Figures Chap 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

24/01/1442

2. Basic Definitions Load curves


EXAMPLE 1
Assume that the loading data
given in Table 1.1 belongs to one
of the primary feeders of the No
Light & No Power (NL&NP)
Company and that they are for a
typical winter day.

Develop the idealized daily load


curve for the given hypothetical
primary feeder.
Table 1.1: Idealized Load Data
for the No Light & No Power
Company's Primary Feede

Dr. Sadek DHBAIBI 14

1
24/01/1442

2. Basic Definitions Load curves


Solution

Figure 2-3

Dr. Sadek DHBAIBI 15

2
24/01/1442

2. Basic Definitions Diversified demand

D1max

D2max

D3max

D4max

Figure 1.10: Diversified demand curves


Dgmax
Dr. Sadek DHBAIBI 18

3
24/01/1442

2. Basic Definitions Examples


Solution of EXAMPLE 6

(a) The class contribution factor is:

For street lighting, residential, and


commercial loads, we obtain:

Table 1.1: Idealized Load Data for the No


Light & No Power Company's Primary Feede

Dr. Sadek DHBAIBI 44

4
24/01/1442

3. Relationship between load and loss factors


The Figure 1.16 showing an
arbitrary and idealized load
curve does not represent a daily
load curve.

Assume that the off-peak loss is


PLS,1 at some off-peak load P1 and
that the peak loss is PLS,2 at the
peak load P2.

The load factor is :

From the front Figure,


Figure 1.16: An arbitrary and
idealized load curve

Dr. Sadek DHBAIBI 48

5
24/01/1442

3. Relationship between load and loss factors


Figure 1.17 gives three different curves of loss factor as a function of
load factor.

Figure 1.17: Loss factor curves as a function of load factor. (From Westinghouse Electric
Corporation, Electric Utility Engineering Reference Book-Distribution Systems, vol. 3, East
Pittsburgh, PA, 1965. With permission.)
Dr. Sadek DHBAIBI 54

6
24/01/1442

3. Relationship between load and loss factors


EXAMPLE 8
Assume that the Riverside distribution substation of the NL&NP
Company supplying Ghost Town, which is a small city, experiences an
annual peak load of 3500 kW as shown in the Figure 1.18 below.

The total annual energy


supplied to the primary
feeder circuits is 10 GWh.
The peak demand occurs in
July or August and is due to
air-conditioning load.

(a) Find the annual average


power demand.
(b) Find the annual load
factor.
Figure 1.18: Monthly load curve
Dr. Sadek DHBAIBI 56

7
24/01/1442

3. Relationship between load and loss factors


EXAMPLE 9
Use the data given in EXAMPLE 8 and suppose that a new load of 100 kW
with 100 percent annual load factor is to be supplied from the Riverside
substation as shown on the Figure 1.19 below.
The investment cost, or
capacity cost, of the power
system upstream, i.e., toward
the generator, from this
substation is 18 $/kW per
month. Assume that the energy
delivered to these primary
feeders costs the supplier, that
is, NL&NP, 0.06 $/kWh.
(a) Find the new annual load
factor on the substation.
(b) Find the total annual
additional cost to NL&NP to Figure 1.19: new load curve
serve this load. after the new load addition
Dr. Sadek DHBAIBI 58

8
24/01/1442

4. Maximum Diversified Demand


Table 1.2

Dr. Sadek DHBAIBI 64

9
24/01/1442

4. Maximum Diversified Demand


Figure 1.20: Maximum diversified 30-min demand
characteristics of various residential loads
A = clothes dryer; B = off-peak water heater,
"off-peak" load; C = water heater, uncontrolled,
interlocked elements; D = range; E = lighting
and miscellaneous appliances; F = O.5-hp room
coolers; G = off-peak water heater, "on-peak"
load, upper element uncontrolled; H = oil
burner; I = home freezer; J = refrigerator; K =
central air conditioning including heat-pump
cooling, 5-hp heat pump (4-ton air
conditioner); L = house heating, including heat-
pump-heating-connected load of 15-kW unit-
type resistance heating or 5-hp heat pump.
(From Westinghouse Electric Corporation,
Electric Utility Engineering Reference Book-
Distribution Systems, vol. 3, East Pittsburgh, PA,
1965. With permission)
Dr. Sadek DHBAIBI 65

10

You might also like