Drawing Chiller 300TR Crtag
Drawing Chiller 300TR Crtag
Drawing Chiller 300TR Crtag
Items: CRTAG-1
Qty: 1 Tags: CRTAG-1
7/30/2021 2:33:04 PM
END VIEW
ISO VIEW
6 in (DN 150)
18 mm
137 L
SIDE VIEW
TOP VIEW
WATER CONNECTION DIAMETER
MOUNTING HOLE DIAMETER
1054 mm
152 mm
1854 mm
SIDE VIEW
10043 mm
3472 mm
2250 mm
1057 mm
151 mm
421 mm
MAIN CONTROL PANEL
IN
TOP VIEW
OUT
6318 mm
1745 mm
421 mm
2498 mm
283 mm
END VIEW
2205 mm
2165 mm
1122 mm
40 mm
450 mm
CONTROL PANEL
LIFTING 8 PLACES
ISO VIEW
CONTROL PANEL
NOTE:
1. LIFTING CHAINS/CABLES WILL NOT BE THE SAME LENGTH.
ADJUST TO KEEP UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-134A CHARGE.
4. WEIGHTS ARE TYPICAL FOR UNITS WITHOUT LOUVER PANELS.
950 mm
1100 mm
943 mm
700.0 kg 575.0 kg N/A 582.0 kg 889.0 kg 640.0 kg 937.0 kg 851.0 kg 710.0 kg 947.0 kg 714.0 kg 971.0 kg N/A N/A N/A N/A
N/A
N/A
9000 mm
7800 mm
4400 mm
3400 mm
2250 mm
1000 mm
2 4 6 8 10 12 14 16
2X 40 mm
1 3 5 7 9 11 13 15
Job01
159 mm
127 mm
76 mm
1905 mm
70 mm
Page: 7
7/30/2021 2:33:05 PM
Items: CRTAG-1
Air-Cooled Series R(TM) CRTAG
A
L1
B
L2
C
L3
WARNING AVERTISSEMENT ADVERTENCIA
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
7 5Q5 INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
COULD RESULT IN DEATH OR
SERIOUS INJURY.
A B C A B C
L1 L2 L3 L1 L2 L3 5Q7
INSET "B" INSET "B"
A B C
L1 L2 L3 1X1
1Q2
"B"
FIELD POWER CONNECTIONS ARE MADE
1Q1 5K12 30 29
TO 1Q1 OR 1Q2 OR 1X1
18 30
5K13
EQUIPMENT 19 30
GROUND
82A 81A
400V 415V 5K14
H1 H2 H3 H4
20 30
380V 50HZ UNIT IS FACTORY WIRED AS SHOWN,
380V 50HZ RECONNECT WIRE 81A TO TERMINALS H3
11
OR H4 FOR 400V 50HZ OR 415V 50HZ 5K15
POWER SUPPLIES. 21 30
1T1
5K19
25 30
5K9
27 30
J2 J2
12 11 10 9 8 7 6 5 4 3 2 1 6 5 4 3 2 1
29 18 19 29 20 21 29 22 23 29 24 25 29 27
103
6
104
101
5
102
107
CUSTOMER CHILLED
+20VDC (CURRENT MODE)
2-10V OR 4-20ma
TO NEXT UNIT
AUTO STOP
105
WIRED TO CUSTOMER CURRENT LIMIT
SETPOINT 2-10V OR 4-20mA.
GND
GND
106
J2
J2
J2
+
6 5 4 3 2 1 1 2 3 4 1 2 3 4
5K23 9
10 9
10 9 12 11
5K24 9
12 11
106 105 108 107 103 104 101 102
SHIELDED TWISTED
SHIELDED TWISTED
2-10V OR 4-20ma
2-10V OR 4-20ma
PAIR LEADS
PAIR LEADS
J3 1K14
DUAL HIGH VOLTAGE INPUT
CHILLED WATER FLOW AND
INTERLOCK
J2
1X5-29
15
63
1. REFER TO RTHE ELECTRICAL SCHEMATIC FOR SPECIFIC ELECTRICAL CONNECTION INFORMATION AND NOTES PERTAINING TO WIRING INSTALLATION.
3. ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. EXCEPT AS NOTED, ALL
CUSTOMER WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14 TO 18 AWG.
4 CUSTOMER SUPPLIED POWER 115/60/1 OR 220/50/1 TO POWER RELAYS. MAX. FUSE SIZE IS 15 AMPS. GROUND ALL CUSTOMER SUPPLIED POWER SUPPLIES AS REQUIRED
BY APPLICABLE CODES. GREEN GROUND SCREWS ARE PROVIDED IN UNIT CONTROL PANEL.
5 WIRED TO NEXT UNIT. 22 AWG SHIELDED COMMUNICATION WIRE EQUIVALENT TO HELIX LF22P0014216 RECOMMENDED. THE SUM TOTAL OF ALL INTERCONNECTED CABLE
SEGMENTS NOT TO EXCEED 4500 FEET. CONNECTION TOPOLOGY SHOULD BE DAISY CHAIN. REFER TO BUILDING AUTOMATION SYSTEM (BAS) COMMUNICATION
INSTALLATION LITERATURE FOR END OF LINE TERMINATION RESISTOR REQUIREMENTS.
6 WIRED TO TRACER OR OTHER TRANE REMOTE DEVICE. 22 AWG SHIELDED COMMUNICATION WIRE EQUIVALENT TO HELIX LF22P0014216 RECOMMENDED. THE SUM TOTAL
OF ALL INTERCONNECTED CABLE SEGMENTS NOT TO EXCEED 4500 FEET. CONNECTION TOPOLOGY SHOULD BE DAISY CHAIN. REFER TO BUILDING AUTOMATION SYSTEM
(BAS) COMMUNICATION INSTALLATION LITERATURE FOR END OF LINE TERMINATION RESISTOR REQUIREMENTS.
7 ALL UNIT POWER WIRING MUST BE 600 VOLT COPPER CONDUCTORS ONLY AND HAVE A MINIMUM TEMPERATURE INSULATION RATING OF 75 DEGREE C. REFER TO UNIT
NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION DEVICE. PROVIDE AN EQUIPMENT GROUND IN ACCORDANCE WITH APPLICABLE
ELECTRIC CODES.
8 1
UNIT PROVIDED DRY CONTACTS FOR CUSTOMER CONNECTION CONTROL. RELAYS ARE RATED FOR 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY, OR 3 HP, 7.2 FLA AT 120
VOLTS 60 HZ, CONTACTS ARE RATED FOR 5 AMPS GENERAL PURPOSE DUTY 240 VOLTS.
9 CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC FOR A 12 mA RESISTIVE LOAD. SILVER OR
GOLD PLATED CONTACTS RECOMMENDED.
10 FLOW SWTICH AND INTERLOCK CONTACTS MUST BE ACCEPTABLE FOR USE IN A 120 VOLT 1 mA CIRCUIT OR A 220 VOLT 2 mA CIRCUIT.
11 380V/50HZ UNIT IS FACTORY WIRED WITH 81A CONNECTED TO H2 - RECONNECT WIRE 81A TO H3 FOR 400V/50HZ, OR H4 FOR 415V/50HZ.