Brief overview Levelflex M FMP40 and FMP45
Brief overview
For quick and simple commissioning:
Æ
Installation → Page 14 ff.
The steps for installing the device and installation conditions (e.g. dimensions)
can be found here.
Æ
Wiring → Page 23 ff.
The device is virtually completely wired on delivery.
Æ
Display and Operating Elements → Page 29 ff.
An overview of the position of the display and operating elements can be found
here.
Æ
Commissioning via Display VU 331 Page 33 ff.
The set-up is supported by a special FieldCare DTM, which is delivered with
the device. Do not use the display VU 331 for set-up.
Æ
Commissioning via Operating Software FieldCare → Page 29 ff.
In the "Commissioning" section, you learn how to switch on the device and
check the functioning.
Æ
Fault Tracking / Trouble Shooting → Page 58 ff.
If faults occur during operation, use the checklist to localise the cause.
Here you can find measures you can take yourself to take remedial action
against the fault.
Æ
Index → Page 77 ff.
You can find important terms and keywords on the individual sections here.
Use the keyword index to find quickly and efficiently the information you need.
2
Levelflex M FMP40 and FMP45 Table of contents
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 4 8 Maintenance . . . . . . . . . . . . . . . . . . . . 55
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning and operation . . . . . . . . 4 9 Accessories . . . . . . . . . . . . . . . . . . . . . 56
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Notes on safety conventions and icons . . . . . . . . . . . 5
10 Trouble-shooting . . . . . . . . . . . . . . . . . 58
2 Identification . . . . . . . . . . . . . . . . . . . . 6 10.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . . 58
10.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 59
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 6 10.3 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 13 10.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . 13 10.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 13 10.6 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10.7 Contact addresses of Endress+Hauser . . . . . . . . . . . 64
3 Installation . . . . . . . . . . . . . . . . . . . . . 14
3.1 Quick installation guide . . . . . . . . . . . . . . . . . . . . . 14 11 Technical data . . . . . . . . . . . . . . . . . . . 65
3.2 Incoming acceptance, transport, storage . . . . . . . . . 15 11.1 Additional technical data . . . . . . . . . . . . . . . . . . . . 65
3.3 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.5 Turn housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12 Appendix . . . . . . . . . . . . . . . . . . . . . . . 74
3.6 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 22 12.1 Function and system design . . . . . . . . . . . . . . . . . . 74
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 23 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.1 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 25
4.3 Recommended connection . . . . . . . . . . . . . . . . . . 28
4.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 28
4.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 28
5 Operation . . . . . . . . . . . . . . . . . . . . . . 29
5.1 Display and operating elements . . . . . . . . . . . . . . . 29
5.2 Display and acknowledging error messages . . . . . . 31
6 Commissioning. . . . . . . . . . . . . . . . . . 32
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.2 Switching on the measuring device . . . . . . . . . . . . 32
6.3 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3
Safety instructions Levelflex M FMP40 and FMP45
1 Safety instructions
Hazardous areas
Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of this Operating Manual. Strict compliance with the
installation instructions and ratings as stated in this supplementary documentation is mandatory.
• Ensure that all personnel are suitably qualified.
• Observe the specifications in the certificate as well as national and local regulations.
4
Levelflex M FMP40 and FMP45 Safety instructions
Safety conventions
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned
Explosion protection
0
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous
area
- Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring
entering areas with the designation “explosion hazardous areas” must conform with the stated type
of protection.
.
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in
safe areas still require a certificate if their outputs run into explosion hazardous areas
Electrical symbols
% Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied
&
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied
)
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an
earth grounding system
*
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment
+
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice
5
Identification Levelflex M FMP40 and FMP45
2 Identification
2.1.1 Nameplate
The following technical data are given on the instrument nameplate:
Order Code:
Ser.-No.: IP68 / NEMA 6P
LN= PN=
Profibus PA
Foundation Fieldbus
Communication 90 … 253 V AC 3,5VA
variant and 10,5 … 32 V DC 1W
16 … 3 V DC 0,8W
supply voltage
4 … 20 mA HART 2-wire
4-wire
TA > 70°C : t >85°C
if modification Patents
X = see sep. label
Dat./Insp.: D01301-A
Reference to additional
safety-relevant documentation
L00-FMP4xxxx-18-00-00-en-001
6
Levelflex M FMP40 and FMP45 Identification
30 Probe length:
Rope probes:
Options A, B, E, D, F:
1000mm-35000mm/40in-1378in
Option C:
35in-1378in
The price is based on 1000mm
A ..... mm, rope 4mm, 316
B ..... mm, rope 6mm, 316
E ..... mm, rope 6mm, PA > steel
The price is based on inch
C ..... inch rope 1/6", 316
D ..... inch, rope 1/4", 316
F ..... inch, rope 1/4", PA > steel
Rod probes:
Options K, L, 1, 2, M, N:
300mm-4000mm/12in-157in
Options P, R, 3, 4:
300mm-2000mm/12in-80in
The price is based on 100mm
K ..... mm, rod 16mm, 316L
L ..... mm, coax, 316L
P ..... mm, rod 6mm, 316L
The price is based on inch
M ..... inch, rod 16mm, 316L
N ..... inch, coax, 316L
R ..... inch, rod 6mm, 316L
Y Special version
40 O-ring Material:
2 Viton
3 EPDM
4 Kalrez
9 Special version
7
Identification Levelflex M FMP40 and FMP45
EN-Flanges
CFJ DN40 PN25/40 B1, 316L
CGJ DN50 PN25/40 B1, 316L
CMJ DN80 PN10/16 B1, 316L
CSJ DN80 PN25/40 B1, 316L
CQJ DN100 PN10/16 B1, 316L
CTJ DN100 PN25/40 B1, 316L
CWJ DN150 PN10/16 B1, 316L
CXJ DN200 PN16 B1, 316L
ANSI-Flanges
ACJ 1-1/2" 150lbs RF, 316/316L
ADJ 1-1/2" 300lbs RF, 316/316L
AEJ 2" 150lbs RF, 316/316L
AFJ 2" 300lbs RF, 316/316L
ALJ 3" 150lbs RF, 316/316L
AMJ 3" 300lbs RF, 316/316L
APJ 4" 150lbs RF, 316/316L
AQJ 4" 300lbs RF, 316/316L
AWJ 6" 150lbs RF, 316/316L
A3J 8" 150lbs RF, 316/316L
JIS-Flanges
KDJ 10K 40A RF, 316L
KEJ 10K 50A RF, 316L
KLJ 10K 80A RF, 316L
KPJ 10K 100A RF, 316L
YY9 Special version
70 Operation:
1 w/o display, via communication
2 4-line display VU331
3 Prepared for FHX40, remote display (Accessory)
9 Special version
80 Remote electronics:
1 Compact, basic version
2 Temp. separator, 400mm
3 Remote, cable 3m
9 Special version
8
Levelflex M FMP40 and FMP45 Identification
mm
9
Identification Levelflex M FMP40 and FMP45
20 Process temperature:
A -200...+280 °C/-328...+536 °F (XT)
B -200...+400 °C/-328...+752 °F (HT)
Y Special version
30 Probe:
Rod probe:
300mm-4000mm/12in-157in
The price is based on 100mm
K ..... mm, rod 16mm, PTFE > 316L
The price is based on inch
M ..... inch, rod 16mm, 316L
Rope probe:
1000mm-35000mm/40in-1378in
The price is based on 1000mm
A ..... mm, rope 4mm, 316
The price is based on inch
C ..... inch, rope 1/6", 316
Coax probe:
300mm-4000mm/12in-157in
The price is based on 100mm
L ..... mm, coax, 316L
The price is based on inch
N ..... inch, coax, 316L
Y Special version
10
Levelflex M FMP40 and FMP45 Identification
EN-Flanges
CRJ DN50 PN10-40 B1, 316L
C1J DN50 PN64 B1, 316L
C2J DN50 PN100 B1, 316L
CSJ DN80 PN10-40 B1, 316L
C3J DN80 PN63 B1, 316L
C4J DN80 PN100 B1, 316L
CHJ DN100 PN10/16 B1, 316L
CTJ DN100 PN25/40 B1, 316L
C5J DN100 PN63 B1, 316L
C6J DN100 PN100 B1, 316L
ANSI-Flanges
AFJ 2" 150lbs RF, 316/316L
ARJ 2" 300/600lbs RF, 316/316L
A1J 2" 1500lbs RF, 316/316L
AGJ 3" 150lbs RF, 316/316L
ASJ 3" 300/600lbs RF, 316/316L
A2J 3" 1500lbs RF, 316/316L
AHJ 4" 150lbs RF, 316/316L
ATJ 4" 300lbs RF, 316/316L
A3J 4" 600lbs RF, 316/316L
A4J 4" 900lbs RF, 316/316L
A5J 4" 1500lbs RF, 316/316L
JIS-Flanges
KFJ 10K 50A RF, 316L
KGJ 10K 80A RF, 316L
KHJ 10K 100A RF, 316L
K3J 63K 50A RF, 316L
K4J 63K 80A RF, 316L
K5J 63K 100A RF, 316L
Y Special version
60 Operation:
1 w/o display, via communication
2 4-line display VU331
3 Prepared for FHX40, remote display (Accessory)
9 Special version
70 Remote electronics:
1 Compact, basic version
3 Remote, cable 3m
9 Special version
80 Housing:
A F12 Alu, coated IP68 NEMA6P
C T12 Alu, coated IP68 NEMA6P, separate conn. compartment
B F23 316L IP68 NEMA6P
D *T12 Alu, coated IP68 NEMA6P + OVP, separate conn. compartment,
OVP = overvoltage protection
Y Special version
11
Identification Levelflex M FMP40 and FMP45
mm
12
Levelflex M FMP40 and FMP45 Identification
13
Installation Levelflex M FMP40 and FMP45
3 Installation
3.1.1 FMP40
AF 60
3
60
max. torque
20 Nm 1
¾"
1
AF 50
Allen key
4 mm / 0.1"
50
max. torque
5 Nm
L00-FMP4xxxx-17-00-00-en-029
14
Levelflex M FMP40 and FMP45 Installation
3.1.2 FMP45
Turn housing
The housing can be turned 350°
in order to simplify access to the
display and the terminal compartment
2
Caution!
Use only the
threaded boss ???
AF 60 3
60
max. torque 1
see table
L00-FMP45xxx-17-00-00-en-003
3.2.2 Transport
" Caution!
Follow the safety instructions and transport conditions for instruments of more than
18 kg.
Do not lift the measuring instrument by its probe rod in order to transport it.
3.2.3 Storage
Pack the measuring instrument so that is protected against impacts for storage and transport. The
original packing material provides the optimum protection for this.
The permissible storage temperature is -40 °C…+80 °C.
15
Installation Levelflex M FMP40 and FMP45
3.3.1 Dimensions
Housing dimensions
Dimensions for the process connection and the probe type see Page 18.
max. 110 65 78
ENDRESS+HAUSER
Ø 129
150
F12 housing
(Aluminium)
85
L00-F12xxxx-06-00-00-en-001
max. 100 94 65 78
ENDRESS+HAUSER
Ø 129
85
L00-T12xxxx-06-00-00-en-001
max. 94 104
40
Ø 129
150
F23 housing
(316L)
L00-F23xxxx-06-00-00-en-001
16
Levelflex M FMP40 and FMP45 Installation
option: option:
distance sleeve remote electronic
88
123
88
4 x Ø 8,5
2765
400
Ø 60,3
270...310
112
Ø 76
Ø 76
Ø 67,8
68
reference point of
measurement
25
25
rope:
Ø 4 mm/0.16”
or
Ø 6 mm/0.24”
or
Ø 8 mm/0.32”, coated PA
internal thread:
150
L00-FMP4xxxx-06-00-00-en-007
17
Installation Levelflex M FMP40 and FMP45
option:
remote electronic
88
123
88
4 x Ø 8,5
2765
112
Ø 76
HT 400 °C XT 280 °C
Threaded connection Flange DN 50…100 Threaded connection Flange DN 50…100
G 1 ½ (1 ½BSP) or equivalent G 1 ½ (1 ½BSP) or equivalent
or 1 ½ NPT or 1 ½ NPT
Ø 60
Ø 60
Ø 60
Ø 60
338
SW 60 SW 60
311
262
235
Ø 90 Ø 90
159
159
Ø 90 Ø 90
132
132
reference point of
measurement
25
25
rope:
Ø 4 mm/0.16”
150
Ø 16/0.63”
Ø 42,4/1.67”
Ø 22/0.87”
L00-FMP45xxx-06-00-00-en-001
18
Levelflex M FMP40 and FMP45 Installation
3.4 Installation
! Note!
If one of these conditions is not met, the interface level measurement is not possible!
3.4.2 Installation
• Coaxial probes may be mounted directly into the tank.
• Rope and Rod probes have to be mounted into a bypass or stilling well
• For the use of any probes into stilling wells it has to be made sure that the stilling well or bypass
is perforated in a way which allows the product level in the inner part of the stilling well to adjust
to the outer level.
• The diameter of the stilling well / bypass should not exceed DN150 / 6” and not be smaller than
DN 50 / 2”
For a bypass, the dimensions of the following diagram should be kept:
recommendation min.
200 mm / 8”
100 %
recommendation min.
200 mm / 8”
0%
L00-FMP4xxxx-17-00-00-en-062
19
Installation Levelflex M FMP40 and FMP45
HT 400 °C
XT 280 °C
high temperature version
(type of probe B)
extended temperature version
(type of probe A) MAX
tank insulation
MAX
tank insulation
L00-FMP45xxx-17-00-00-en-001
HT 400 °C
XT 280 °C
high temperature version
(type of probe B)
extended temperature version
(type of probe A) MAX
tank insulation
MAX
tank insulation
L00-FMP45xxx-17-00-00-en-002
20
Levelflex M FMP40 and FMP45 Installation
65 78
wall
ENDRESS+HAUSER
Levelflex M
Ø 129
150
150
85
88
52
123
1
88
4 x Ø 8,5
94
2765
65 78
Ø 129
ENDRESS+HAUSER
Levelflex M
150
pipe
5
≥7
Note min.
bend radius!
190
max. 80
85 1
min. 30
96
112
52
Ø 76
94
L00-FMP4xxxx-17-00-00-en-015
! Note!
The connection tube cannot be disassembled at these points (1).
With remote electronics, for FMP40 temperatures up to 150 °C (302 °F) and for FMP45
temperatures up to 280 °C (536 °F) or 400 °C (752 °F) are permitted at the process connection
depending on the instrument version.
The ambient temperature for the connecting line (2) between the probe and electronics can be max.
105 °C.
The version with remote electronics consists of the probe, a connecting tube and the housing. If
they are ordered as a set, they are assembled on delivery.
21
Installation Levelflex M FMP40 and FMP45
2 2
1 1
90° 90°
allen key
4 mm/0.1”
L00-FMP41Cxx-17-00-00-de-002
22
Levelflex M FMP40 and FMP45 Wiring
4 Wiring
Caution!
" Before connection please note the following:
● The power supply must be identical to the data on the
nameplate (1). ENDRESS+HAUSER Made in Germany
LEVELFLEX-M D-79689 Maulburg
● Switch off power supply before connecting up the device. Order Code:
1 Ser.-No.: IP68 / NEMA 6P
LN= PN=
● Connect Equipotential bonding to transmitter Profibus PA
Foundation Fieldbus
ground potential.
2
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
7
-
On devices supplied with a certificate, the explosion protection
is designed as follows: 8
● Housing F12/F23 - EEx ia:
Power supply must be intrinsically safe (not for dust-Ex).
● The electronics and the current output are galvanically
separated from the probe circuit.
●
ES
-
communications signal (HART).
6
● Make connection (see pin assignment). 4
● Re-insert terminal module.
● Tighten cable gland (6). Max. torque 10...12 Nm!
● Tighten screws on cover plate (4).
● Insert display if fitted.
●
5
Screw on housing cover (2).
(on dust-Ex torque ≈ 40 Nm).
● Switch on power supply.
DC AC / DC
7
0...20mA
1 2 3 4
Sealed terminal
compartment
7
test sockets
(output current)
plant plant
1 2 3 4 ground 5 6 1 2 ground Note!
L- L+ I+ I- I+ I- L1/L+ N/L- If 4-wire for dust-Ex-applications is used,
the current output is intrinsically save.
2-wire-version 4-wire-version
L00-FMP41Cxx-04-00-00-en-001
23
Wiring Levelflex M FMP40 and FMP45
"
Caution!
Before connection please note the following:
● The power supply must be identical to the data on the
nameplate (1). ENDRESS+HAUSER Made in Germany
LEVELFLEX-M D-79689 Maulburg
● Switch off power supply before connecting up the device. Order Code:
1 Ser.-No.: IP68 / NEMA 6P
LN= PN=
● Connect Equipotential bonding to transmitter Profibus PA
Foundation Fieldbus
ground terminal (7) before connecting up the device. 90 … 253 V AC 1VA
10,5 … 32 V DC 1W
16 … 3 V DC 0,8W
● Tighten the locking screw (8): 4 … 20 mA HART 2-wire
4-wire
TA > 70°C : t >85°C
if modification
It forms the connection between the probe and the housing X = see sep. label
Dat./Insp.:
Patents
D01301-A
ground potential.
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland. 2
-
used. Use a screened cable when working with a superimposed
communications signal (HART). 8
power
1 2 3 4
test sockets
(output current)
plant
1 2 3 4 ground
L- L+ I+ I-
2-wire-version
L00-FMP41Cxx-04-00-00-en-002
24
Levelflex M FMP40 and FMP45 Wiring
Terminal compartment
Three housings are available:
• Aluminium housing F12 with additionally sealed terminal compartment for:
– standard,
– EEx ia.
• Aluminium housing T12 with separate terminal compartment for:
– standard,
– EEx e,
– EEx d
– EEX ia (with overvoltage protection).
• Stainless steel 316L housing F23 for:
– standard,
– EEx ia.
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment.
1 2 3 4
1 2 3 4 1 2 3 4
sealed terminal
compartment
L00-FMR2xxxx-04-00-00-en-019
The instrument data are given on the nameplate together with important information regarding the
analog output and voltage supply. Housing orientation regarding the wiring see "Turn housing" on
Page 22.
Load HART
Minimum load for Hart communication: 250 Ω
Cable entry
Cable gland: M20x1.5
Cable entry: G ½ or ½ NPT
Supply voltage
HART, 2-wire
The following values are the voltages across the terminals directly at the instrument:
25
Wiring Levelflex M FMP40 and FMP45
HART 4 mA 16 V 36 V
standard
20 mA 7.5 V 36 V
4 mA 16 V 30 V
EEx ia
20 mA 7.5 V 30 V
EEx em 4 mA 16 V 30 V
EEx d 20 mA 11 V 30 V
DC 10.5...32 V 600 Ω
AC 85...250 V 600 Ω
Power consumption
min. 60 mW, max. 900 mW
Current consumption
Current
Current
Communication consumption
consumption
Power consumption
PROFIBUS-PA max. 11 mA —
Overvoltage protection
If there is the risk of differences in potential forming when installing the Levelflex M to measure the
level of flammable liquids, the device can be fitted with a T12 housing and integrated overvoltage
protection (600 V gas tube surge arrester), see Ordering structure on Page 6. This overvoltage
protection meets the requirements of DIN EN 60079-14, test standard 60060-1, and also protects
the device (10 kA, impulse 8/20 µs).
26
Levelflex M FMP40 and FMP45 Wiring
4...20 mA
ENDRESS + HAUSER
RMA 422 RMA422
RN221N
1 2 3 4
- FieldCare
Commubox
FXA191
L00-FMP4xxxx-04-00-00-yy-001
DC power supply
unit
or
PLC
4...20 mA
³ 250 W
1 2 3 4
- FieldCare
Commubox
FXA191
L00-FMP4xxxx-04-00-00-en-002
" Caution!
If the HART communication resistor is not built into the supply unit and the HART interface is to
be used, it is necessary to insert a communication resistor of 250 Ω into the 2-wire line.
27
Wiring Levelflex M FMP40 and FMP45
1 1
L00-FMP41Cxx-17-00-00-en-003
" Caution!
In Ex applications, the instrument must only be grounded on the sensor side. Further safety
instructions are given in the separate documentation for applications in explosion hazardous areas.
28
Levelflex M FMP40 and FMP45 Operation
5 Operation
END
Order MICR
RES
S+HA
OPIL
Ser.-NoCode:
.: OT USE
II R
Messbe
Measur reich
ing
range
LCD
U 16...36 max.
4...20 20
Maulburg
mAV DC
m
IP
65
T
Made in Germany
A >70°C
: t
>85°C
ENDRESS + HAUSER
– + E
Symbols 3 keys
L00-FMxxxxxx-07-00-00-en-001
" Caution!
For the Interface version of Levelflex FMP4x, the display unit VU 331 is inteded to show the
measurement values only; The set-up should be done using the special FieldCare DTM which
comes with the device.
Sybmols Meaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol
flashes, this indicates a warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked, i.e. if no input is possible.
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART,
PFOFIBUS-PA or Foundation Fieldbus is in progress.
29
Operation Levelflex M FMP40 and FMP45
Key(s) Meaning
" Caution!
For the Interface version of Levelflex FMP4x, the display unit VU 331 is inteded to show the
measurement values only; The set-up should be done using the special FieldCare DTM which
comes with the device.
30
Levelflex M FMP40 and FMP45 Operation
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the local
display. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between two types of error:
• A (Alarm):
Instrument goes into a defined state (e.g. MAX 22 mA)
Indicated by a constant symbol.
(For a description of the codes see Page 59)
• W (Warning):
Instrument continue measuring, error message is displayed.
Indicated by a flashing symbol.
(For a description of the codes see Page 59)
• E (Alarm / Warning):
Configurable (e.g. loss of echo, level within the safety distance)
Indicated by a constant/flashing symbol.
(For a description of the codes see Page 59)
⇒
ENDRESS + HAUSER
– + E
Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique error code is
also output. A description of the error codes is given on Page 59.
• The "diagnostics" (0A) function group can display current errors as well as the last errors that
occurred.
• If several current errors occur, use O or S to page through the error messages.
• The last occurring error can be deleted in the "diagnostics" (0A) function group
with the function "clear last error" (0A2).
31
Commissioning Levelflex M FMP40 and FMP45
6 Commissioning
⇒
ENDRESS + HAUSER
– + E
⇓
Select the basic unit
(this message appears the first time the instrument is
switched on)
⇓
The current measured value is displayed
" Caution!
For the Interface version of Levelflex FMP4x, the display unit VU 331 is inteded to show the
measurement values only; The set-up should be done using the special FieldCare DTM which
comes with the device.
32
Levelflex M FMP40 and FMP45 Commissioning
L00-FMP4xxxx-19-00-00-de-002
L00-FMP4xxxx-19-00-00-de-004
Please use the flash buttoms to go through the basic calibration step by step.
33
Commissioning Levelflex M FMP40 and FMP45
L00-FMP4xxxx-19-00-00-de-006
! Note!
Each changed parameter has to be entered / confirmed by the Return key.
l00-L00-FMP4xxxx-19-00-00-de-007
34
Levelflex M FMP40 and FMP45 Commissioning
l00-L00-FMP4xxxx-19-00-00-de-008
! Note!
The table value of the dielectic constant may be different from the real product dielectric value.
! Note!
After entering the function “Dist. total level”, the parameter “upper blocking dist.” is adjusted to
the same value!
35
Commissioning Levelflex M FMP40 and FMP45
l00-fmp4xxxx-20-00-00-de-004
L00-FMP4xxxx-19-00-00-de-009
In case the function "probe length " "changed" has been selected, in the following steps the new,
actual probe length can be entered.
36
Levelflex M FMP40 and FMP45 Commissioning
L00-FMP4xxxx-19-00-00-de-012
L00-FMP4xxxx-19-00-00-de-013
37
Commissioning Levelflex M FMP40 and FMP45
L00-FMP4xxxx-19-00-00-de-013
" Achtung!
The usable measurement range is situated between the overall level and the probe length. Especially
for products / media of the upper layer with a dielectric value bigger than 4, the measurement range
can be diminished by adjusting the upper blocking distance.
More information about this topic please refer to function “upper blocking dist.” see page 47.
38
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
! Note!
The value of the dielectric constant can be identified also by activating the table of dielectric values
by clicking on the tank drawing. The listed dielectric values may vary from the real dielectric values
of the product.
! Note!
After entereing the "Dist. total level" function, the "upper blocking dist." function is automati-
cally set to the same value!
Endress+Hauser 39
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
40 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
! Note!
The usable measurement range extends between the overall level and the probe length.
For media of the upper product phase with a dielectric value > 4, the measurement range may have
to be restricted by increasing the upper blocking distance. The upper blocking distance is used to
eliminate the overall level echo.
Further Informations to the "blocking distance" see function "upper blocking dist." on page 47.
Selection:
• MIN (<= 3.6mA)
• MAX (22mA)
• hold
• user specific
Endress+Hauser 41
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
hold
user specific
If the instrument is in alarm state, the output is set to the value configured in "output on alarm"
(x mA).
" Caution!
This selection is available for HART devices only!
" Caution!
This function is available for HART devices only!
42 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
Selection:
• alarm
• hold
• ramp %/min
alarm
On echo loss, the instrument switches to alarm state after an adjustable "delay time". The output
response depends on the configuration set in "output on alarm".
hold
On echo loss, a warning is generated after a definable "delay time". Output is held.
Endress+Hauser 43
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
ramp %/min
On echo loss, a warning is generated after a definable "delay time". The output is changed towards
0% or 100% depending on the slope defined in "ramp %span/min".
Enter the size of the safety distance here. The default value is: 0.1 m.
44 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
Selection:
• alarm
• warning
alarm
Instrument enters the defined alarm state ("output on alarm"). The alarm message E651 -
"level in safety distance - risk of overspill" is displayed.
If the level drops out of the safety distance, the alarm warning disappears and the instrument starts
to measure again.
warning
Instrument displays a warning E651 - "level in safety distance - risk of overspill", but conti-
nues to measure. If the level leaves the safety distance, the warning disappears.
Endress+Hauser 45
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
Selection:
• modified
• not modified
! Note!
If "modified" was selected in the "probe length" function, the probe length is defined in the next
step.
The echo quality is the benchmark for measurement reliability. It describes the amount of reflected
energy and depends primarily on the following conditions:
• Dielectric constant of the medium
• probe type
• Distance between sensor and product
Low values increase the probability that the echo is lost through a change in measurement conditi-
ons, e.g. emulsion or high dampening of the upper product phase.
46 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
User input:
0...255 s
The default value depends on the selected application parameter "process cond.".
! Note!
The available measuring range is decreased by the value entered.
" Caution!
This function is available for HART devices only!
" Caution!
This user input is available for HART devices only!
Endress+Hauser 47
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
Selection:
• off minimum output -10% (3.8 mA for HART)
• on minimum output 0% (4 mA for HART)
" Caution!
This user input is available for HART devices only!
Selection:
• standard
• curr. turn down
• fixed current
standard
This selection displays the complete measuring range (0...100%) across the full current interval
(4...20 mA).
fixed current
Selecting this outputs a fixed current. The measured value is only transmitted using the HART sig-
nal. The current output value is set using the "fixed cur. value" function.
" Caution!
This selection is available for HART devices only!
48 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
User input:
3,8...20,5 mA
" Caution!
This user input is available for HART devices only!
Selection:
• sim. off
• sim. volume
• sim. current (HART only)
sim. off
Simulation is switched off.
Endress+Hauser 49
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
sim. level
Enter the level value in "simulation value".
The functions
• measured value
• measured level
• output current" - only with HART instruments!
follow the entered values.
sim. volume
Enter the volume value in "simulation value".
The functions
• measured value
• output current" - only with HART instruments!
follow the entered values.
" Caution!
This function is available for HART devices only!
Selection:
• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Katakana (japanese)
50 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
Dependence
All texts are changed.
" Caution!
This function is not visualised in Commuwin II!
User input:
3...9999 s
Selection:
• decimal
• ft-in-1/16"
decimal
The measured value is given in decimal form in the display (e.g. 10.70%).
ft-in-1/16"
The measured value is given in the display in this format (e.g 5'05-14/16").
This option is only possible for "distance unit" - "ft" and "in"!
Selection:
•x
• x.x
• x.xx
• x.xxx
Selection:
•.
•,
.
The decimal place is separated by a point.
,
The decimal place is separated by a comma.
Endress+Hauser 51
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the local dis-
play. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between two types of error:
• A (Alarm):
Instrument goes into a defined state (e.g. MAX)
Indicated by a constant symbol.
(For a description of the codes see system error messages)
• W (Warning):
Instrument continue measuring, error message is displayed.
Indicated by a flashing symbol.
(For a description of the codes, see system error messages)
• E (Alarm / Warning):
Configurable (e.g. loss of echo, level within the safety distance)
Indicated by a constant/flashing symbol.
(For a description of the codes, see system error messages)
Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique error code is
also output. A description of the error codes is given by system error messages.
• The "diagnostics" function group can display current errors as well as the last errors that occur-
red.
• If several current errors occur, use O or S to page through the error messages.
The last occurring error can be deleted in the "diagnostics" function group with the function "clear
last error".
Selection:
• keep
• erase
" Caution!
Generally, no reset is necessary.
52 Endress+Hauser
Levelflex M FMP40 and FMP45 7 Description of Instrument Functions
"unlock parameter":
A value <> 100 for HART (e.g. 99) must be entered in "unlock parameter" in the "diagnostics"
function group. The lock is shown on the display by the symbol and can be released again either
via the display or by communication.
"unlock parameter":
By entering the unlock parameter (on the display or via communication)
100 = for HART devices
" Caution!
Changing certain parameters such as all sensor characteristics, for example, influences numerous
functions of the entire measuring system, particularly measuring accuracy. There is no need to
change these parameters under normal circumstances and consequently, they are protected by a
special code known only to the E+H service organization. Please contact Endress+Hauser if you
have any questions.
Selection:
• not modified
• modified
Endress+Hauser 53
7 Description of Instrument Functions Levelflex M FMP40 and FMP45
User input:
• 16 alphanumeric characters for HART instruments (8 using the HART universal command)
Display:
xx: hw-version
yy: sw-version
zz: sw-revision
prot: protocoll type (e.g. HART)
Selection:
•m
• ft
• mm
• inch
Dependence
m, mm: "format display" can only be "decimal".
! Note!
The parameter up- / download are not possible with the Levelflex M interface version.
54 Endress+Hauser
Levelflex M FMP40 and FMP45 Maintenance
8 Maintenance
The Levelflex M measuring instrument requires no special maintenance.
Exterior cleaning
When cleaning the Levelflex M, always use cleaning agents that do not attack the surface of the
housing and the seals.
Repairs
The Endress+Hauser repair concept assumes that the measuring devices have a modular design and
that customers are able to undertake repairs themselves. Spare parts are contained in suitable kits.
They contain the related replacement instructions. All the spare parts kits which you can order from
Endress+Hauser for repairs to the Levelflex M are listed with their order numbers on Page 60 ff.*.
* Excepted from this is the exchange of an electronics according to MVTFN0341. Please contact
Endress+Hauser Service for further information on service and spare parts.
55
Accessories Levelflex M FMP40 and FMP45
9 Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
Levelflex M.
EN
DR
Orde MIC ES
r
Se Code
RO S+H
r.-No : PIL AU
.: OT SE
II R
Me
Messbere
asur ich
ing
rang
U 16 e ma
4...20...36 x. 20
Maulburg
m
mAV DC
IP
65
T
Made in Germany
A >7
0°C
: t >8
5°C
L00-FMR2xxxx-00-00-06-en-001
56
Levelflex M FMP40 and FMP45 Accessories
Dimensions
Wall-mounting Pipe-mounting
(without mounting bracket) (mounting bracket and plate
supplied optionally,
s. product structure)
5
8,
0 Separate housing
15 FHX 40 (IP 65)
Micropilot M 122
180
160
Levelflex M
Prosonic M
80
EN
DR
Orde ES
r Co S+H
Se
r.-N de: AU
o.: SE
R
Me
Messberei
asuri ch
ng
U 16
ran
4...20...36
ge
ma
x. 20
Cable
Maulburg
m
mAV DC
EN
DR
ES TA >70°
IP
65
88
Made in Germany
Orde
r Co S+H C :
Se
r.-N de: AU t >85°C
o.: SE
Me
Messberei
asuri ch
ng
R
120
118
ran
U 16 ge
ma
4...20...36 x. 20
82
Maulburg
m
mAV DC
T
Made in Germany
A >7
0°C
96
: t
>8 5°C
3
6,
max. 80
min. 30
106
122
pipe
L00-FMxxxxxx-00-00-06-en-003
Approval:
A Nn-hazardous area
1 ATEX II 2 G EEx ia IIC T6, ATEX II 3D
S FM IS Cl.I Div.1 Gr.A-D
U CSA IS Cl.I Div.1 Gr.A-D
N CSA General Purpose
Cable length:
1 20m/65ft
Additional option:
A Basic version
B Mounting bracket, pipe 1"/ 2"
57
Trouble-shooting Levelflex M FMP40 and FMP45
10 Trouble-shooting
No
ok
No
ok
No Not ok
Not ok Yes
Check plug contact Connect the plug Ready
Display works?
of the display. correctly
No
ok
No
Yes Yes
Output current Not ok Correct the
Check cabling Current is ok? Ready
< 3.6 mA ? (2 wire) cabling
< 2.4 mA ? (4 wire) No
ok
No
ok
No
No
Contact E+H Service
Communication
via Service adapter Yes Yes
Check configuration Not ok Correct configuration
FXA 193 does not Communication ok? Ready
of COM port on PC
function
No
Contact E+H Service
Instrument
measures Yes Not ok Yes
Check basic setup Repeat Measurement ok?
incorrectly Ready
basic setup
No
ok
Proceed according
to section
'Trouble shooting’ in OM
L00-FMP4xxxx-19-00-00-en-010
58
Levelflex M FMP40 and FMP45 Trouble-shooting
A102 checksum error device has been powered off before data avoid emc problem;
general reset & new calibr. could be stored; exchange electronics
required emc problem;
E2PROM defect
W103 initialising - please wait E2PROM storage not yet finished wait some seconds; if warning
prevails, exchange electronics
A106 downloading please wait processing data download wait until warning disappears
A110 checksum error device has been powered off before data avoid emc problem;
general reset & new calibr. could be stored; exchange electronics
required. emc problem;
E2PROM defect
W153 initialising - please wait initialisation of electronics wait some seconds; if warning
prevails, power off device and
power on again
A160 checksum error device has been powered off before data avoid emc problem;
general reset & new calibr. could be stored; exchange electronics
required. emc problem;
E2PROM defect
A221 Probe pulse deviation from HF module or cable between HF module Check contacts on HF module
average values and electronics defective If fault cannot be eliminated:
Replace HF module
A251 Feedthrough Lost contact in the process feedthrough Replace process feedtrough
A261 HF cable defective HF cable defective or HF connector Check HF connector, replace cable
removed if defective
A275 Offset too high Temperature at the electronics too high or Check temperature, replace HF
HF module defective module if defective
W511 no factory basic setup is factory basic setup is deleted exchange electronics
present
E641 no usable echo echo lost due to application conditions check installation;
channel 1 clean probe (cf. Operating
check calibr. Instructions)
E651 level in safety distance - risk level in safety distance alarm will disappear as soon as level
of overspill leaves safety distance
59
Trouble-shooting Levelflex M FMP40 and FMP45
Spare parts Levelflex M FMP40 and FMP45 housing type F12 with a combined
connection compartment and electronics compartment
10
35 11
EN
D
Ord M REICR SS
er
Ser Cod OP +HA
.-N
o.:
e: ILO US
T E II R
Mes
Measber l
surineich ina
g ra rm
U 16
nge
max
Te
4...2 ...36 . 20
Maulburg
0m VD m
A C
IP
65
T
Made in Germany
A >70
°C
: t
>8 5°C
4
3
2
1
12 30 20
12
s
tecker h:
ax-S eic gen-
s Ko -Ber zo
n de im Ex i abge tische e
ziehe echsel) dass be osta r Sond eren).
bei Abodul W tellen, ine elektrzität) de er Entlefort
ung us pa
Acht .B. HF-Msicherz tecker keerte Ka füllen odtecker so s
tecker h:
(z ist ax-S (isoli rch Be ax-S ax-S eic gen-
Es Ko ng . du n Ko s Ko -Ber zo
em fladu (z.B ture ken! n de im Ex i abge tische e
Au folgt para fstec
er i Re au ziehe hsel) ss be osta r Sond eren).
Be eder g bei Ab ul Wec llen, da elektrzität) de Entle t
od uste ine pa er for
wi un
Acht .B. HF-Msicherz tecker keerte Ka füllen odtecker so
(z ist ax-S (isoli rch Be ax-S
Es Ko ng . du n Ko
em fladu (z.B ture ken!
Au folgt para fstec
er i Re au
Be eder
wi
ER
US
HA
S+
ES
DR
EN
31
40
L00-FMP41Cxx-00-00-06-xx-001
See the following pages for probe versions and spare parts for probes.
60
Levelflex M FMP40 and FMP45 Trouble-shooting
10 Housing
52013409 Housing F12, aluminium, coated, M20, metal
52013351 Housing F12, aluminium, coated, M20, metal
543120-0022 Housing F12, aluminium, G1/2
543120-0023 Housing F12, aluminium, NPT1/2
543120-0024 Housing F12, aluminium, M20
12 Set of screws
535720-9020 Set of screws for housing F12/T12
20 Cover
52005936 Cover F12/T12 aluminium, inspection glass, seal
517391-0011 Cover F12/T12 aluminium, coated, seal
30 Electronics
Electronic according to MVTFN0341 LEVELFLEX M, Ex, 2 Dr, HART - Please contact your
Endress+Hauser service.
31 HF module
52019780 HF module LEVELFLEX-M
40 Display
52005585 Display/operating module VU331
61
Trouble-shooting Levelflex M FMP40 and FMP45
Spare parts for Levelflex M FMP45 housing type T12 with separate connecting compart-
ment
25
35
10
11
EN
D
Ord MIC RES
er
Ser Cod RO S+H
.-N e: PIL AU
o.: OT SE
FM R
Mes
sb
R
Mea er
surineich
g ra
nge
U 16 max
4...2 ...36 . 20
30
Maulburg
0m VD m
A C
IP
65
T
Made in Germany
A >7
0°C
: t
>8 5°C
kers
-Stec h: n-
Koax Ex-Bereicgezogehe
des
hen el) im ss bei ab tatisc Sonde en).
i Abzie Wechs n, da elektros der tleer
ng be odul stelle ine pazität) er En fort
Achtu B. HF-Msicherzu tecker keerte Ka füllen odtecker so rs
tecke h:
(z. ist ax-S (isoli rch Be ax-S ax-S eic gen-
s Ko -Ber zo
12
Es Ko ng du
em fladu (z.B. turen Koken! n de im Ex i abge ische e
Au folgt para fstec
er i Re au ziehe hsel) ss be ostat r Sond eren).
Be eder ng bei Abodul Wecstellen, daine elektrzität) de er Entlefort
wi pa
Achtu B. HF-Msicherzu tecker keerte Ka füllen odtecker so
(z. ist ax-S (isoli rch Be ax-S
20
12 Es Ko ng du
em fladu (z.B. turen Koken!
Au folgt para fstec
er i Re au
Be eder
wi
S ER
AU
+H
SS
D RE
EN
40
31
L00-FMP41Cxx-00-00-06-xx-002
62
Levelflex M FMP40 and FMP45 Trouble-shooting
10 Housing
52006205 Housing T12, aluminium, M20, PEL, cover
543180-1023 Housing T12, aluminium, NPT1/2, PEL
12 Set of screws
535720-9020 Set of screws for housing F12/T12
20 Cover
52005936 Cover F12/T12 aluminium, inspection glass, seal
517391-0011 Cover F12/T12 aluminium, coated, seal
30 Electronics
Electronic according to MVTFN0341 LEVELFLEX M, Ex, 2 Dr, HART - Please contact your
Endress+Hauser service.
31 HF module
52019780 HF module LEVELFLEX-M
40 Display
52005585 Display/operating module VU331
63
Trouble-shooting Levelflex M FMP40 and FMP45
10.4 Return
The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g.
for repair or calibration:
• Remove all residue which may be present. Pay special attention to the gasket grooves and crevices
where fluid may be present. This is especially important if the fluid is dangerous to health, e.g.
corrosive, poisonous, carcinogenic, radioactive, etc.
• Always enclose a duly completed "Declaration of contamination" form (a copy of the “Declaration
of contamination” is included at the end of this operating manual). Only then can Endress
+Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/
155/EEC.
Additionally specify:
• An exact description of the application
• The chemical and physical characteristics of the product
• A short description of the error that occurred (specify error code if possible)
• If necessary, give the error code
10.5 Disposal
In case of disposal please seperate the different components according to their material consistence.
64
Levelflex M FMP40 and FMP45 Technical data
11 Technical data
11.1.1 Input
Measured variable The measured variable is the distance between a reference point (see Fig. on Page 18) and the
interface.
Subject to the input empty distance, the level is calculated.
11.1.2 Output
Signal on alarm Error information can be accessed via the following interfaces:
• Local display:
– Error symbol (see Page 29)
– Plain text display
• Current output
• Digital interface
Resolution • Digital: 1 mm
• analog: 0.03 % of the measuring range
65
Technical data Levelflex M FMP40 and FMP45
Influence of ambiente The measurements are carried out in accordance with EN 61298-3:
temperature • digital output (HART):
– average TK: 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C...+80 °C
2-wire
• Current output (additional error, in reference to the span of 16 mA):
– Zero point (4 mA)
average TK: 0.032 %/10 K, max. 0.35 % over the entire temperature range -40 °C...+80 °C
– Span (20 mA)
average TK: 0.05 %/10 K, max. 0.5 % over the entire temperature range -40 °C...+80 °C
4-wire
• Current output (additional error, in reference to the span of 16 mA):
– Zero point (4 mA)
average TK: 0.02 %/10 K, max. 0.29 % over the entire temperature range -40 °C...+80 °C
– Span (20 mA)
average TK: 0.06 %/10 K, max. 0.89 % over the entire temperature range -40 °C...+80 °C
Ambient temperature range Ambient temperature for the transmitter: -40 °C ... +80 °C (-40 °F … +176 °F)
The functionality of the LCD display may be limited for temperatures
Ta<-20 °C and Ta>+60 °C.
A weather protection cover should be used for outdoor operation if the instrument is exposed to
direct sunlight.
-40
-40 0 50 80 100 150 T [°C]
max. process connection temperature
L00-FMP40xxx-05-00-00-en-001
66
Levelflex M FMP40 and FMP45 Technical data
40 54 °C compact:
F23 housing
0
T2
-27
-33
-40
-60
-250 -200 -100 -40 0 80 200 300 400 T2 [°C]
tank insulation permitted process connection temperature
L00-FMP45xxx-05-00-00-en-002
T2 0
-20
-29
-40
-60
tank insulation -250 -200 -100 -40 0 80 200 280 T2 [°C]
permitted process connection temperature
L00-FMP45xxx-05-00-00-en-003
67
Technical data Levelflex M FMP40 and FMP45
Cleaning the probe Depending on the application, soilings or sediments can accumulate on the probe. A thin, even layer
only influences measurement slightly. Thick layers can dampen the signal and then reduce the
measuring range. Heavy, uneven build-up, adhesion e.g. through crystallisation, can lead to
incorrect measurement. In this case, we recommend that you use a non-contact measuring
principle, or check the probe regularly for soiling
! Note!
The medium temperature can be higher.
FMP45
The maximum permitted temperature at the process connection (see figure measuring point) is
determined by the process connection ordered:
350 350
300 300
250
200
FMP45 XT FMP45 HT
150
100
50
0
o o
-200
1C -100
2 C 03oC 100o
4 C 200o
5 C 300o
6 C 400o
7 C
-60oC 0oC 100oC 200oC 300oC 400oC
o
280 °C Temp. [ C]
L00-FMP45xxx-05-00-00-en-001
68
Levelflex M FMP40 and FMP45 Technical data
Part Materials
69
Technical data Levelflex M FMP40 and FMP45
Dielectric constant • With coax, rod or rope probe in bypass or stilling well: εr of the upper phase ≥ 1,4.
• Difference of DC between upper and lower phase: minimum 10.
• Total level constant
• minimum layer thickness ≥ 100 mm (> 3,8") for DC 2.
Weight
FMP45
Rod probe Rope probe Coax probe Rod probe Rope probe Coax probe
Weight with F12 or approx. 8.5 kg approx. 8.5 kg approx. 8.5 kg approx. 9.5 kg approx. 9.5 kg approx. 9.5 kg
T12 housing + + + + + +
approx. 1.6 kg/m approx. 0.1 kg/m approx. 3.5 kg/m approx. 1.6 kg/m approx. 0.1 kg/m approx. 3.5 kg/m
Probe length Probe length Probe length Probe length Probe length Probe length
+ + + + + +
Flange weight Flange weight Flange weight Flange weight Flange weight Flange weight
70
Levelflex M FMP40 and FMP45 Technical data
CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms
the instrument passing the required tests by attaching the CE-mark.
2 II 1/2 D IP6x, T 115 °C Output: EEx ia IIB G, H 4W, F12, Alu-cover XA168F
5(8) II 1/2 G, II 1/3 D (+WHG) EEx ia IIC T6 IP6x, T 82 °C B, D, F 2W, F12, HART, PA, FF XA172F
Telecommunication Fulfils "Part 15" of the FCC regulations for an "Unintentional Radiator". All probes meet the
requirements for a "Class A Digital Device".
In addition to this, all probes in metallic tanks meet the requirements for a "Class B Digital Device".
71
Technical data Levelflex M FMP40 and FMP45
Pressure Equipment Directive The FMP45 corresponds to the 97/23/EC Directive (Pressure Equipment Directive). It is a pressure
FMP45 accessory with a volume < 0.1 l, corresponding to Category I.
Conformity assessment was carried out as per Module A, the design as per EN 13445 and AD 2000
technical specifications. FMP45 is not suitable for use with unstable gases at nominal pressures
above 200 bar.
72
Levelflex M FMP40 and FMP45 Technical data
73
Appendix Levelflex M FMP40 and FMP45
12 Appendix
Stand-alone
• Power supply unit (2-wire).
• Operation only by FieldCare via Commubox FXA191.
PLC
- FieldCare
Commubox
FXA 191
transmitter power
supply unit
RMA422 operating and ENDRESS + HAUSER
ENDRESS + HAUSER
RMA 422
FXA191
or
DXR375
L00-FMP4xxxx-14-00-06-en-022
If the HART communication resistor is not installed in the supply device and HART protocol
communication is to be carried out, it is necessary to insert a ≥ 250 Ω communication resistor into
the 2-wire line.
12.1.2 Patents
This product may be protected by at least one of the following patents.
Further patents are pending.
• US 5,661,251 i EP 0 780 664
• US 5,827,985 i EP 0 780 664
• US 5,884,231 i EP 0 780 665
• US 5,973,637 i EP 0 928 974
74
Levelflex M FMP40 and FMP45 Appendix
75
Appendix Levelflex M FMP40 and FMP45
76
Levelflex M FMP40 and FMP45 Index
Index
A Return. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 RMA 422 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 RN 221 N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
C S
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Safety conventions and symbols . . . . . . . . . . . . . . . . . . . . . . 5
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Software history. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Commubox. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Commubox FXA 191 HART . . . . . . . . . . . . . . . . . . . . . . . 56 System error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Commuwin II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 T
T12 housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
D Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
declaration of conformity. . . . . . . . . . . . . . . . . . . . . . . . . . 13 Terminal compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 ToF Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Trouble-shooting instructions. . . . . . . . . . . . . . . . . . . . . . . 58
DXR 375. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
W
E Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Equipotential bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . 56
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31, 59 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Ersatzteile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Ex(-)approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Ex-Zulassung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
F
F12 housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
FHX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
FXA 191 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
FXA 193 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
G
Grundabgleich . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
H
HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25, 27
K
Key assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
N
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
O
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ordering structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
R
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Repairs to Ex-approved devices . . . . . . . . . . . . . . . . . . . . . 55
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
77
Levelflex M FMP40 and FMP45 Index
78
"CAJ?P?RGMLMDAMLR?KGL?RGML
$EARCUSTOMER
"ECAUSEOFLEGALDETERMINATIONSANDFORTHESAFETYOFOUREMPLOYEESANDOPERATINGEQUIPMENTWENEEDTHIS $ECLARATIONOF
CONTAMINATION WITHYOURSIGNATUREBEFOREYOURORDERCANBEHANDLED0LEASEINCLUDETHECOMPLETELYFILLEDINDECLARATIONWITHTHE
DEVICEANDTHESHIPPINGDOCUMENTSINANYCASE!DDALSOSAFETYSHEETSANDORSPECIFICHANDLINGINSTRUCTIONSIFNECESSARY
4YPEOFDEVICESENSOR 3ERIALNO
-EDIUMCONCENTRATION 4EMPERATURE 0RESSURE
#LEANEDWITH #ONDUCTIVITY 6ISCOSITY
5?PLGLEFGLRQDMPKCBGSKSQCBMARKTHEAPPROPRIATEHINTS
SAFE
0C?QMLDMPPCRSPL
!MKN?LWB?R?
#OMPANY #ONTACTPERSON
$EPARTMENT
!DDRESS 0HONE
&AXE
MAIL
9OURORDERNO
)HEREBYCERTIFYTHATTHERETURNEDEQUIPMENTHASBEENCLEANEDANDDECONTAMINATEDACCTOGOODINDUSTRIALPRACTICESANDISIN
COMPLIANCEWITHALLREGULATIONS4HISEQUIPMENTPOSESNOHEALTHORSAFETYRISKSDUETOCONTAMINATION
-OREINFORMATIONABOUTSERVICESANDREPAIRS
WWWSERVICESENDRESSCOM
www.endress.com/worldwide
BA327F/00/en/03.05
Nr. 52027874
CCS/FM+SGML 6.0/ProMoDo 52027874