Automatic Dosing Unit for Chilled Water Unit

 Precommissioning, Commissioning Procedure

WIND FLOW TRADING CONTRACTING & SERVICES W L L


Automatic Dosing Unit
for Chilled Water Unit

Green future - Environmental Protection with Wind Flow

PRECOMMISSIONING & COMMISSIONING PROCEDURE FOR AUTOMATIC CHEMICAL


DOSING UNIT

Objectives:
The purpose of this procedure is to define the step by step method to implement the correct practices for
the precommissioning & commissioning of “Automatic Chemical Dosing Unit”.
Through the guidelines contained herein so as to ensure that the job execution complies with the project
requirements and serves the intended function to satisfactory level.

Precommissioning Procedure for Automatic Chemical Dosing Unit:


Ensure that the system installation is complete and mechanical completion is approved & the installed unit
is as per approved material and as per approved shop drawings. Ensure that no damage has occurred
between mechanical completion & precommissioning.
 Ensure that inlet & outlet connection of the dosing pot is completed as per approved specialist
drawings.
 Check that the chilled water piping network is complete with proper meter, isolating & float valves,
drains, vents, strainers & instruments in place.
 Ensure that the flushing, chemical cleaning & addition of permanent chemicals is carried out in
line with the approved method statement.
 Ensure that the chilled water network is pressure tested and approved.
 Ensure that chemical tank is fixed & outlet pipe is connected to the suction of the chilled water
pump as per approved specialist drawings & manufacturer’s instructions.
 Check the conductivity sensor is properly installed in the by-pass of the suction & discharge pipes.
 Ensure that electrical connection from the conductivity sensor to the control panel is completed.
 Ensure that the power supply to the control panel is complete.
 Ensure that the field wiring is pre-tested for continuity and insulation resistance.
 Check for proper installation of the chemical tank, pump & related pipework.
 Check that the manual dosing pot installation is complete.
 Check for identification & labelling of the system components.

Wind Flow Trading Contracting & Services W L L | DOHA QATAR


www.windflowqatar.com | info@windflowqatar.com
Automatic Dosing Unit
for Chilled Water Unit

Green future - Environmental Protection with Wind Flow

Commissioning Procedure for Automatic Chemical Dosing Unit:


 Ensure that all the precommissioning checks are carried out successfully.
 Check the availability of power to the dosing unit.
 Fill the dosing tank up to 50 liters’ mark with clean potable water.
 Remove the discharge pipe of the dosing pump.
 Give power to the system & prime the pump.
 Connect the discharge end & make sure the suction & delivery tubes are kept straight.
 Check the installation of the conductivity controller.
 Check the power supply to the conductivity controller.
 Switch the dosing pump to AUTO mode.
 Induce a low conductivity signal to the control panel & check that the pump starts. The default set
point shall be decided on site by the manufacturer’s representative based on the conductivity of
water & the amount of final chemical added.
 Check the chemical in the tank is injected to the chilled water piping.
 Observe for any leakage from the unit.
 Check pumps for overheating (physically sensing by hand)
 Check for any undue vibration/noise.
 Check the pump switched OFF upon withdrawal of low conductivity signal.
 Manufacturer’s recommendations shall be fully followed for operation and maintenance of the
automatic dosing unit.

--------------------------------------------------END--------------------------------------------------