VFD and Motor Details

VFD PARAMETER

Project : Media Zone Development - Plot C41


Name of Panel : CP-SPF-L5-01
Feeder Name : E-SMDB-L4-M1

VFD MODEL NO :ACH580-01-018A-4

LIST OF PARAMETERS
ACTUAL
CODE DISCRIPTION SET-RANGE REMARKS
SETTINGS
99.07 MOTOR NOM VOLT 380 - 415V 400V
99.06 MOTOR NOM CURRENT 0.4In to 1In 10.5 Amps
99.08 MOTOR NOM FREQUENCY 50 to 60HZ 50 HZ
99.09 MOTOR NOM SPEED 1450 to 1500 1460
99.10 MOTOR NOM POWER 7.5KW 5.5KW
19.11 EXT-1/EXT2 SELECTION Various EXT1
20.01 EXT-1 COMMANDS Various DI1
20.06 Ext2 commands Not Selected Not Selected
20.07 Ext2 start trigger type NA NA
20.08 Ext2 in 1 Source Various DI1
20.40 Emergency stop source Various DI1
21.19 Scalar start mode Yes Automatic
22.11 Ext1 speed ref1 Analog Input - 1 & 2 AI-1
22.18 Ext2 speed ref1 Various 0
22.22 Constant speed sel1 Various DI2
23.11 Ramp set selection Various Acc / Dcc Time-1
23.12 Acceleration time 1 0-30 Sec 20 Sec
23.13 Deceleration 2 0-30 Sec 20 Sec
28.11 Ext1 frequency ref1 AI - 0-10V, 0-40mA 0-10V
28.15 Ext2 frequency ref1 AI - 0-10V, 0-40mA NA
30.11 Minimum speed 0-1500 0
30.12 Maximum speed 0-1500 1460
30.13 Minimum Frequency 0-50HZ 0 HZ
30.14 Maximum Frequency 0-50HZ 50 HZ

Tested By Panel manufacturer WITNESSED BY BILT WITNESSED BY AECOM

Name

Signature

Date