Professional Documents
Culture Documents
02 - Sprinklers & Hose Cabinets Calculations
02 - Sprinklers & Hose Cabinets Calculations
02 - Sprinklers & Hose Cabinets Calculations
0 The occupancy classification is ordinary hazard (Group 1) for basement (1&2) from
NFPA. And light hazard for the upper floors Pages 13-14, 13-167, 13-168
1 The pipe sizing is based on pipe schedule method as per NFPA 13, table {8-5-2-2} &
Table {8-5-3-2 (a)}. Refer to attachment no. (4), (5).
3 Minimum residual pressure required, at the outlet of fire hose reel, is 65 PSI (4.5 Bar)
from NFPA14 page (14-16). Refer to attachment No. (7).
4 Total area served by the sprinklers system is (279) m2.
5 Pendent sprinklers standard application with K-factor (5.6) used for covering area with
false ceiling, this sprinklers shall be distributed, as following:
(1940) Sprinklers at ground floor.
(1842) Sprinklers at first floor.
(721) Sprinkler at second floor
(503) Sprinkler at basement (2)
6 Upright sprinklers standard application with K-factor (5.6) used for covering area
without false ceiling, this sprinklers shall be distributed, as following:
(2939) sprinklers at basement (1)
(1691) sprinkler at basement (2)
7 sidewall sprinklers standard application with K-factor (5.6) used for covering area
without false ceiling, this sprinklers shall be distributed, as following:
(4) Sprinklers at basement (2)
Q = Flow in (L/Min)
As per National Fire Protection Association Code "NFPA13" Table 5-6 .2.2 (b)
ト Actual area served by one sprinkler = room area ÷ actual No. of sprinklers.
= 352÷ 29 = 12 m².
= 49.2 L/min
Cases of loading
-So the maximum load occur when all sprinklers at this area opened