Job01
General Data
Evaporator Information
Evaporator Application Standard Cooling (4 To 27C) Saturated evap temp - ckt 1 6.6 C
Evap fouling factor 0.000100 hr-sq ft-deg F/ Btu Saturated evap temp - ckt 2 4.0 C
Leaving fluid evap 7.00 C Min flow evap 25.90 L/s
Entering fluid evap 12.00 C Press drop at min evap flow 3.51 ft H2O
Flow evap 51.86 L/s Max flow evap 77.80 L/s
Fluid pressure drop evap 16.0 ft H2O Fluid pressure drop max flow evap 37.0 ft H2O
Evap configuration 1 Pass arrangement, insulated
Condenser Information
Electrical Information
Incoming Power Line Dual Point Power Connection Single Point unit starting current
Job01
Physical Information
Acoustical Performance
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units
may be found in the AHRI Directory at www.ahridirectory.org.