Fires damper shall be installed where ducts pass through fire walls or area
separation walls. Dampers shall be installed at the fire wall and shall be Comply
of the folding blade curtain type with fusible link.
Fire dampers must be approved by City Inspection Department and
Fire dampers Engineer and shall be installed in sleeves in accordance with Comply
manufacturer instructions.
Dampers shall be actuated by approved fusible link. Upon operation of
Comply
the link, the dampers shall close automatically and remain tightly closed.
Fusible links shall operate approximately 10°C above the maximum
temperature the duct system shall encounter under normal operation, but Comply
not less than 72°C, unless otherwise noted on the Drawings.
Fire dampers shall be equipped with stainless steel spring catches. Comply
Provide hinged duct access door for inspection and servicing of dampers. Comply
flanges. Axles shall be of geared type and shall be interlocked with blades
minimum of four (4) blades running the entire length of the damper to
assure rigidity and tight close-off. Blades shall be on centers not greater
Manual
than 150 mm and no blade shall exceed 1200 mm in length. All blades shall Comply
dampers
be interconnected and in unison for opposed blade operation.
leakage between duct and damper frame. Head and sill shall have stops.
design to securely hold the damper sections and blade linkage hardware.
Furnish and install backdraft dampers where indicated on the Drawings.
Each damper shall be sized as indicated on the Drawings and shall be
suitable for installation in the mounting arrangement shown. Backdraft
dampers mounted in roof curbs shall be secured to galvanized steel support
Comply
angles fastened to the curb.
Backdraft dampers shall be heavy duty relief shutter type suitable for wall
and duct mounting or installation at a fan discharge and shall be constructed
as follows:
zamzam
Damper frame shall be constructed of at least 2 mm thick aluminium or
at least 1.2 mm galvanized steel. Damper frame shall be of channel
Comply
construction when installed in ductwork or have a front flange when
Back Draft
installed in a wall.
Dampers
Damper blades shall be constructed of at least 1 mm extruded aluminium
suitable for face velocities up to 7.5 m/s and at least 1.20 mm extruded
aluminium for face velocities to 12.5 m/s. Damper blades shall have
neoprene or vinyl gaskets rivetted or rolled into the blade edges. Each Comply
backdraft damper section shall be furnished with tie bars constructed of at
least 1.2 mm aluminium. Furnish two (2) tie bars on damper sections
over 1000 mm wide.
Furnish backdraft dampers with mesh aluminium bird screen for rear
Comply
mounting where backdraft dampers are mounted in outside walls.
Furnish and install smoke dampers where shown on the drawings in
accordance with applicable local regulations. Smoke shall be subject to
approval of the fire department.In general, dampers are required to isolate air handling
equipment from the
remainder of the system and wherever ducts penetrate smoke partitions.
Where fire partitions are used as smoke partitions, dampers shall be
combination fire/ smoke type as specified above.
Smoke dampers shall be constructed 3.4 mm sheet steel with high
Smoke Dampers temperature blade seal fusible links designed break at 820 C.
Comply