Murray Centennial P.S. - Revised Carrier Shop Drawings (KP)
Murray Centennial P.S. - Revised Carrier Shop Drawings (KP)
SUBMITTAL KP
REV.1 05/21/2021
RVA: resubmit the Hot water coil (HW-103,104,
and 106) only, the remaining items in this shop x
drawing should be reviewed as noted.
FOR APPROVALS
REVIEWED
Carrier Canada Adamson & Dobbin Ltd.
195 Statesman Drive May 17th 2021
Mississauga, Ontario R. Stephen Dawson
L5S 1X4
-1-
Unit Report For RTU-101
Project: Murray Centennial PS 05/14/2021
Prepared By: Doug Roberts P. Eng. 05:06PM
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
15-Year heat exchanger - Stainless Steel(std.)
Complete Unit Year 2-5 Parts Only Extended Warranty
Start-up by Carrier Representative
Complete Unit 1st Year Carrier CCS Labor Warranty
Ordering Information
Service Options
0 = None
Heat Size 1 = Unpowered Convenience Outlet
D - Low Gas heat 2 = Powered Convenience Outlet
E - Medium Gas Heat 3 = Hinged Panels
F - High Gas Heat 4 = Hinged Panels, Unpowered Convenience Outlet
S - Low Stainless Gas Heat 5 = Hinged Panels, Powered Convenience Outlet
R - Medium Stainless Gas Heat
T - High Stainless Gas Heat Intake / Exhaust Options
A = None
Refrigeration Systems Options B = Temperature Economizer w/ Barometric Relief
D - 2 – Stage Cooling F = Enthalpy Economizer w/ Barometric Relief
E – 2 – Stage Cooling with Humidi- K = 2-Position Damper
MiZer (only available on 17- U = Temp Ultra Low Leak Economizer w/Baro Relief
28 sizes with RTPF coil V = Temp Ultra Low Leak Economizer w/PE (cent) Power Exhaust
models) W = Enthalpy Ultra Low Leak Economizer w/Baro Relief
X = Enthalpy Ultra Low Leak Economizer w/PE (cent) Power Exhaust
Cooling Tons (Vertical Air Flow Models Only) D = Temperature Economizer with PE (cent) Power Exhaust
17 - 15 ton
20 - 17.5 ton Base unit controls
24 - 20 ton 0 = Electro-mechanical Controls Can be used with W7212
28 - 25 ton EconoMi$er IV (Non – Fault Detection and Diagnostic)
30 – 27.5 ton 1 = PremierLink Controller
2 = RTU Open Multi-Protocol Controller
6 = Electro-mechanical w/ 2-speed fan and W7220 Econo controller
Controls. Can be used with W7220 EconoMi$er X (with Fault
Sensor Options Detection and Diagnostic)
A = None
B = RA Smoke Detector
C = SA Smoke Detector Design Revision
D = RA + SA Smoke Detector - = Factory Assigned
E = CO2
F = RA Smoke Detector and CO2
Voltage
G = SA Smoke Detector and CO2
1 = 575/3/60
H = RA + SA Smoke Detector and CO2
5 = 208-230/3/60
J = Condensate Overflow Switch (electro mech controls only)
6 = 460/3/60
K = Condensate Overflow Switch and RA Smoke Detectors
L = Condensate Overflow Switch and RA and SA Smoke
Detectors Coil Options
Novation Coils Only (Outdoor-Indoor-Hail Guard)
G = Al/Al - Al/Cu T = Al/Al - Al/Cu, Louvered
Indoor Fan Options (Vertical Air Flow Models Only) H = Al/Al - Cu/Cu U = Al/Al - Cu/Cu, Louvered
1 = Standard Static Option, Vertical J = Al/Al - E-coat Al/Cu V = Al/Al - E-coat Al/Cu, Louvered
2 = Medium Static Option, Vertical K = Al/Al E-coat - Al/Cu W = Al/Al E-coat - Al/Cu, Louvered
3 = High Static Option, Vertical L = Al/Al E-coat - Al/Cu E-coat X = Al/Al E-coat - Al/Cu E-coat, Louvered
B =Medium Static High Efficiency Motor/Vertical
Indoor fan option #2 Supply, Return Air Flow Round Tube Plate Fin (RTPF) (Outdoor-Indoor-Hail Guard)
is the correct option C =High Static, High Efficiency Motor/Vertical Supply, A = Al/Cu – Al/Cu M = Al/Cu – Al/Cu – Louvered
required to meet the Return Air Flow B = Precoat Al/Cu – Al/Cu N = Precoat Al/Cu – Al/Cu – Louvered
specified airflow and C = E-coat Al/Cu – Al/Cu P = E-coat Al/Cu – Al/Cu - Louvered
external static D = E-coat Al/Cu – E-coat Al/Cu Q = E-coast Al/Cu – E-coat Al/Cu –
pressure Not all possible options can be displayed above – see E = Cu/Cu – Al/Cu Louvered
following pages for more details F = Cu/Cu – Cu/Cu R = Cu/Cu – Al/Cu – Louvered
S = Cu/Cu – Cu/Cu – Louvered
-3-
Certified Drawing for RTU-101
Project: Murray Centennial PS 05/14/2021
Prepared By: Doug Roberts P. Eng. 05:06PM
Part Number:48TCRD20A2P5-6V3J0
Unit
Unit Voltage-Phase-Hertz: ............................................................................................................... 208-3-60
Air Discharge:.................................................................................................................................... Vertical
Fan Drive Type:....................................................................................................................................... Belt
Actual Airflow: ........................................................................................................................................ 2358 L/s
Site Altitude: ............................................................................................................................................. 282 m
Cooling Performance
Condenser Entering Air DB: .................................................................................................................... 28.9 C
Evaporator Entering Air DB: .................................................................................................................... 26.8 C
Evaporator Entering Air WB: ................................................................................................................... 19.4 C
Entering Air Enthalpy: ........................................................................................................................... 56.44 kJ/kg
Evaporator Leaving Air DB: ..................................................................................................................... 11.8 C
Evaporator Leaving Air WB: .................................................................................................................... 11.5 C
Evaporator Leaving Air Enthalpy: .......................................................................................................... 33.55 kJ/kg
Gross Cooling Capacity: ....................................................................................................................... 62.69 kW
Gross Sensible Capacity: ...................................................................................................................... 41.20 kW
Compressor Power Input: ..................................................................................................................... 14.24 kW
Coil Bypass Factor: ............................................................................................................................... 0.081
Mixed Air
Outdoor Air Airflow: ................................................................................................................................ 1369 L/s
Outdoor Air DB: ....................................................................................................................................... 28.9 C
Outdoor Air WB: ...................................................................................................................................... 20.6 C
Outdoor Air Htg. Temp.: ......................................................................................................................... -27.2 C
Return Air DB: ......................................................................................................................................... 23.9 C
Return Air WB: ........................................................................................................................................ 17.8 C
Return Air Htg. Temp.: ............................................................................................................................ 21.1 C
Heating Performance
Heating Airflow: ...................................................................................................................................... 2358 L/s
Entering Air Temp: .................................................................................................................................... 1.7 C
Leaving Air Temp: ................................................................................................................................... 28.4 C
Gas Heating Input Capacity: ......................................................................................................... 72.7 / 90.9 kW
Gas Heating Output Capacity: ...................................................................................................... 58.6 / 73.6 kW
Temperature Rise: .................................................................................................................................. 26.7 K
Thermal Efficiency (%): ........................................................................................................................... 81.0
Supply Fan
External Static Pressure:..................................................................................................................... 250.00 Pa
Power Exhaust
Return Duct Static: .............................................................................................................................. 102.82 Pa
Max. Air to Exhaust: ............................................................................................................................... 2002 L/s
Electrical Data
Voltage Range: ............................................................................................................................... 187 - 253
Compressor #1 RLA:............................................................................................................................... 29.5
Compressor #1 LRA:................................................................................................................................ 195
Compressor #2 RLA:............................................................................................................................... 28.2
Compressor #2 LRA:................................................................................................................................ 239
Indoor Fan Motor Type: .......................................................................................................................... MED
Indoor Fan Motor FLA: ............................................................................................................................ 13.6
Combustion Fan Motor FLA (ea): ............................................................................................................ 0.52
Power Supply MCA: ................................................................................................................................... 95
Power Supply MOCP (Fuse or HACR):.................................................................................................... 110
Disconnect Size FLA: ............................................................................................................................... 101
Disconnect Size LRA: .............................................................................................................................. 551
Electrical Convenience Outlet: .............................................................................................................. None
Power Exhaust [Motor Qty / FLA(ea motor)]: ....................................................................................... 2 / 5.9
Outdoor Fan [Qty / FLA (ea)]: .............................................................................................................. 3 / 1.5
Acoustics
Sound Rating: ......................................................................................................................................... 84.0 db
Sound Power Levels, db re 10E-12 Watts
Advanced Acoustics
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
( h Pa ) F a n Cu r v e
5 . 0
1 2 0 0 R P M
1 1 0 0 R P M
Pr e s s u r e
1 0 0 0 R P M
3 . 8
9 0 0 R P M
R P
S C 5 . 5 9 k W
2 . 5 8 0 0 R P M
S t a t ic
7 0 0 R P M
6 0 0 R P M
1 . 3 3 . 7 3 k W
5 0 0 R P M
2 . 2 4 k W
4 0 0 R P M 1 . 4 9 k W
1 . 1 2 k W
3 0 0 R P M 0 . 7 5 k W
0 . 3 7 k W
0 . 5 6 k W
0 . 0
0 . 0 5 . 0 1 0 . 0 1 5 . 0 2 0 . 0 2 5 . 0 3 0 . 0 3 5 . 0 4 0 . 0 4 5 . 0
A ir f lo w ( l/ s - h u n d r e d s )
= 8 3 7 k W = 1 . 9 4 M a x i m u m R P M = 1 2 9 0 M a x i m u m k W = 6
S C - S y s t e m C u r v e R P - R a t e d P o i n t
-13- 16
-14-
Fig. 56 — 48TC**17-30 Control Wiring Diagram
51
-15-
Fig. 57 — 48TC**17-30 Power Wiring Diagram, 208/230-3-60
52
Unit Feature Sheet for RTU-101
Project: Murray Centennial PS 05/14/2021
Prepared By: Doug Roberts P. Eng. 05:06PM
PART #MS7505A2030
-17-
N314 3 Nm, 5 Nm Series Spring Return
Direct Coupled Actuators
MS3103, MS3105, MS4103, MS4105, MS7403,
MS7405, MS7503, MS7505, MS8103, MS8105
MS3103, MS3105, MS4103, MS4105, MS7403, MS7405, SPECIFICATION DATA
MS7503, MS7505, MS8103, MS8105 Spring Return Direct
Coupled Actuators (DCA) are used within heating, ventilating,
and air-conditioning (HVAC) systems. They can drive a variety SPECIFICATIONS
of quarter-turn, final control elements requiring spring return
fail-safe operation. Models:
See Table 1.
Device Weight:
APPLICATIONS 3.5 lbs (1.60 kg)
Ambient Operating Temperature:
• Volume control dampers, mounted directly to the drive -40° to 150°F (-40° to 65°C)
shaft or remotely (with the use of accessory hardware).
-22° to 150°F (-30° to 65°C) (Two position only)
• Quarter-turn rotary valves, such as ball or butterfly
valves mounted directly to the drive shaft. Shipping and Storage Temperature:
• Linear stroke globe or cage valves mounted with -40° to +150°F (-40° to +65°C)
linkages to provide linear actuation. Humidity Ratings:
• Available with cable on select models. 5% to 95% R.H., Non-Condensing
Table 1. Models.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising
out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and
subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or
-18-
resulting from, any modification to the literature by you. Put Bar Code Here
63-1336-05
3 NM, 5 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Electrical Connections: Stroke: 95° ±3°, mechanically limited.
Field wiring 18 AWG (0.5 mm) to 14 AWG (1.5 mm)
Approvals:
conductors (stranded or solid) and up to 2 - 14 AWG (1.5
UL873
mm) conductors (stranded) to screw terminals, located
IEC 60730-1 and Part 2–14
under the removable access cover.
UL1097 for Double Insulation
Auxiliary Switch (One SPDT): CE Certification Low Voltage Directive 2006/95/EC
Switch adjustable from 0-95° CE EMC 2004/108/EC
500 uA Resistive at 5 Vdc (minimum) C-Tick N314
250 Vac, 8 A resistive, 3 A inductive
Design Life (at Rated Voltage):
Mounting: Self-centering shaft adapter (shaft coupling): 60,000 full stroke cycles; 1,500,000 repositions;
Round damper shafts: 3/8 to 5/8 in. (9 to 16 mm) 60,000 full stroke spring returns.
Square damper shafts: 1/4 to 1/2 in. (6 to 13 mm)
Enclosure Ratings:
Minimum Damper Shaft Length: IP54
1 in. (25 mm); 3 in.(76 mm) recommended. NEMA 2
Flame Resistance UL94-5VA
Torque Ratings:
Typical Holding, Driving, Spring Return: Input Impedance:
MSXX03: 27 lb-in. (3 Nm) 95 kOhms minimum.
MSXX05: 44 lb-in. (5 Nm)
Feedback Signal:
Stall Maximum (fully open at 75°F):
0(2)-10 Vdc, 3 mA minimum.
MSXX03: 71 lb-in. (8 Nm)
MSXX05: 106 lb-in. (12 Nm) Analog Output Signal:
0(2)-10Vdc
Spring Return Timing (at rated load):
< 25 seconds @ -4°F to 130°F (-20°C to 55°C) Noise Rating at 1m (Maximum):
< 60 seconds @ -22°F (-30°C) Driving
Floating/Modulating/Econ/Sylk-enabled: < 40 dB(A)
Cable Specification: 2-Position: < 50 dB(A)
300 V, 75° C, Plenum Rated, 3 ft length from end of access Spring Return: < 60 dB(A)
cover, 18 AWG
Accessories:
Sylk™ Bus 27518 Balljoint (5/16 in.)
Sylk is a two-wire, polarity insensitive bus that provides 103598 Balljoint (1/4 in.)
communications between a Sylk-enabled Zelix and a Sylk- 27520B, C, E, G, H, K, L, Q Pushrod (5/16 in. diameter)
enabled controller. For wiring, the Zelix Sylk-enabled STRN-STRNRLF Water-tight Cable Gland/Strain-relief
actuator may be mounted up to 200 ft. (61 m) from the Fitting (10 pack)
controller; twisted pair wire is recommended for wire runs STRN-WMK-01 Wall Mount Kit
longer than 100 ft. (30.5 m). Using Sylk-enabled actuators STRN-ECONO-01 Economizer Retrofit Kit
saves I/O on the controller and is faster and cheaper to STRN-CRK-01 Crank Arm Kit
install since the bus is polarity insensitive. STRN-SCSA Self Centering Shaft Adapter
STRN-CA-01 Crank Arm (Non-Self-Centering)
3-55/64 (98) 3-5/32 (80)
1-9/16 1-15/16
2-27/64 (61) 47/64 STRN-CA-02 Crank Arm (Self-Centering)
(40) (49) (19) STRN-BRKT Anti-Rotation Bracket
1-1/8
(29)
TYPICAL SPECIFICATION
Spring return actuators shall be direct coupled type requiring neither cran-
1-1/16
(27) karm nor linkage and be capable of direct mounting to a jackshaft of up to 5/8
in. diameter. The actuator shall connect to the shaft using a removable output
hub with a self-centering shaft coupling. This coupling shall provide concen-
tric mounting and include an integral adjustable range-stop mechanism.
4-9/16
(116) 6-61/64 The actuator shall provide two-position, floating, proportional, or Sylk bus
(177) control. Proportional control refers to direct acceptance of 0-10 Vdc, 2-10 Vdc,
or (with addition of a 500 ohm resistor) a 4-20 mA input signal. Proportional
5-27/32
(148) and floating control models shall provide a feedback signal. Sylk-enabled
models provide control and feedback via communication between the actua-
tor and Sylk-enabled controller. Actuators shall provide wiring terminals
located within an integral access cover with conduit connections. Propor-
tional and floating actuators shall have a rotation direction control switch
accessible on the cover.
All spring return actuators must be designed for either clockwise or counter-
clockwise fail-safe operation with a continuously engaged mechanical spring.
This spring must return the valve or actuator to a fail-safe position within 25
2-1/64 seconds of power loss.
(55)
All actuators shall be designed for a minimum of 60,000 fullstroke cycles at
rated torque and temperature, 60,000 springreturn cycles and 1,500,000 repo-
1 CABLE AND STRAIN
sitions. Run time shall be constant and independent of: load, temperature,
RELIEF ON SELECT
1 and supply voltage (within specifications). All actuators shall be UL60730 and
MODELS ONLY. 36 (914) M28945A cUL (CSA22.2) listed, have a five year warranty, and be manufactured under
ISO 9001 International Quality Control Standards. Actuators shall be as manu-
factured by Honeywell.
Fig. 1. Dimensional drawing of actuator in in. (mm)
-19-
Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
Golden Valley, MN 55422 © 2015 Honeywell International Inc.
63-1336—05 M.S. Rev. 03-15
customer.honeywell.com Printed in United States
37KN
BYPASS AIR TERMINAL
WITHOUT CONTROLLER
RVA:
General Contractor to provide all the duct fitting necessary to connect all the
By pass damper with the duct works as specified in the contract document
Accessories Included:
22
- Belimo 2-10VDC actuator, 24 VAC
- 115V to 24V transformer
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
-20-
Unit Report For BPB-101
Project: Murray Centennial PS 04/07/2021
Prepared By: Doug Roberts P. Eng. 04:24PM
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-101
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082507030000
Dimensions
Unit Depth: ...................................................................................................................................................................... 835.7 mm
Unit Width: ...................................................................................................................................................................... 660.4 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-101
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082507030000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 389.4 L/s
Min. Primary Airflow: ....................................................................................................................................................... 331.8 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-101
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082507030000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-102
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................14 Inch (MAX 2500 CFM)
Part Number: ........................................................................ 35KN00--14-000000000CS0000000000.000000096806230000
Dimensions
Unit Depth: ...................................................................................................................................................................... 886.5 mm
Unit Width: ...................................................................................................................................................................... 688.3 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-102
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................14 Inch (MAX 2500 CFM)
Part Number: ........................................................................ 35KN00--14-000000000CS0000000000.000000096806230000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 456.8 L/s
Min. Primary Airflow: ....................................................................................................................................................... 294.0 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-102
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................14 Inch (MAX 2500 CFM)
Part Number: ........................................................................ 35KN00--14-000000000CS0000000000.000000096806230000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-103
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082505150000
Dimensions
Unit Depth: ...................................................................................................................................................................... 835.7 mm
Unit Width: ...................................................................................................................................................................... 660.4 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-103
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082505150000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 389.4 L/s
Min. Primary Airflow: ....................................................................................................................................................... 243.1 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-103
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000082505150000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-104
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000071205170000
Dimensions
Unit Depth: ...................................................................................................................................................................... 835.7 mm
Unit Width: ...................................................................................................................................................................... 660.4 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-104
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000071205170000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 336.0 L/s
Min. Primary Airflow: ....................................................................................................................................................... 244.0 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-104
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000071205170000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-105
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000086905530000
Dimensions
Unit Depth: ...................................................................................................................................................................... 835.7 mm
Unit Width: ...................................................................................................................................................................... 660.4 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-105
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000086905530000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 410.0 L/s
Min. Primary Airflow: ....................................................................................................................................................... 261.0 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-105
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000086905530000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-106
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000072305150000
Dimensions
Unit Depth: ...................................................................................................................................................................... 835.7 mm
Unit Width: ...................................................................................................................................................................... 660.4 mm
Unit Height: ..................................................................................................................................................................... 434.3 mm
Unit Operating Weight : ........................................................................................................................................................ 12 kg
*** Weights and Dimensions are approximate. Weight does not include curbs
and accessories. Approximate dimensions are provided primarily for
shipping purposes. For exact dimensions, refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Base Unit
0000: Field supplied controls w/ no Control Enclosure and no Flow
Probe
Hangers
Balancing Air Damper, Manual Inlet
Accessories None
Note:
Controls contractor shall supply all DDC / BACNET controllers, SAT sensor, hot water coil
control valve, and space temperature sensor
CODE
THIS DOCUMENT IS THE PROPERTY OF SUBMISSION OF THESE
CARRIER CORPORATIONAND IS DELIVERED DRAWINGS OR DOCUMENTS BYPASS TERMINAL
CATALOG #
UPON THE EXPRESS CONDITION THAT
THE CONTENTS WILL NOT BE DISCLOSED
OR USED WITHOUT CARRIER
DOES NOT CONSTITUTE
PART PERFORMANCE
OR ACCEPTANCE OF
UNIT WITH 35K
CORPORATION'S WRITTEN CONSENT CONTRACT ELECTRONIC CONTROLS
ACCESSORIES
. Hanger Brackets
. Damper, Manual Inlet
. Damper, Manual Bypass
. Thermostat
NOTES:
1. 20 ga. Steel construction.
2. "D" dimensin is diameter of inlet, bypass and outlet connection.
3. 1/2" dual density coated insulation meeting NFPA90Aand UL 181.
4. Damper operates on a 24 Volt thermostat signal.
INLET SIZE A B C D E F G
6 12-7/8 7-1/8 11-1/8 5-7/8 4-1/4 12-3/8 5-9/16
8 12-7/8 7-1/8 11-1/8 7-7/8 5-1/4 12-3/8 5-9/16
10 14-7/8 8-1/8 13-1/8 9-7/8 6-1/4 14-3/8 6-9/16
12 18-7/8 10-1/8 17-1/8 11-7/8 7-1/4 18-3/8 8-9/16
14 18-7/8 10-1/8 17-1/8 13-7/8 8-1/4 18-3/8 8-9/16
16 22-7/8 12-1/8 21-1/8 15-7/8 9-1/4 22-3/8 10-9/16
18 22-7/8 12-1/8 21-1/8 17-7/8 10-1/4 22-3/8 10-9/16
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-106
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000072305150000
Unit Performance
Altitude: .................................................................................................................................................................................. 0 m
Max. Primary Airflow: ...................................................................................................................................................... 341.0 L/s
Min. Primary Airflow: ....................................................................................................................................................... 243.1 L/s
Inlet Static Pressure: ....................................................................................................................................................... 0.149 kPa
Downstream Static Pressure: .......................................................................................................................................... 0.050 kPa
Minimum Static Pressure Drop:....................................................................................................................................... 0.001 kPa
Note: ...................................................................................... Inlet Static Pressure includes downstream pressure drop.
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Unit Parameters
Tag Name: ................................................................................................................................................................ BPB-106
Quantity: ................................................................................................................................................................................. 1
Model Type: .......................................................................................................................... No Controls or Field Supplied
Model: ........................................................................................................................................................35K Bypass Units
Control Type: ................................................................................0000: Field supplied controls w/ no Control Enclosure
Unit and Inlet Size: ..........................................................................................................................12 Inch (MAX 2000 CFM)
Part Number: ........................................................................ 35KN00--12-000000000CS0000000000.000000072305150000
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer, and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Application
For proportional modulation of dampers in HVAC systems. Actuator sizing
should be done in accordance with the damper manufacturer’s specifications.
The default parameters for 2 to 10 VDC applications of the …MFT actuator are
assigned during manufacturing. If necessary, custom versions of the actuators
can be ordered. The parameters can be changed by two means: pre-set and
Technical Data 1512
custom configurations from Belimo or on-site configurations using the Belimo
Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% PC-Tool software.
Power consumption in operation 3.5 W
Power consumption in rest 1.3 W Operation
position The actuator is not provided with and does not require any limit switches, but is
Transformer sizing 6 VA (class 2 power source) electronically protected against overload. The anti-rotation strap supplied with
Shaft Diameter 1/2...1.05” round, centers on 1/2” and 3/4” the actuator will prevent lateral movement.
with insert, 1.05” without insert
The NMB(X) series provides 95° of rotation and a visual indicator indicates
Electrical Connection 18 GA plenum cable with 1/2” conduit
position of the actuator. When reaching the damper or actuator end position,
connector, degree of protection NEMA 2 /
the actuator automatically stops. The gears can be manually disengaged with a
IP54, 3 ft [1 m] 10 ft [3 m] and 16ft [5 m]
button on the actuator cover.
Overload Protection electronic throughout 0...95° rotation
Operating Range 2...10 V (default), 4...20 mA w/ ZG-R01 (500 The NMB(X)24-MFT actuators use a brushless DC motor, which is controlled
Ω, 1/4 W resistor), variable (VDC, PWM, on/ by an Application Specific Integrated Circuit (ASIC). The ASIC monitors
off, floating point) and controls the actuator’s rotation and provides a digital rotation sensing
Operating range Y variable Start point 0.5...30 V (DRS) function to prevent damage to the actuator in a stall condition. Power
End point 2.5...32 V consumption is reduced in holding mode.
Input Impedance 100 kΩ for 2...10 V (0.1 mA), 500 Ω for
4...20 mA, 1500 Ω for PWM, On/Off and Add-on auxiliary switches or feedback potentiometers are easily fastened
Floating point directly onto the actuator body for signaling and switching functions.
Date created, 02/10/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.
7.7" [196.2]
Accessories
K-NA Shaft clamp reversible
24 VAC Transformer 1 3 11
ZG-100 Univ. right angle bracket 17”x11-1/8”x6” (HxWxbase).
ZG-101 Univ. right angle bracket 13x11x7-7/16” (HxWxbase).
Line Blk (1) Common
ZG-103 Univ. right angle bracket 7-1/2x11x2-3/4” (HxWxbase).
Volts Red (2) Hot +
ZG-104 Univ. right angle bracket 13-5/8x7-1/2x4” (HxWxbase).
ZG-NMA Mounting kit for linkage operation
AV8-25 Shaft extension Wht (3) Y Input
1
ZG-NMSA-1 Shaft extension for 1/2” diameter shafts (3.8” L). Position (–) Pnk (4) Y Input
2
ZS-100 Weather shield - galvaneal 13x8x6” (LxWxD). Feedback VDC (+) Org (5) U Output
ZS-150 Weather shield - PC w/ foam seal 16x8-3/8x4” (LxWxD).
TOOL-06 8 mm and 10 mm wrench. On/Off
S1A Auxiliary switch for damper actuators and rotary actuators
S2A Auxiliary switch for damper actuators and rotary actuators
P10000A GR Feedback potentiometer for damper actuators and rotary 24 VAC Transformer (AC Only) 1 10 11
actuators
P1000A GR Feedback potentiometer for damper actuators and rotary Line Blk (1) Common
actuators Volts
Red (2) Hot +
P140A GR Feedback potentiometer for damper actuators and rotary
actuators Wht (3) Y Input
1
P2800A GR Feedback potentiometer for damper actuators and rotary
actuators Pnk (4) Y Input
Position (–) 2
P5000A GR Feedback potentiometer for damper actuators and rotary Feedback VDC (+) Org (5) U Output
actuators
P500A GR Feedback potentiometer for damper actuators and rotary Floating Point
actuators
SGA24 Positioners suitable for use with the modulating damper
actuators LM..A-SR, NM..A-SR, SM..A-SR and GM..A-SR 24 VAC Transformer 1 3 5 11
ZG-R01 4 to 20 mA adaptor, 500Ω, 1/4 W resistor w 6” pigtail wires.
NSV24 US Battery back-up module for non-spring return actuators. Line Blk (1) Common
ZG-X40 120 to 24 VAC, 40 VA transformer. Volts Red (2) Hot +
Ω 500 Ω
1/4 watt
Typical Specification Control Signal (–)
Wht (3) Y Input
which require no crank arm and linkage and be capable of direct mounting 7 Pnk (4) Y Input
to a shaft from 1/4” to 1/2” diameter. Actuators must provide proportional 2
damper control response to a 2 to 10 VDC or, with the addition of a 500Ω Org (5) U Output
resistor, a 4 to 20 mA control input from an electronic controller or positioner.
Actuators shall have brushless DC motor technology and be protected from VDC/mA Control
overload at all angles of rotation. Actuators shall have manual override on the
cover. Run time shall be constant and independent of torque. Actuators shall
24 VAC Transformer (AC Only)
be cULus listed, have a 5-year warranty, and be manufactured under ISO 9001 1 8 11
International Quality Control Standards. Actuators shall be as manufactured
by Belimo. Blk (1) Common
Line
Volts Red (2) Hot +
PWM Control
UNIT TAG:HW-105
QTY (1)
MODEL: 620F2-15X17-1010R511
ACCESSORIES INCLUDED:
• None. BAS contractor shall supply the hot water coil control valve.
-47-
Hot Water Coil Report
Coil Data
Model Number 620F2-15X17-106R721
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 2
Number Of Feeds 2
Fins Per Inch 6
Supply Connection Size 3/4"
Return Connection Size 3/4"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 50.46 ft²
Connection Type MPT
Casing Material Galvanized Steel 16 gauge
Coil Weight 30.49 lb
Air Data
Total Air Flow 824 SCFM
Air Flow Per Coil 824 SCFM
Standard Face Velocity 465.32 FPM
Altitude 0 FT
Entering Dry Bulb 57 °F
Leaving Dry Bulb 99.34 °F
Air Pressure Drop 0.12 inWG
Total Capacity 38.09 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 3.88 GPM
Fluid Velocity 2.32 FPS
Fluid Pressure Drop 1.76 ftWG
Notes
-48-
17/05/2021 MADOK MANUFACTURING INC. Page 2 of 13
-49-
17/05/2021 MADOK MANUFACTURING INC. Page 3 of 13
Hot Water Coil Report
Coil Data
Model Number 620F1-15X17-1010R511
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 1
Number Of Feeds 1 RVA: Provide pipe fitting necessary
Fins Per Inch 10 to connect the hot water piping with
Supply Connection Size 1/2" the coil.
Return Connection Size 1/2"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 40.45 ft²
Connection Type MPT
Casing Material Galvanized Steel 16 gauge
Coil Weight 26.88 lb
Air Data
Total Air Flow 968 SCFM
Air Flow Per Coil 968 SCFM
Standard Face Velocity 546.64 FPM
Altitude 0 FT
Entering Dry Bulb 57 °F
Leaving Dry Bulb 86.28 °F
Air Pressure Drop 0.11 inWG
Total Capacity 30.95 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 3.15 GPM
Fluid Velocity 3.76 FPS
Fluid Pressure Drop 3.52 ftWG
Notes
-50-
17/05/2021 MADOK MANUFACTURING INC. Page 4 of 13
-51-
17/05/2021 MADOK MANUFACTURING INC. Page 5 of 13
Hot Water Coil Report
Coil Data
Model Number 620F1-15X17-1010R511
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 1
Number Of Feeds 1
Fins Per Inch 10
Supply Connection Size 1/2"
Return Connection Size 1/2"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 40.45 ft²
Connection Type MPT
RVA: the max flow is 389 L/s
Casing Material Galvanized Steel 16 gauge
(824 cfm) and the minimum flow
Coil Weight 26.88 lb
is 243 L/s (515 CFM) as spe-
cified in the contract drawing
Air Data
M107, the coil should be able to
Total Air Flow 389 SCFM
operate on this range of flow
Air Flow Per Coil 389 SCFM
Standard Face Velocity 219.67 FPM
Altitude 0 FT
RVA: Provide hot water coil
Entering Dry Bulb 57 °F
with a capacity of 7.8 KW as
Leaving Dry Bulb 96.95 °F
specified in drawing M107 in
Air Pressure Drop 0.02 inWG
the contract document
Total Capacity 16.97 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 1.73 GPM
Fluid Velocity 2.06 FPS
Fluid Pressure Drop 1.14 ftWG
Notes
-52-
17/05/2021 MADOK MANUFACTURING INC. Page 6 of 13
-53-
17/05/2021 MADOK MANUFACTURING INC. Page 7 of 13
Hot Water Coil Report
Coil Data
Model Number 620F1-15X17-1010R511
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 1
Number Of Feeds 1
Fins Per Inch 10
Supply Connection Size 1/2"
Return Connection Size 1/2"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 40.45 ft²
Connection Type MPT
RVA: the max flow is 336 L/s
Casing Material Galvanized Steel 16 gauge
(712 CFM) and the minimum
Coil Weight 26.88 lb
flow is 244 L/s (517 CFM) as
specified in the contract drawing
Air Data M107, the coil should be able to
Total Air Flow 336 SCFM operate on this range of flow
Air Flow Per Coil 336 SCFM
Standard Face Velocity 189.74 FPM
Altitude 0 FT
RVA: Provide hot water coil
Entering Dry Bulb 57 °F
with a capacity of 7.8 KW as
Leaving Dry Bulb 98.73 °F
specified in drawing M107 in
Air Pressure Drop 0.02 inWG
the contract document
Total Capacity 15.31 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 1.56 GPM
Fluid Velocity 1.86 FPS
Fluid Pressure Drop 0.94 ftWG
Notes
-54-
17/05/2021 MADOK MANUFACTURING INC. Page 8 of 13
-55-
17/05/2021 MADOK MANUFACTURING INC. Page 9 of 13
Hot Water Coil Report
Coil Data
Model Number 620F1-15X17-1010R511
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 1
Number Of Feeds 1
Fins Per Inch 10
Supply Connection Size 1/2"
Return Connection Size 1/2"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 40.45 ft²
Connection Type MPT
Casing Material Galvanized Steel 16 gauge
Coil Weight 26.88 lb
Air Data
Total Air Flow 868 SCFM
Air Flow Per Coil 868 SCFM
Standard Face Velocity 490.16 FPM
Altitude 0 FT
Entering Dry Bulb 57 °F
Leaving Dry Bulb 87.51 °F
Air Pressure Drop 0.09 inWG
Total Capacity 28.91 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 2.95 GPM
Fluid Velocity 3.52 FPS
Fluid Pressure Drop 3.1 ftWG
Notes
-56-
17/05/2021 MADOK MANUFACTURING INC. Page 10 of 13
-57-
17/05/2021 MADOK MANUFACTURING INC. Page 11 of 13
Hot Water Coil Report
Coil Data
Model Number 620F1-15X17-1010R511
Coil Quantity 1
Finned Height 15 In
Finned Length 17 In
Rows Deep 1
Number Of Feeds 1
Fins Per Inch 10
Supply Connection Size 1/2"
Return Connection Size 1/2"
Tube Material Copper - 0.020
Tube Diameter 5/8
Fin Material Aluminum 0.01
Fin Surface Corrugated
Face Area 1.77 ft²
External Surface Area 40.45 ft²
Connection Type MPT
RVA: the max flow is 341 L/s
Casing Material Galvanized Steel 16 gauge
(722.92 CFM) and the minimum
Coil Weight 26.88 lb
flow is 243 L/s (115CFM) as
specified in the contract drawing
Air Data M107, the coil should be able to
Total Air Flow 341 SCFM operate on this range of flow
Air Flow Per Coil 341 SCFM
Standard Face Velocity 192.56 FPM
Altitude 0 FT
RVA: Provide hot water coil
Entering Dry Bulb 57 °F
with a capacity of 7.8 KW as
Leaving Dry Bulb 98.55 °F
specified in drawing M107 in
Air Pressure Drop 0.02 inWG
the contract document
Total Capacity 15.47 MBH
Fluid Data
Fluid Type Water
Fluid Ratio 0%
Entering Fluid Temp 160 °F
Leaving Fluid Temp 140 °F
Fluid Flow Rate(Per Coil) 1.58 GPM
Fluid Velocity 1.88 FPS
Fluid Pressure Drop 0.96 ftWG
Notes
-58-
17/05/2021 MADOK MANUFACTURING INC. Page 12 of 13
-59-
17/05/2021 MADOK MANUFACTURING INC. Page 13 of 13
24AHA SERIES
14 SEER CONDENSING UNIT
R-410A REF.
ACCESSORIES INCLUDED:
-60-
24AHA4
Performance Series Air Conditioner
with Puron Refrigerant
1-1/2 to 5 Nominal Tons
Lorem ipsum
Product Data
TABLE OF CONTENTS
-61-
Specifications subject to change without notice.
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 11 12 13
N N A A A/N N N N A/N A/N A/N N N
2 4 A H A 4 1 8 A 0 0 3 0
Product Product Product Major Minor
Series Family Type Series SEER Variations Open Open Voltage Series
3=208/
H= Cooling Capacity 230-1
24 = AC A = AC Horizontal 4 = 14 A= 0 = Not 0 = Not 5=208/ 0, 1, 2...
Discharge SEER Standard Defined Defined 230-3
6=460/3
PHYSICAL DATA
UNIT SIZE-SERIES 18-30 24-30 30-30 36-30, 50, 60 48-30, 50, 60 60-30, 50, 60
Charge lb (kg) 6.40 (2.90) 6.50 (2.95) 8.60 (3.90) 8.90 (4.04) 9.00 (4.08) 10.60 (4.81)
Cond Coil
Face Area (Sq ft) 7.3 7.3 12.1 12.1 12.1 14.1
Rows 2 2 2 2 2 2
Circuits 3 3 3 3 3 4
Liquid 3/8
* Units are rated with 25 ft. (7.6 m) of lineset length. Review the VAPOR LINE SIZING AND COOLING CAPACITY LOSS section when using other lineset sizes and lengths of
lineset.
Note: Review the unit’s Installation Instructions for proper installation guidance.
Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
2
-62-
Specifications subject to change without notice. 24AHA4-06PD
REFRIGERANT PIPING LENGTH LIMITATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengths for Cooling Only Systems with Puron Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between the indoor and
outdoor units. Review “Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit,” for the liquid line sizing and maximum
lengths.
Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit
048
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 --
Puron
060
AC with 3/8 3/8 250* 250* 250* 225* 190 150 110 -- --
Puron
1/4 30 -- -- -- -- -- -- --
030
AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250*
Puron
3/8 250* 250* 250* 250* 250* 250* 250* 250*
036 5/16 225* 250* 250* 250* 250* 250* 250* 250*
AC with 3/8
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
048
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
Puron
060
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
Puron
-63-
Total equivalent length accounts for losses due to elbows or fitting. See “LONG-LINE APPLICATIONS,” for details.
-- = outside acceptable range
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The LONG-LINE APPLICATIONS
factory charge for 3/8” lineset 9 oz (266.16 g). When using other An application is considered Long-Line, when the refrigerant level in
length or diameter liquid lines, charge adjustments are required per the the system requires the use of accessories to maintain acceptable
REFRIGERANT CHARGE ADJUSTMENTS table. refrigerant management for systems reliability. See ACCESSORY
Charging Formula: USAGE GUIDELINES on page 7 for the required accessories.
[(Lineset oz/ft x total length) – (factory charge for lineset)] = Defining a system as long-line depends on the liquid line diameter,
charge adjustment actual length of the tubing, and vertical separation between the indoor
and outdoor units.
Example 1: System has 15 ft of line set using existing 1/4 “liquid line.
What charge adjustment is required? For air conditioner systems, the “AC WITH PURON
REFRIGERANT LONG-LINE DESCRIPTION ft (m)” table shows
Formula:
when an application is considered long-line.
(.27 oz/ft x 15ft) – (9 oz) = (4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the
charge adjustment?
Formula:
(.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
LIQUID LINE SIZE UNITS ON SAME LEVEL - FT (M) OUTDOOR BELOW INDOOR - FT (M) OUTDOOR ABOVE INDOOR
(IN. OD) - FT (M)
1/4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 (53.3)
5/16 120 (36.6) 50 (15.2) vertical or 120 (36.6) total 120 (36.6)
4
-64-
Specifications subject to change without notice. 24AHA4-06PD
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
LONG LINE APPLICATION: An application is considered “long- The maximum vertical separation is 200 ft. (60.96 m) when the
line” when the total equivalent tubing length exceeds 80 ft. (24.4 m) or outdoor unit is above the indoor unit, and up to 80 ft. (24.4 m) when
when there is more than 20 ft. (6.09 m) vertical separation between the the outdoor unit is below the indoor unit. Refer to the ACCESSORY
indoor and outdoor units. These applications require additional USAGE GUIDELINES on page 7 for required accessories. See the
accessories and system modifications for reliable system operation. The Long-line Application Guideline for required piping and system
maximum allowable total equivalent length is up to 250 ft. (76.2 m). modifications. Also, refer to the “Vapor Line Sizing and Cooling
Capacity Losses — Puron Refrigerant 1-Stage Air Conditioner
Applications” table for the vapor tube diameters based on the total
length to minimize the cooling capacity loss.
Vapor Line Sizing and Cooling Capacity Losses — Puron Refrigerant 1-Stage Air Conditioner Applications
MAXIMUM COOLING CAPACITY LOSS (%) TOTAL EQUIVALENT LINE LENGTH FT. (M)
UNIT LIQUID LINE VAPOR LINE
NOMINAL DIAMETERS 26-50 51-80 81-100 101-125 126-150 151-175 176-200 201-225 226-250
SIZE (BTUH) DIAMETERS (IN. OD)
(IN. OD) (7.9-15.2) (15.5-24.4) (24.7-30.5) (30.8-38.1) (38.4-45.7) (46.0-53.3) (53.6-61.0) (61.3-68.6) (68.9-76.2)
018 1/2 1 2 3 5 6 7 8 9 11
1 Stage 3/8 5/8 0 1 1 1 2 2 2 3 3
AC with
Puron 3/4 0 0 0 0 1 1 1 1 1
024 5/8 0 1 2 2 3 3 4 5 5
1 Stage 3/4 0 0 1 1 1 1 1 2 2
AC with 3/8
Puron 7/8 0 0 0 0 0 1 1 1 1
030 5/8 1 2 3 3 4 5 6 7 8
1 Stage 3/4 0 0 1 1 1 2 2 2 3
3/8
AC with
Puron 7/8 0 0 0 0 1 1 1 1 1
036 5/8 1 2 4 5 6 8 9 10 12
1 Stage 3/4 0 1 1 2 2 3 3 4 4
AC with 3/8
Puron 7/8 0 0 0 1 1 1 1 2 2
048 3/4 0 1 2 3 4 5 5 6 7
1 Stage 7/8 0 0 1 1 2 2 2 3 3
3/8
AC with
Puron 1 1/8 0 0 0 0 0 0 0 1 1
060 3/4 1 2 4 5 6 7 9 10 11
1 Stage 3/8 7/8 0 1 2 2 3 4 4 5 5
AC with
Puron 1 1/8 0 0 0 1 1 1 1 1 1
*Applications in this area may be long- line and may have height restrictions. See LONG-LINE APPLICATIONS on page 4.
24AHA4-06PD
-65-
Specifications subject to change without notice. 5
ELECTRICAL DATA
UNIT SIZE - OPER VOLTS* COMPR FAN MAX FUSE** OR
VOLTAGE, SERIES V/PH MCA CKT BRK AMPS
MAX MIN LRA RLA FLA
18-30 56.3 9.0 0.50 11.8 20
24-30 62.9 10.9 0.50 14.1 25
30-30 73.0 14.1 0.70 18.3 30
208/230/1 253 197
36-30 77.0 14.1 1.20 18.8 30
48-30 124.0 18.5 1.20 24.3 40
60-30 152.5 23.7 1.45 31.1 50
36-50 71.0 9.0 1.20 12.5 20
48-50 208/230/3 253 197 83.1 13.7 1.20 18.3 30
60-50 110.0 15.9 1.45 21.4 35
36-60 38.0 5.6 0.60 7.6 15
48-60 460/3 506 414 41.0 6.2 0.60 8.4 15
60-60 52.0 7.1 0.80 9.7 15
LEGEND:
FLA - Full Load Amps * Permissible limits of the voltage range at which the unit operates satisfactorily
HACR - Heating, Air Conditioning, Refrigeration ** Time-Delay fuse.
LRA - Locked Rotor Amps Complies with 2007 requirements of ASHRAE Standards 90.1
NEC - National Electrical Code
RLA - Rated Load Amps (compressor)
NOTE: Sound pressure data vs distance converted using AHRI 275 Standard under certain environmental and layout assumptions.
CHARGING SUB−COOLING (TXV−TYPE EXPANSION DEVICE
UNIT SIZE-SERIES REQUIRED SUBCOOLING °F (°C)
18 12 (6.7)
24 12 (6.7)
30 12 (6.7)
36 8 (4.4)
48 12 (6.7)
60 10 (5.6)
-66-
NOTE: The conversion is accurate only when all the assumptions are correct.
208/230-3-60
203-1-60
460-3-60
1. Clearance Requirements:
X = YES a. Single Unit Applications:
0 = NO With the coil facing the wall, allow 6in (152mm) minimum
AIR clearance on the coil side, the coil end, and allow 20in (508mm)
minimum clearance on the fan side.
With the fan facing the wall, allow 8in (203mm) minimum
7 1/2” 2 1/2” clearance on the fan side, 6in (152mm) on the coil end and 20in
(508mm) minimum clearance on the coil side.
b. Multi Unit Applications:
4 3/16” Allow 24in (610mm) minimum clearance between the fan and the
coil sides of the multiple units. Arrange the units so the discharge
of one unit does not enter the inlet of the other unit. When two
units are installed end to end with the coil ends facing each other
allow 12in (305mm) in minimum clearance between the units.
11/16” c. Compressor End Service Clearance:
AIR Allow 24in (610mm) minimum clearance on the compressor end
when the units are stacked or there is less than 40 in. (1016mm) of
Fig. 2 — Dimensions clearance above the top of the unit. If there is 40 in. (1016mm) of
clearance above the unit and top panel is accessible for removal,
allow 8in (203mm) minimum clearance minimum clearance on the
compressor end for service.
8 1/16”
Fig. 3 — Dimensions
MINIMUM MOUNTING
UNIT SIZE
PAD DIMENSIONS
18,24 23” x 42”
-67-
30,36,48,60 24” x 50”
-68-
• TCG - Gross Cooling Capacity (1000 Btuh)