Modbus Address List: Model: SIEMENS Controller - 2ABH&LHH (Preessure Transmitter)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MODBUS Address LIST

Model : SIEMENS Controller_2ABH&LHH(Preessure Transmitter) Date : 2015.12.01.


Serial Device Bit Device Bit Engineering Signal
Address Description Units Scale
No. Status= 1 Status= 0 Unit Type
1 42000 Chilled water inlet temp. ℃ 0.1 -200-1000 Analog
2 42001 Chilled water outlet temp. ℃ 0.1 -200-1000 Analog
3 42002 Cooling water inlet temp. ℃ 0.1 -200-1000 Analog
4 42003 Cooling water outlet temp. ℃ 0.1 -200-1000 Analog
5 42004 Evaporator Refrigerant Temp. ℃ 0.1 -200-1000 Analog
6 42005 Condenser Refrigerant Temp. ℃ 0.1 -200-1000 Analog
7 42006 1st Generator outlet temp. ℃ 0.1 -200-1000 Analog
8 42007 Hot water inlet temp. ℃ 0.1 -200-1000 Analog
9 42008 Hot water outlet temp. ℃ 0.1 -200-1000 Analog
10 42009 Chiller operating status Run Stop on/off Binary
11 42010 Chiller alarm status Alarm on/off Binary
12 42011 Valve opening % 0~100 Analog
13 42012 Chilled water flow abnormal Alarm on/off Binary
14 42013 Cooling water flow abnormal Alarm on/off Binary
15 42014 Refrigerant pump over-current Alarm on/off Binary
16 42015 Solution pump1 over-current Alarm on/off Binary
17 42016 Solution pump2 over-current (2ABH,LHH) Alarm on/off Binary
18 42017 Solution pump3 over-current (2ABH) Alarm on/off Binary
19 42018 Solution pump4 over-current (2ABH) Alarm on/off Binary
20 42019 Low temp. cut out of Chilled water outlet Alarm on/off Binary
21 42020 Low temp. cut out of refrigerant Alarm on/off Binary
22 42021 Chilled water outlet temp. sensor abnormal Alarm on/off Binary
23 42022 Cooling water inlet temp. sensor abnormal Alarm on/off Binary
24 42023 Evaporator refrigerant temp. sensor abnormal Alarm on/off Binary
25 42024 Condenser refrigerant temp. sensor abnormal Alarm on/off Binary
26 42025 Hot water inlet temp. sensor abnormal Alarm on/off Binary
27 42026 1st Generator absorbent temp. sensor abnormal Alarm on/off Binary
28 42027 High temp. cut out of G1 absorbent Alarm on/off Binary
29 42028 Low temp. cut out of cooling water inlet Alarm on/off Binary
30 42029 High Temp. cut out of hot water Alarm on/off Binary
31 42030 Chiller Operating Time Hour 1 Analog
32 42031 Chilled water outlet temp set up. ℃ 0.1 Analog
33 42032 Chilled water outlet temp set up.(For Setting, Blank)
34 42033 Please Purge! (High pressure purge tank. ) Alert on/off Binary
35 42034 Purge Tank Pressure mmHg 0.1 Analog
* Default Setting of Touch Module
No. Item Setting Remark
1 09. COM1 Serial baud Rate 9600 [BPS]
2 10. COM1 Serial Data Bit 8 [BIT]
3 11. COM1 Serial Stop Bit 1 [BIT]
4 12. COM1 Serial Parity Bit None [BIT]
Modbus Address Slave ID
5 13. COM1 Station Num. In Diag. 3 Changeable according to the
site condition

* Recommend Setting of Client System


No. Item Setting Remark
1 Base Address 1
Device ID Changeable
2 Device ID(Slave ID) 3 according
to the site condition
3 Function Read Holding Registers Object Type : Word, Read Only
4 Address 2000
5 Baud Rate 9600
6 Data Bit 8
7 Stop Bit 1