrical equipment for explosive gas atmospheres
Part 7: Increased safety “e”

ExTR Reference Number...............:


ExTR Free Reference Number ......: PRD-2019-SU82
Complied by + signature ....: Gavin Li ...................................................
Reviewed by + signature....: Konstantin Zhao ...................................................
Date of issue ..................................: 2019-11-04
Ex Testing Laboratory ........: Ente Certificazione Macchine

Address ..........................................: Via Cà Bella, 243 - 40050- Italia

Applicant’s name............................: ErGong Explosion Protection Technology Co., Ltd.


Address ..........................................: No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province

Standard.........................................: EN 60079-7:2015
Test procedure ...............................: EXTR
Test Report Form No. ....................: ExTR60079-7_4A
TRF Originator................................: EN60079-7:2015
Master TRF ....................................: dated2015- 08
Instructions for Intended Use of Ex Test Report:
This ExTR blank document is to be compiled and reviewed by the ExTL. The ExTR package in which this
ExTR is incorporated (comprised of a single ExTR document or multiple ExTR documents) is to be
accompanied by a single ExTR Cover Sheet, which is to be approved by the ExCB. ExTR Addendum(s)
and/or ExTR Report of National Differences may also supplement this ExTR.
Copyright © 2006 International Electrotechnical Commission Scheme for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx), Geneva, Switzerland. All rights
reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx is acknowledged as copyright owner and source of the material. IECEx takes no responsibility for
and will not assume liability for damages resulting from the reader's interpretation of the reproduced
material due to its placement and context.
Possible test case verdicts:
- test case does not apply to the test object ..................:N / A NA
- test object does meet the requirement ........................:Pass P
General remarks:
The tests results presented in this report relate only to the object tested.
This report shall not be reproduced except in full without the written approval of the testing laboratory.

"(see Attachment #)" refers to additional information appended to the report.


"(see appended table)" refers to a table appended to the report.

Throughout this report a point is used as the decimal separator.

TRF No.: ExTR60079-7_4A


Page 2 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict

1 SCOPE

2 NORMATIVE REFERENCES

3 TERMS AND DEFINITIONS

4 CONSTRUCTIONAL REQUIREMENTS FOR ALL ELECTRICAL APPARATUS

4.1 General — P

4.2 Electrical connections


4.2.1 General See drawing No. : EG5573 063.1~ P
6(2P/3P assembly of plug core), WM5HR 573
066.1~3(4P plug assembly), WM5HR 573
053.1~2(5P assembly of plug core), WM5HR
906 005(screw assembly).
The wiring platen and M4×10 screw for
pressure inside the plug, pressure connection.
The tightening moment is 3.2N.m.

See drawing No. : WM5HR 573 062.1~


6(2P/3P assembly of socket core), WM5HR 513
022.1~3(2/3P assembly of conducting rod),
WM5HR 573 064.1~3(4P socket assembly),
WM5HR 513 015.1~2 (4/5P assembly of
conducting rod), WM5HR 573 054(5P socket
assembly).
The wiring and conducting rod are mechanically
pressed together inside the socket.

See drawing No. : WM5HR 552 231(2P/3P


control switch), WM5HR 573 065(4P assembly
of socket core), WM5HR 573 055(5P assembly
of socket core), WM5HR 906 005(screw
assembly).
Control switch inside socket with the wiring
platen and M4×10 screw for pressure
connection. The tightening moment is 3.2N.m.
4.2.2 Field wiring connections

TRF No.: ExTR60079-7_4A


Page 3 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.2.2.1 General See drawing No. WM5HR 573 063.1~6(2P/3P P
assembly of plug core), WM5HR 573 066.1~
3(4P plug assembly), WM5HR 573 053.1~2(5P
assembly of plug core), WM5HR 906 005(screw
assembly);
WM5HR 552 231(2P/3P control switch),
WM5HR 573 065(4P assembly of socket core),
WM5HR 573 055(5P assembly of socket core),
WM5HR 906 005(screw assembly);
The connecting leads cross section are not
more than 2.5mm2.
The number and size of conductors that can be
safely connected have been specified in the
Operational Instruction.
4.2.2.2 Connections made using Terminals comply with IEC60947-7-1. P
terminals complying with IEC Test of terminals, see clause 6.9 of IEC60079-
60947-7-1, IEC 60947-7-2, IEC
7:2006 and clause 26.5.1 of IEC60079-0:2007.
60999-1, or IEC 60999-2
4.2.2.3 Field wiring connection facilities See IEC60079-7:2006 clause 4.2.2.2. P
integral to “e” apparatus or
components
4.2.2.4 Connections designed to be — NA
used with cable lugs and similar
devices
4.2.2.5 Connections using permanent — NA
arrangements
4.2.3 Factory connections
4.2.3.1 General — P
4.2.3.2 Field wiring connection methods — P
used for factory connections
4.2.3.3 Permanent connections See drawing No. : WM5HR 573 062.1~ P
6(2P/3P assembly of socket core), WM5HR 513
022.1~3(2/3P assembly of conducting rod),
WM5HR 573 064.1~3(4P socket assembly),
WM5HR 513 015.1~2 (4/5P assembly of
conducting rod), WM5HR 573 054(5P socket
assembly).
The wiring and conducting rod are mechanically
pressed together inside the socket.
4.2.3.4 Pluggable connections No pluggable connections NA
4.2.3.5 Terminal bridging connections — NA

4.3 Clearances (see appended table 4.3) P

4.4 Creepage distances


4.4.1 Required values of creepage (see appended table 4.4) P
distance

TRF No.: ExTR60079-7_4A


Page 4 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.4.2 Creepage distances between (see appended table 4.4) P
bare conductive parts at different PA66: CTI=500, see annex 22
potentials
PBT: CTI= 500, see annex 20
DMC-2: CTI= 500, see annex 26
E44: CTI= 475, see annex 28
4.4.3 Effects of ribs and grooves (see appended table 4.4) P
PA66: CTI=500, see annex 22
PBT: CTI= 500, see annex 20
DMC-2: CTI= 500, see annex 26
E44: CTI= 475, see annex 28

4.5 Solid electrical insulating materials


4.5.1 Clarification of the term solid — P
electrical insulating materials
4.5.2 Mechanical characteristics The insulating materials of plug is made of PBT P
Polybutylece Terephthalate (blue, yellow,
purple, white, black, red).
The insulating materials of socket is made of
PA66 polyamide (blue, yellow, purple, white,
black, red).
The insulating materials of 2P/3P control switch
is made of PBT Polybutylece Terephthalate
(white).
The insulating materials of 4P/5P control switch
is made of DMC-2 Bulk molding
compounds(white) and E-44 epoxy resin.

PBT Polybutylece Terephthalate (blue, yellow,


purple, white, black, red): RTI: 112°C, see
annex 11.
PA66 polyamide (blue, yellow, purple, white,
black, red): RTI: 125°C, see annex 7.
DMC-2 Bulk molding compounds(white): RTI:
125°C, see annex 14.
E-44 epoxy resin COT: -60~+180℃, see annex
6.
4.5.3 Insulating parts made of plastics — NA
or laminates

4.6 Windings
4.6.1 Insulated conductors to comply — NA
with either 4.6.1.1 or 4.6.1.2
4.6.1.1 Two layers of insulation — NA
4.6.1.2 Enamelled round winding wires — NA
4.6.2 Windings following fastening and — NA
wrapping

TRF No.: ExTR60079-7_4A


Page 5 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.6.3 Minimum nominal conductor — NA
dimension
4.6.4 Sensing elements of RTDs — NA

4.7 Temperature limitations


4.7.1 General Maximum surface temperature : lower than 80 P
℃(T6);
See clause 26.5 of IEC60079-0
4.7.2 Conductors — P
4.7.3 Insulated windings — NA
4.7.4 Winding Protection — NA

4.8 Wiring internal to apparatus — P

4.9 Degrees of protection provided by enclosures


4.9.1 Minimum degree of protection IP65 P
4.9.2 Accumulation of condensation — NA
within enclosure
4.9.3 Covers of enclosures containing — NA
non-intrinsically-safe items shall
be adequately labelled

4.10 Fasteners — NA

5 SUPPLEMENTARY REQUIREMENTS FOR SPECIFIC ELECTRICAL


APPARATUS

5.1 General — NA

5.2 Rotating electrical machines


5.2.1 Degrees of protection provided — NA
by machine enclosures
5.2.2 Internal fans — NA
5.2.3 Minimum radial air gap — NA
5.2.4 Machines with cage rotors
5.2.4.1 Requirements for machines with — NA
caged rotors
5.2.4.2 Requirements for the bars of — NA
caged rotors
5.2.4.3 Rotor construction and air gap — NA
sparking
5.2.4.4 Limiting temperature of the rotor — NA

TRF No.: ExTR60079-7_4A


Page 6 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.2.4.4.1 Starting current ratio IA/IN shall — NA
be determined and marked
5.2.4.4.2 Winding temperature sensors — NA
associated with protective
devices
5.2.4.5 Converter-fed motors — NA
5.2.4.6 Information on thermal — NA
protection
5.2.5 Winding requirements — NA
5.2.6 Stator winding terminals — NA
5.2.7 Stator winding insulation system — NA
5.2.8 Bearing seals and shaft seals
5.2.8.1 Non-rubbing seals and labyrinths — NA
5.2.8.2 Rubbing seals — NA

5.3 Luminaires No such design construction NA


5.3.1 Light source — NA
5.3.2 Minimum distance between lamp — NA
and protective cover
5.3.3 Lampholders and lamp caps
5.3.3.1 Screw lampholders and lamp — NA
caps
5.3.3.2 Other lampholders and lamp — NA
caps
5.3.3.3 Requirements for electrical — NA
contact between the lampholder
and lamp cap
5.3.4 Surface temperature of lamps — NA
5.3.5 Temperature of lamp caps — NA
5.3.6 Limiting temperatures — NA
5.3.7 Luminaires for tubular fluorescent bi-pin lamps
5.3.7.1 General — NA
5.3.7.2 Maximum ambient temperature — NA
5.3.7.3 Temperature class — NA
5.3.7.4 Lampholders for bi-pin lamps — NA
5.3.7.5 Enhanced voltage used to — NA
initiate discharge within the lamp
5.3.7.6 Maximum values for torque and — NA
/or force at each end of the lamp
5.3.7.7 Reliability under corrosion and — NA
vibration conditions

TRF No.: ExTR60079-7_4A


Page 7 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.3.7.8 Where provided, isolation switch — NA
shall de-energize each
lampholder when the protective
cover is removed

5.4 Caplights and handlights Contain no caplights and handlights NA

5.5 Measuring instruments and instrument transformers


5.5.1 Measuring instruments and — NA
instrument transformers and
limiting temperatures according
to Clause 4.7
5.5.2 Current transformers and current — NA
carrying parts of measuring
instruments shall be able to
withstand thermal and dynamic
stresses
5.5.3 Temperature attained during the — NA
passage of a current
5.5.4 Measuring instruments supplied — NA
by current transformers
5.5.5 Measuring instruments with — NA
moving coils not permitted
5.5.6 Guarding against secondary — NA
circuit becoming open circuited
in service and marking with an
"X"

5.6 Transformers other than — NA


instrument transformers

5.7 Batteries
5.7.1 Secondary batteries with capacity greater than 25 Ah
5.7.1.1 General — NA
5.7.1.2 Battery containers — NA
5.7.1.3 Cells — NA
5.7.1.4 Connections — NA
5.7.2 Primary and secondary batteries — NA
with capacity up to 25 Ah
5.7.3 Release of flammable gas — NA
5.7.4 Charging of cells — NA
5.7.5 Discharge of cells — NA
5.7.6 Incorporation of other types of — NA
protection
5.7.7 Disconnection and transportation — NA

TRF No.: ExTR60079-7_4A


Page 8 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.8 General purpose connection and — NA
junction boxes

5.9 Resistance heaters (other than trace heaters)


5.9.1 Supplementary requirements for — NA
the resistance heating devices
and resistance heating units
5.9.2 Application of 4.6 and Clause 7 — NA
of IEC 60079-0
5.9.3 Temperature coefficient of — NA
heating resistors
5.9.4 Testing of insulating materials — NA
used in a resistance heating
device
5.9.5 Cold start current of the — NA
resistance heating device
5.9.6 The manufacturer shall specify — NA
an electrical protective device for
use with each resistance heating
device or unit.
5.9.7 Requirements for electrically — NA
conductive covering
5.9.8 Electrical insulation of the — NA
heating resistors
5.9.9 Cross-section of the conductors — NA
for connections to the resistance
heating device
5.9.10 Determination of the — NA
temperature class of a
resistance heating device
5.9.11 Prevention from exceeding the — NA
limiting temperature of
resistance heating device or unit
5.9.12 Protection offered by a safety — NA
device
5.9.13 Requirements for resistance — NA
heating devices and units

5.10 Other electrical apparatus — NA

6 TYPE VERIFICATIONS AND TYPE TESTS

6.1 Dielectric strength (see appended table 6.1) P

6.2 Rotating electrical machines


6.2.1 Machines with cage rotors — NA

TRF No.: ExTR60079-7_4A


Page 9 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.2.2 Test conditions required for — NA
rotating electrical machines
6.2.3 Additional tests for machines
6.2.3.1 Stator winding insulation system
6.2.3.1.1 Test required for motor — NA
components
6.2.3.1.2 Arrangements for stator — NA
connection cables
6.2.3.1.3 Insulation systems and — NA
connection cables
6.2.3.1.4 Insulation systems and — NA
connecting cables - Impulse test
6.2.3.2 Cage rotor construction
6.2.3.2.1 Tests to be carried out using a — NA
machine representative of a
finished machine
6.2.3.2.2 Ageing process of rotor cage — NA
6.2.3.2.3 Motors to be subjected to 10 — NA
direct-on-line uncoupled starts or
10 locked rotor tests
6.2.3.2.4 Maintenance of terminal voltage — NA
and hydrogen concentration

6.3 Luminaires designed for mains supply


6.3.1 Mechanical tests for screw — NA
lampholders other than E10
6.3.2 Abnormal operation of luminaires with tubular fluorescent lamps
6.3.2.1 Rectification test — NA
6.3.2.2 Inoperative lamp test — NA
6.3.2.3 Power dissipation of cathodes of — NA
lamps supplied by electronic
ballasts
6.3.3 Sulphur dioxide test for the — NA
connection of bi-pin lamp caps to
lampholders
6.3.4 Vibration test for luminaires with — NA
bi-pin lamps

6.4 Measuring instruments and — NA


instrument transformers

6.5 Transformers other than — NA


instrument transformers

6.6 Secondary batteries


6.6.1 Application of tests — NA

TRF No.: ExTR60079-7_4A


Page 10 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.6.2 Insulation resistance
6.6.2.1 Test conditions — NA
6.6.2.2 Insulation resistance — NA
6.6.3 Shock test
6.6.3.1 General — NA
6.6.3.2 Test conditions — NA
6.6.3.3 Test procedure — NA
6.6.3.4 Acceptance criteria — NA
6.6.4 Test for ventilation of battery container
6.6.4.1 Determination of the maximum — NA
hydrogen concentration within
the battery container
6.6.4.2 Determination of hydrogen flow — NA
rate
6.6.4.3 Test Method — NA
6.6.4.4 Test Procedure — NA
6.6.4.5 The test to be carried out at least — NA
twice
6.6.4.6 Hydrogen concentration not to — NA
exceed 2 %

6.7 General purpose connection and — NA


junction boxes

6.8 Resistance heating devices and resistance heating units


6.8.1 Type tests and additional — NA
requirements of 5.9
6.8.2 The tests carried out on a — NA
sample or prototype
6.8.3 Verification of the electrical — NA
insulation of the sample or
prototype
6.8.4 Thermal stability of the insulating — NA
materials of the resistance
heating device
6.8.5 The test for resistance to impact — NA
shall be carried out on two new
samples or prototypes with an
apparatus similar to that shown
in IEC 60079-0.
6.8.6 Test for cold start current — NA
6.8.7 Tests for specific forms of — NA
resistance heating devices or
units

TRF No.: ExTR60079-7_4A


Page 11 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.9 Terminal insulating material tests After the thermal endurance test of the terminal, P
a pulling force test to the conductor which size
is 2.5mm2, the pull is 50N, the conductor shall
not separate from clamp device, the terminal
assembly shall not separate from the terminal
insulator.

7 ROUTINE VERIFICATIONS AND ROUTINE TESTS


7.1 Dielectric tests See the manufacturer’s document, annex 2, P
Technical conditions of power-frequency
withstand voltage test, DOC. No. 0HR 599 010.
7.2 Dielectric tests for batteries — NA
7.3 Inter-turn overvoltage test — NA

8 EX COMPONENT CERTIFICATES
8.1 General — NA
8.2 Terminals — NA

9 MARKING AND INSTRUCTIONS


9.1 General Marking
Rated voltage(s) or voltage See nameplate drawings: WM8HR 860 894, P
range(s) (V)................................: WM8HR 860 913, WM8HR 860 912, WM8HR
860 884, WM8HR 860 924, WM8HR 860 923.
Rated voltage: 24VDC, 36VDC, 110V~130V
AC, 200V~250V AC, 380V~415V AC,
480V~500V AC.
Rated current (mA or A).............: 16A P
Rated power ..............................: — NA
Starting current ratio IA/IN ................. : — NA
Time tE .............................................................: — NA
Short circuit current ISC.......................: — NA
Electrical rating, lamp ................: — NA
Lamp dimensions.......................: — NA
Rated maximum dissipated — NA
power ......................................... :
Permissible number of — NA
conductors ................................. :
Size of conductors .....................: — NA
Maximum current ....................... : — NA
Restrictions in use ..................... : — NA
Characteristics of special — NA
protective devices ......................:
Type of construction of cells ......: — NA

TRF No.: ExTR60079-7_4A


Page 12 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
Number of cells..........................: — NA
Nominal voltage of cells............. : — NA
Rated capacity of cells...............: — NA
Duration of cell discharge .......... : — NA
WARNING - DO NOT CHARGE — NA
IN HAZARDOUS AREA.............:
Conductor range ........................: — NA
Rated voltage............................. : — NA
Operating temperature...............: — NA
9.2 Instructions for use
9.2.1 Battery operated apparatus No such design construction NA
Name of manufacturer or — NA
supplier or registered trademark
Manufacturer's type identification — NA
Number of cells — NA
Nominal voltage of the battery — NA
Rated capacity — NA
Charging instructions — NA
Safe operating conditions — NA
WARNING - REFER TO THE — NA
INSTRUCTION MANUAL FOR
BATTERY CHARGING
9.2.2 Terminals
Assigned torque value(s) See operational instruction P
Indication of rearrangement or — NA
adjustment to adapt to various
sizes of conductors
Instructions for proper conductor See operational instruction P
installation
Conductor insulation stripping See operational instruction P
requirements
9.2.3 Luminaires No such design construction NA
Bi-pin luminaires — NA
Screw-cap lamps — NA
9.2.4 Motors No such design construction NA
Routine maintenance and — NA
lubrication of bearings
Routine testing of insulated rotor — NA
bar insulation
9.3 Warning markings Has a warning marking: DO NOT OPEN WHEN P
ENERGIZED.

TRF No.: ExTR60079-7_4A


Page 13 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
ANNEX A CAGE MOTORS- METHODS OF TEST AND OF CALCULATION
A.1 Temperature rise of the stator — NA
A.2 Temperature rise of the stator — NA
and rotor windings at rated
service
A.3 Determination of temperature — NA
rise in stalled motors
A.3.1 Ambient temperature and — NA
application of rated voltage and
rated frequency
A.3.2 Measurement of stator current — NA
A.3.3 Temperature rises in the rotor — NA
cage
A.3.4 Average temperature rise in the — NA
stator
A.3.5 Stalled motor test — NA
A.4 Calculation of temperature rise — NA
in stalled motors
A.4.1 Calculating the temperature of — NA
the short-circuited rotor
A.4.2 The rate of temperature rise — NA
A.5 Determination of time tE — NA
A.6 Motors designed for arduous — NA
starting conditions
A.7 Motors forming units with — NA
converters and the associated
protective devices

ANNEX B TYPE TESTS FOR SPECIFIC FORMS OF RESISTANCE HEATING DEVICES


OR RESISTANCE HEATING UNITS
B.1 Resistance heating devices — NA
subjected to mechanical
stresses
B.2 Resistance heating devices or — NA
units intended for immersion
B.3 Resistance heating devices or — NA
units having hygroscopic
insulating material
B.4 Verification of limiting — NA
temperature of resistance
heating devices (other than trace
heaters)
B.4.1 Test procedure — NA
B.4.2 Resistance heating unit — NA
protected by a safety device in
accordance to 5.9.12
B.4.2.1 Safety device sensing the — NA
temperature
TRF No.: ExTR60079-7_4A
Page 14 of 16 Report No. PRD-2019-SU82

EN 60079-7
Clause Requirement – Test Result – Remark Verdict
B.4.2.2 Safety device sensing the — NA
temperature and at least one
other protective parameter
B.4.2.3 Safety device sensing a — NA
parameter other than the
temperature
B.4.3 Resistance heating unit of — NA
stabilized design
B.4.4 Heating device with temperature — NA
self-limiting characteristic

ANNEX H TEST PROCEDURE FOR T8, T10 AND T12 LAMPS


H.1 Asymmetric pulse test
H.1.1 General — NA
H.1.2 Test procedure — NA
H.2 Asymmetric power test
H.2.1 General — NA
H.2.2 Test procedure — NA

TRF No.: ExTR60079-7_4A


Page 15 of 16 Report No. PRD-2019-SU82

APPENDIX A: Additional construction remarks

4.3 TABLE: clearance distance measurements

Clearance (cl) between circuit parts: Ur.m.s. a.c. or d.c. Required cl Measured cl
(V) (mm) (mm)
Type BCZ8060–16/250/3P
Control switch terminal 200~250(rated value 250) 5.0 13.0
Plug 200~250(rated value 250) 5.0 14.0
Socket 200~250(rated value 250) 5.0 20.0
Type BCZ8060–16/500/4P
Control switch terminal 480~500(rated value 500) 8.0 19.0
Plug 480~500(rated value 500) 8.0 14.0
Socket 480~500(rated value 500) 8.0 13.0
Type BCZ8060–16/415/5P
Control switch terminal 380~415(rated value 415) 6.0 19.0
Plug 380~415(rated value 415) 6.0 14.0
Socket 380~415(rated value 415) 6.0 13.0

4.4 TABLE: creepage distance measurements

Creepage (dcr) distance between Ur.m.s. a.c. or d.c. Required dcr Measured dcr
circuit parts: (V) (mm) (mm)
Type BCZ8060–16/250/3P
Control switch terminal 200~250(rated value 250) 8.0 13.0
Plug 200~250(rated value 250) 8.0 14.0
Socket 200~250(rated value 250) 8.0 20.0
Type BCZ8060–16/500/4P
Control switch terminal 480~500(rated value 500) 12.5 19.0
Plug 480~500(rated value 500) 12.5 14.0
Socket 480~500(rated value 500) 12.5 13.0
Type BCZ8060–16/415/5P
Control switch terminal 380~415(rated value 415) 10.0 19.0
Plug 380~415(rated value 415) 10.0 14.0
Socket 380~415(rated value 415) 10.0 13.0

TRF No.: ExTR60079-7_4A


Page 16 of 16 Report No. PRD-2019-SU82

APPENDIX B: Additional test remarks

6.1 TABLE: dielectric strength tests


test voltage applied between: test voltage (V) breakdown
a.c. / d.c. Yes / No
Type BCZ8060–16/250/3P: Between phases, phase and earth 1500 No
Type BCZ8060–16/500/4P: Between phases, phase and earth 2000 No
Type BCZ8060–16/415/5P: Between phases, phase and earth 1830 No

supplementary information

4.5 TABLE: maximum temperatures


test voltage (V) : ⎯
tamb1 (°C) : ⎯
tamb2 (°C) : ⎯
maximum temperature T of part/at: T (°C) allowed
Tmax (°C)

temperature T of winding: R1 (Ω) R2 (Ω) T (°C) allowed insulation


Tmax (°C) class

TRF No.: ExTR60079-7_4A


ExTR Reference No.: PRD-2019-SU82.

IECEx TEST REPORT


EN 60079-31
Explosive atmospheres –
Part 31: Equipment dust ignition protection by enclosure “t”

ExTR Reference Number............... :


ExTR Free Reference Number ...... :
Compi by + signature .... : Gavin Li ....................................
Reviewed by + signature .... : Konstantin Zhao
...............................
Approved by + signature ….: Li Tao
..................................
Nov, 4 . 2019
th
Date of issue .................................. :

Ex Testing Laboratory ........ : Ente Certificazione Macchine


Address .......................................... : Via Cà Bella, 243 - 40050- Italia

Applicant’s name ............................ : ErGong Explosion Protection Technology Co., Ltd.


Address .......................................... : No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province

Standard......................................... : EN 60079-31:2014
Test procedure ............................... : EXTR
Test Report Form Number ............. : ExTR60079-31_2A (released 2014-01)
Instructions for Intended Use of Ex Test Report:
An Ex Test Report provides a clause-by-clause documentation of the initial evaluation and testing that
verified compliance of an item or product with an IEC Ex standard. This Ex Test Report is part of an ExTR
package that may include other Ex Test Report, Addendum and National Differences documents, along with a
single ExTR Cover. An Ex Test Report is to be compi and reviewed by the ExTL. The Issuing ExCB
indicates final approval of the Ex Test Report as part of the overall ExTR package on the associated ExTR
Cover.
Copyright © 2014 International Electrotechnical Commission System for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx System), Geneva, Switzerland. All
rights reserved.
This blank publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx System is acknow ged as copyright owner and source of the material. The IECEx system takes no
responsibility for, and will not assume liability for, damages resulting from the reader's interpretation of the
reproduced material due to its placement and context.

Possible test case verdicts:


- test case does not apply to the test item ..................... :N / A
- test item does meet the requirement ........................... :Pass
General remarks:
The test results presented in this Ex Test Report relate only to the item or product tested.
▪ "(see Attachment #)" refers to additional information appended to this document.
▪ "(see appended table)" refers to a table appended to this document.
▪ Throughout this document, a point is used as the decimal separator.
The technical content of this Ex Test Report shall not be reproduced except in full without the written approval
of the Issuing ExCB and ExTL.

TRF No. ExTR60079-31_2A Page 1 of 3


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-31
Clause Requirement – Test Result – Remark Verdict

1 Scope

2 Normative references

3 Terms and definitions

4 General
4.1 Levels of protection tb Pass
Equipment groups and ingress
4.2 IP67 Pass
protection
4.3 Requirements for electrical equipment with level of protection “ta”
4.3.1 Fault current The level of protection of EGKP-T- is “tb”. N/A
4.3.2 Maximum surface temperature The level of protection of EGKP-T- is “tb”. N/A
4.3.3 Overpressure The level of protection of EGKP-T- is “tb”. N/A
4.3.4 Dust exclusion The level of protection of EGKP-T- is “tb”. N/A
4.3.5 Protective devices
4.3.5.1 General The level of protection of EGKP-T- is “tb”. N/A
4.3.5.2 Thermal protective devices The level of protection of EGKP-T- is “tb”. N/A
Protection for arcing and
4.3.6 The level of protection of EGKP-T- is “tb”. N/A
sparking parts
4.4 Requirements for electrical equipment with Level of Protection “tb” and “tb”
4.4.1 Maximum surface temperature See test report IEC60079-0 clause 5.3 Pass
4.4.2 Over pressure See clause 6.1.1.3. Pass
4.4.3 Dust exclusion See clause 6.1.1. Pass

5 CONSTRUCTION
5.1 Joints
5.1.1 General Refer to test report IEC60079-1 clause 5.3. Pass
Threaded entries comply with IEC 60079-31 Pass
5.1.2 Threaded joints
clause 5.3.2.
5.1.3 Gaskets and seals No gaskets. N/A
The width of cemented joint between the glass Pass
5.1.4 Cemented joints plate and shell body of Power Distribution
Equipment is 10mm.
Operating rods, spindles and
5.1.5 No operating rods, spindles and shafts. N/A
shafts
5.1.6 Windows
Windows employing a cemented The glass plate is cemented to the shell body. Pass
5.1.6.1
joint

TRF No. ExTR60079-31_2A Page 2 of 3


ExTR Reference No.: PRD-2019-SU82.

IEC 60079-31
Clause Requirement – Test Result – Remark Verdict
Windows employing a gasket See part IEC 60079-31 clause 5.1.6.1. N/A
5.1.6.2
joint
5.2 Cable glands No cable glands. N/A
5.3 Entries
5.3.1 Plain entries See clause 5.3.2 N/A
Thread specification: M25 Pass
Thread pitbh: 1.5mm
5.3.2 Threaded entries Length of thread: 25mm
Number of full thread: 16
Tolerance class: 6H

6 Verification and tests


6.1 Type tests
6.1.1 Type tests for dust exclusion by enclosures
6.1.1.1 General See part IEC 60079-0 clause 26.4.5. Pass
Impact test for supplementary
6.1.1.2 No supplementary enclosure. N/A
enclosures
The Power Distribution Equipment were Pass
6.1.1.3 Pressure test submitted to gas pressure test. Test pressure:
2kPa. Duration: 61s, No damage to enclosure
has been found.
6.1.1.4 IP test IP66 or IP67 Pass
6.1.2 Thermal tests See part IEC 60079-0 clause 26.5.1.3. Pass
6.2 Routine tests

7 Marking See the cover of the report. Pass

Measurement Section, including Additional Narrative Remarks (as deemed applicable)


N/A