LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 7

Maximum
Overall size of No of Actual Weight of Panel weight Load
Actual panel (L panel units panel as per for critical Distribution per
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT x W)in m in Nos Vendor input slab sqm area Remarks

Weight of existing LV
panel not available,
6 x 750 = 4500 / (4 x
Hence Existing Slab
LV (415V) ACTUAL PANEL 4500Kg 1.200) =
SS-07 Switch board DATA
9.640 x 1.200 12 750 Kgs
(Refer Page 937.5Kg/m2
strcutural adequacy is
verified for the panel
No 11) =9.2kN/m2
load of 9.2kN/m2.

No. of panels Total weight of


Grid between the panel between the
grid grid

B/W 4 & 3 6 39.24 kN


B/W 3 & 2 5 37.28 kN
B/W 2 & 1 1 5.89 kN
LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 3
Maximum Panel
Overall size of No of Actual weight for Load
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT Actual panel (L panel units critical slab Distribution per Remarks
x W)in m in Nos (Refer Page sqm area
No-10)

Weight of existing LV
panel not available,
40.23/ (3.6 x Hence Existing Slab
LV (415V) ACTUAL PANEL
SS-03 Switch board DATA
10.240 x 1.200 15 40.23 kN 1.200) = strcutural adequacy is
=9.33kN/m2 verified for the panel
load of 9.33kN/m2.

Total weight of
panel between the
No. of panels grid (as per
approved vendor
Grid between the Equipment ID LOAD PER AREA
load data, P5693-
grid
A0-VD-3002-
0009,Refer Page No
– 25 & 26)

B/W 4 & 3 6 40.23 kN = ( EN01+02+03+04+05+06+(07/2)) = 40.23 / (3.6 x 1.2) = 9.33 kN/m2


B/W 3 & 2 5 41.21 kN = ( EN07+08+09+10+11) = 41.21 / (4.0 x 1.2) = 8.59 kN/m 2
B/W 2 & 1 4 23.55 kN = ( EN12+13+14+15) = 41.21 / (4.0 x 1.2) = 4.90 kN/m 2
LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 6
Maximum Panel
No of Actual weight for Load
panel units critical slab Distribution per Remarks
Overall size of in Nos (Refer Page sqm area
Actual panel (L No-10)
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT x W)in m

Weight of existing LV
panel not available,
39.24 / (4 x Hence Existing Slab
LV (415V) ACTUAL PANEL
SS-06 Switch board DATA
9.640 x 1.200 14 39.24 kN 1.200) = strcutural adequacy is
=8.2kN/m2 verified for the panel
load of 8.2kN/m2.

Total weight of
panel between the
grid (as per
No. of panels
approved vendor
Grid between the
load data, P5693-
grid
A0-VD-3002-
0012,Refer Page No
– 25 & 26)

B/W 4 & 3 6 39.24 kN


B/W 3 & 2 5 37.28 kN
B/W 2 & 1 3 17.70 kN
LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 4
Maximum Panel
Overall size of No of Actual weight for Load
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT Actual panel panel units critical slab Distribution per Remarks
(L x W) in m in Nos (Refer Page sqm area
No-10)

Weight of existing LV
panel not available,
39.24 / (4 x Hence Existing Slab
LV (415V) ACTUAL PANEL
SS-04 Switch board DATA
9.040 x 1.200 12 39.24 kN 1.200) = strcutural adequacy is
=8.2kN/m2 verified for the panel
load of 8.2kN/m2.

Total weight of
panel between the
grid (as per
No. of panels
approved vendor
Grid between the
load data, P5693-
grid
A0-VD-3002-
0010,Refer Page No
– 24 & 25)

B/W 4 & 3 6 39.24 kN


B/W 3 & 2 5 37.28 kN
B/W 2 & 1 1 5.89 kN
LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 5

Overall size of No of Actual Weight of Maximum Panel Load


Actual panel (L panel units panel as per weight for Distribution per
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT x W)in m in Nos Vendor input critical slab sqm area Remarks

Weight of existing LV
panel not available,
4500 / (4 x
6 x 750 = 4500Kg Hence Existing Slab
LV (415V) ACTUAL PANEL 1.200) =
SS-05 Switch board DATA
9.040 x 1.200 13 (Refer Page No
937.5Kg/m2
strcutural adequacy is
11) verified for the panel
=9.2kN/m2
750 Kgs load of 9.2kN/m2.
(P5693-A0-20-
RPT-18-00-001
APPENDIX -A
( ELECTRICAL
INPUT &
EXISTING
DRAWINGS)
Page No:25)
LV PANEL WEIGHT COMPARISION TABLE -SUBSTATION : 7
Maximum
Panel weight
Overall size of No of Actual Load
for critical
SUBSTATION TYPE OF PANEL SNAP SHOT OF ACTUAL PANEL ARRANGEMENT Actual panel (L panel units Distribution per Remarks
slab (Refer
x W)in m in Nos sqm area
Page
No-10)

Weight of existing LV
panel not available,
39.24 / (4 x Hence Existing Slab
LV (415V) ACTUAL PANEL
SS-07 Switch board DATA
9.640 x 1.200 14 39.24 kN 1.200) = strcutural adequacy is
=8.2kN/m2 verified for the panel
load of 8.2kN/m2.

Total weight of
panel between the
grid (as per
No. of panels
approved vendor
Grid between the load data, P5693-
grid
A0-VD-3002-
0009,Refer Page No
– 25 & 26)

B/W 5 & 4 3 17.66 kN = ( EN01+02+03)


B/W 4 & 3 5 37.28 kN = ( (EN04+05+06+07+(08+09/2))
B/W 3 & 2 6 39.24 kN = ( EN(08+09/2)+10+11+12+13+14)