Cold Test Report 4

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

COMMISSIONING RECORD SHEET : MAIN/SUB MAIN/FINAL DISTRIBUTION BOARD

Project MEDIA ZONE DEVELOPMENT, ABU DHABI


Panel Reference N-DB-B2-LP4

Panel Location B2-T2-ELE.ROOM Sheet 1 of 1 Rev. 0

PANEL DETAILS INCOMING CABLE IR TEST (MΩ)


REMARKS
Supply cable size : 4C 10 SQMM Source : N-SMDB-B1-LP2 Earth : 1C 10 SQMM CPC : R-Y R-B Y-B R-N Y-N B-N R-E Y-E B-E N-E
Protective device type: Rating : Setting : >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
CIRCUIT DETAILS COLD TEST
Circui Circuit continuity
Breaker No of Cable ECC RCB Ring Insulation resistance (MΩ)
t designation
No. Amps Type (kA) cores (mm2) (mm2) Rating () R-Y R-B Y-B R-N Y-N B-N R-E Y-E B-E N-E ()

1 N-DB-B2-LP4 CP/EAF-B2-03 20 MCCB 35 2x1C 4.0 4.0 >1000 >1000 >1000 OK

2 N-DB-B2-LP4 CP/MAF-B2-03 20 MCCB 35 2x1C 4.0 4.0 >1000 >1000 >1000 OK

3 CP/EAF-B2-03 ISOL EAF-B2-03 20 MCCB 35 2x1C 4.0 4.0 >1000 >1000 >1000 OK

4 CP/MAF-B2-03 ISOL MAF-B2-03 20 MCCB 35 2x1C 4.0 4.0 >1000 >1000 >1000 OK

*Test all phases and record the MOST Cold Tested by : RAJAMALLU Date : 04.08.2021
Date:04.08.2021 Test instrument serial no : HIOKI-21-15523-01
Company: BILT ACC AECOM
Name: VENKITESH P G
Signature:
Date: