Professional Documents
Culture Documents
Lifespan of Batteries in UPS Systems Whitepaper
Lifespan of Batteries in UPS Systems Whitepaper
Lifespan of Batteries in UPS Systems Whitepaper
For a UPS, battery failure is as serious – and In fact, this means that a 10-year design life
unwanted – as any mains power outage. Batteries battery will last for 10 years – assuming perfect
represent a significant share of the total cost of a operating conditions – but its performance will
UPS too. Good upkeep is essential. significantly reduce over time to a degree where
it isn’t safe to use in a UPS system.
Ignoring maintenance and/or service
recommendations and letting the battery system Of course, no installation is ever perfect – this
fall into a poor state increases the risk to both the would be technically impractical, not to mention
critical load and business continuity. cost-prohibitive. Actual battery service life
depends on several factors, including operational
Although alternatives such as lithium-ion are and storage temperatures, discharge levels, and
becoming more popular and commercially viable, how many times they are called into action.
the majority of UPS today still use traditional
sealed lead-acid batteries.
Excluding these external influences, the
These cells have low energy-to-weight and operational capacity of a 10-year design life
energy-to-volume ratios – they are big and battery will drop below the required 100%
heavy – but they do provide high surge currents: capacity at year 6 (Figure 1). Over the remaining 4
therefore, they are ideal to provide backup time years, the capacity will reduce to 80%, while the
during a mains failure or while the generator autonomy of the UPS will reduce too.
starts.
1 of 6
www.rielloupsamerica.com No. 02-2020
This helps explain why it’s become accepted best service life will reduce by 50% for every 10°F
practice to replace 10-year design life batteries in constant increase above the recommended
years 7 or 8. temperature.
This takes into account all the external factors Short-term fluctuations in temperature have little
that can reduce battery life and provides a safe effect on battery life.
enough margin for potential failure, without
compromising the protected load. Adjusting the float voltage depending on the
temperature can reduce the effect of higher
Comparable drop-offs in performance over time temperatures, but only marginally.
are also seen in 5-year design life batteries,
which are typically replaced in either year 3 or 4. Figure 3 below shows the typical effects of the
ambient temperature on the life expectancy of
3. Premature battery failure - The the battery.
Standby/Float Charge Service Life
bathtub curve 100%
2 of 6
www.rielloupsamerica.com No. 02-2020
3 of 6
www.rielloupsamerica.com No. 02-2020
Dry out
Making a VRLA battery Also known as water loss, this is caused when
Valve Regulated Lead-Acid (VRLA) batteries – also overcharging increases the concentration of acid
in the electrolyte. As the battery gases, it loses
known as Sealed Lead-Acid (SLA) or Maintenance-
water, which will lead to a decline in capacity
Free – are the most commonly used in UPS over time. Dry out will eventually cause separator
installations. failure.
A VRLA battery is made up of cells consisting of A knock-on effect of dry out is an increase in self-
lead alloy plates immersed in an electrolyte of discharge and sulphation rates.
dilute sulphuric acid. This liquid (or gel) fills the
space between the positive and negative plates, Thermal runaway
forming a closed circuit of cells. The chemical A condition accelerated by an increase in battery
reaction creates DC current, which can be stored temperature which, in turn, releases energy that
causes a further rise in temperature.
for later discharge.
In essence, when the temperature inside the
VRLA batteries incorporate a valve that opens and battery is so high that it cannot escape through
relieves the pressure if an excess of hydrogen gas the safety vents of sealed cells. This causes an
builds up inside the block. increase in temperature around the exterior
of the battery, which consequently raises the
temperature within the battery again.
VRLA battery cases tend to be manufactured from
flame retardant polypropylene or Acrylonitrile
Butadiene Styrene (ABS) plastic. Ultimately, thermal runaway can result in case
meltdown and expose the battery grid.
the battery doesn’t recover, replace and remove it. premature failure.
4 of 6
www.rielloupsamerica.com No. 02-2020
This strategy should start with a proper performance over time, making it easier to
monitoring regime that detects any issues early identify any signs of weakness or deterioration.
enough to enable swift replacement, so they
aren’t allowed to develop into a full-scale failure. An AC current is applied to each battery via
probes attached to the block terminals, with the
It is essential to monitor batteries at the impedance measured and recorded in milliohms.
individual cell level annually. This gives a broad indication of the general
condition without placing any undue stress on the
Physical tests should cover the inspection of batteries or requiring them to be taken offline.
terminals and connections for corrosion and
checking batteries for any cracks, leaks, or Discharge testing (also known as load bank
swelling. Engineers should also tighten inter-cell testing) is the only examination that will truly
connections, where necessary, clean the batteries, determine the actual capacity of the battery
and remove any debris. string. It tests the batteries under normal and
peak load conditions, showing which cells
As well as these basic manual checks, dedicated are holding the charge and which might be
battery monitoring systems can offer more approaching their end of working life.
advanced support. Ensure the monitoring system
covers all the parameters recommended by IEEE best practice recommends performing this at
the globally-recognised IEEE 1491 standard, the time of installation, then ideally repeating the
including: test every year. The main drawback with discharge
testing is that the batteries must be taken out
• String and cell float voltages of service. The worst-case scenario is that this
• String and cell charge/discharge voltages can last for several days, although usually the
• AC ripple voltage batteries are available within 24 hours.
• AC ripple current
• String charge current As the name implies, partial discharge testing
• String discharge current offers something of a middle-ground. This
• Ambient and cell temperatures involves discharging the batteries by up to 80%.
• Cell internal resistance This reduces their availability, but they should
• Cycles be available again within 8 hours. If there’s an
emergency and the UPS needs to operate off
batteries it can do so, although they will only
Along with robust maintenance and monitoring, have 20% of their full capacity.
several tests can determine whether a battery is
approaching the end of its life. Maintaining optimum operating temperatures and
conditions
Many modern UPS will test their batteries The alternative is to house the batteries in
regularly, usually every 24 hours, and will alarm a dedicated, air-conditioned and humidity-
if there are any faults. The test places a load controlled battery room which is kept at the
onto the battery set and monitors the discharge. optimum temperature, while the UPS (and other IT
However, this only provides a general indication equipment) are installed in a separate space.
of the overall battery set, not the individual cells.
Don’t pack battery blocks too tightly together –
Impedance testing is a non-intrusive way of leave sufficient room for case expansion and heat
building up a ‘history’ of every battery cell. dissipation. This is particularly important to avoid
It should be undertaken annually to track thermal runaway if a block goes to open circuit.
5 of 6
www.rielloupsamerica.com No. 02-2020
6 of 6