Professional Documents
Culture Documents
9IS44056-1 IS IWC 720-730-740-750 (LX) Series EN 1206
9IS44056-1 IS IWC 720-730-740-750 (LX) Series EN 1206
12/06 -GB-
code. 9IS44056
IWC Series
IWC 720-730-740-750 (LX)
Electronic controllers for “ventilated” refrigeration units
KEYS AND LEDS
External
UP/AUX
• Scrolls through menu items
Defrost /ESC
• ESC (exit) function • ON for alarm active;
eco Reduced set
• Blinking when the reduced set is
aux
• Increases values • Manually enable • Blinking when the alarm is silenced on;
• Manual activation of defrost cycle (press and hold for • OFF for main set on;
auxiliary relay aux LED on display 2 seconds.) (see par. H33) Fans (IWC 730 and WHEN PRESENT)
comes on • ON for fans on; Function %RH
(if configured to do this, par. LIGHT • OFF for fans off; • ON for forcing on
H34=9) • Turns the light relay on • Otherwise blinking • OFF for normal operation
DOWN LED associated with the key comes on
• Scrolls through menu items (if configured to do this, Compressor Lock (LED associated with Lock
• Decreases values par. H34=2) • ON for compressor on; key)
• Programmable by parameter • Flashes if there is a delay, a pro- • ON for Lock on
(see par. H32) on/off tection, or activation is blocked; • OFF for Lock off
off
Set - press once on/ • Turns instrument on and off • Otherwise OFF;
set • Opens machine status menu and forces the associated relay *Manual defrost
Defrost
• Activates functions (if present) (LED associated with Defrost key)
• ON for defrosting on
• Confirms commands • ON for manual defrosting on
• Blinking when dripping
• Displays alarms (if active) • Otherwise OFF
- Press and hold Stand By
• Opens programming menu (LED associated with on/off key)
* if conditions for defrosting are not present or if OdO is not 0, the display will • ON for instrument off
blink and defrosting will not be performed • OFF for instrument on
and press the “UP” and “DOWN” keys to scroll the list of active
The Setpoint value appears on the display. To change the Setpoint alarms.
value, press the “UP” and “DOWN” keys within 15 seconds. d) When HACCP parameters have been enabled, there will be sub-
If you press the “set” key again, press the “fnc” key or allow folders under folder AL for this kind of message (see HACCP alarms
15 seconds to elapse, the last value displayed will be saved and the section).
label “SEt” will reappear on the display.
PROGRAMMING MENU
To access the programming menu, press and hold the “set” key • Press the “set” key for the selected
for more than 5 seconds. folder (‘dEF/dty’ in this example) to view
the first parameter in the folder. Use the
set
“UP” and “DOWN” keys to select the
• After pressing the ‘set’ key, the first
set required parameter.
folder in the menu will appear
• Press “set” to display the value of the
(e.g.: “CP” folder).
selected parameter and “UP” and
“DOWN” to modify the value.
set Once you have pressed the “set” key (or
• By pressing the ‘UP’ and ‘DOWN’ keys
15 seconds have elapsed), the new value
you can scroll through all the folders in
will appear and the display will show the value of the corresponding para-
the programming menu.
meter.
PASSWORDS
Access to parameter management can be restricted by means of • If the password PA1 is enabled (different
a password. The password can be enabled by setting parameter from 0), you will be asked to enter it.
set
PA1 in the ‘diS’ folder. The password is enabled if the value of Select the correct value using the UP and
DOWN keys and press ‘set’ to confirm.
parameter PA1 is different from 0.
• To access the “Programming” menu,
If the password is incorrect, the display will show the ‘PA1’ label again
press and hold the “set” key for more
and you will have to repeat the operation.
than 5 seconds.
set If specified, the access PASSWORD will be
requested.
At each level in both menus, if you press the “Defrost/ESC” key or allow 15 seconds to elapse, you will return to the level above
and the last value on the display will be saved.
HACCP ALARMS
HACCP models only
KEYBOARD LOCKING
The instrument includes a facility for disabling the keyboard: If the keyboard is locked, you can access the “Programming”
• Using the keys (pressing UP+DOWN simultaneously for Menu by pressing the “set” key”.
2 seconds; see KEYS AND LEDS)
• By programming the “Loc” parameter (see folder with “diS” The Setpoint can also be viewed.
label).
IWC 720-730-740-750 (LX) 2/7
FUNCTIONS
The following functions are available in the FnC folder (last folder visible from the programming menu, level 1) :
Function Function label ACTIVE Function label INACTIVE D.I. Key Function active indication
request defrost dEF dEF 1 1
reduced set OSP SP* 2 3 LED ON
** reset HACCP alarms rES rES N.A. 7
** cyclic regulator Con CoF 8 10
* Indicates default
** Functions only visible if enabled
NOTE: To modify the status of a given function, press the ‘set’ key
NOTE: If the instrument is switched off, the functions will return to the default status.
IMPORTANT! Check presence of functions on the basis of IWC 720-730 model used
ALARMS
Label Alarm Cause EFFECTS Problem solving
E1 Probe 1 (setting) • Values read are outside the nominal range. E1” label shown on display; • Check the probe wiring.
faulty • Regulating probe faulty/short-circuited/open. the regulator is activated as indicated by • Replace probe.
parameters Ont and OFt if set for Duty
Cycle.
E2 Probe 2 (evaporator) • Values read are outside the nominal range. E2” shown on display. • Check the probe wiring.
faulty • Regulating probe faulty/short-circuited/open. • Replace probe.
AH1 High temperature • Value read by probe 1 > HAL after time of Alarm created in folder “AL” • Wait until temperature value read by
alarm “tAO” (see MIN MAX ALARMS table and descrip- via label AH1. probe 1 returns below HAL.
tion of parameters “HAL” and “Att” and “tAO”).
AL1 Low temperature • Value read by probe 1 < LAL after time of “tAO” Alarm created in folder “AL” • Wait for the temperature value read
alarm (see MIN MAX ALARMS table and description of via label AL1. by the probe to come back above LAL.
parameters “LAL” and “Att” and “tAO”).
Ad2 Defrost terminated • If the defrost cycle terminates due to a timeout Alarm created in folder “AL” • Press any key during an alarm to
for time-out (instead of end of defrost temperature being read with label AD2. switch off the warning light. The alarm
by the defrost probe). is definitively cancelled after the next
deforst cycle is completed.
Opd(1) Door open alarm • If the door is open, depending on delay set in Alarm created in folder “AL” with label • Resets automatically.
parameter tdO. “Opd”.
EA External alarm • Alarm setting from D.I. active if “H11”=4 (see Alarm created in folder “AL” via label EA • If regulators block, they can only be
description of parameter “H11”). Blocks regulators only if EAL= y. released after the DI has been disabled.
HACCP HACCP alarm • If the thermostat control temperature is outside Alarm Led lit continuously • When any key is pressed, the LED
the control range defined in parameters SLH and HACCP alarm created in folder “AL” (see will start flashing to signal that the
SHH for longer than the time set in parameter drA. section on HACCP alarms). event has been read.
(1) The tAo parameter does not clear if the door is closed: in fact, if the door is continually opened and closed, any alarms would not be signalled.
NOTE - If an exclude alarm time has been set (see table on folder ‘AL’ parameters) the alarm will not be signalled (this applies to all types of alarm).
NOTE - Press any key to override any alarm.
NOTE - See alarm LED - Buzzer signal ONLY IN MODELS WITH BUZZERS.
IMPORTANT! Check for alarms in relation to the IWC 720-730 model used.
MAX-MIN Absolute temperature value (par “Att”=0) Abs(olute) Temperature relative to Setpoint value (par “Att”=1) rEL(ative)
ALARMS 2
1 Off
AFd AFd
AFd AFd
set
LAL HAL
SEt + LAL SEt+ HAL
Minimum temperature alarm Temperature less than or equal to LAL (LAL with sign) Temperature less than or equal to set+LAL (LAL positive only)
Maximum temperature alarm Temperature greater than or equal to HAL (HAL with sign) Temperature greater than or equal to set+HAL (HAL positive only)
Reset after minimum Temperature greater than or equal to LAL + AFd Temperature greater than or equal to set + LAL + AFd
temperature alarm set -|LAL|+AFd
Reset after maximum Temperature less than or equal to HAL-AFd Temperature less than or equal to set+HAL-AFd
temperature alarm
If Att=reL(ative) LAL must be negative: so
set+LAL<set since set+(-|LAL|)=set-|LAL|
Auxiliary Regulator
only on models featuring auxiliary regulator
The auxiliary regulator can be activated via a digital input if this is set to auxiliary (parameter H11=7) or by a key (parameter H3x=9): in this case, the
regulator control must be configured as Aux by setting parameters H2x=8.
This function is used to energize the relay if it was de-energized, or vice versa. The relay state is stored in order to maintain correct operation in the
event of a power failure, unless parameter H11 is set to 7 (aux); in this case, the relay reflects the state of the digital input.
NOTE: The significance of the Digital Input (D.I.) must remain the same: for example when activating the relay by D.I. and switching off
with a key, if the D.I. is repositioned. The relay does not change state when de-energized by key.
Cyclic Regulator
only on models featuring cyclic regulator
Note: The PERIODIC CYCLE function can be selected by key or by digital input.
This function can be associated to one of the relay outputs (by setting parameters H2x=9) and can be used to actuate “Duty Cycle” regulation at the
intervals set in parameters Con and CoF. Regulator activation type can also be set in parameter dCE (see description of parameters). This function can
be activated via a digital input by setting parameter H11=8 or by key by setting parameters H3x=10.
Alarms - label AL
AFd H11
label Lit
OdO 0...250 0 min OFL n/y n flag tAb / / /
dSC(*) 0...255 0 sec
dOd n/y n flag Only on models with this feature
dty 0/1/2 0 num dAd SHH -55.0...150.0 10 °C/°F
Defrost-label dEF
min
label HCP
0...250 0
SLH -55.0...150.0 10 °C/°F
dit 0...250 6h hours/min/sec dCO 0...250 0 min
drA 0...99 10 num
dCt 0/1/2 1 num ddO 0...250 0 min
drH 0...250 24 hours
dOH 0...59 0 min Only on models with this feature
H50 0/1/2 0 num
dSt -50.0...15.0 8.0 °C/°F PtS t/d t flag
label Add
label FPr
Only on models with this feature FAA 0...14 0 num
FSt -50.0...150.0 2.0 °C/°F PtY n/E/o E num dL / / /
FAd 1.0...50.0 2.0 °C/°F StP
Fans - label FAn
1b/2b 1b flag Fr / / /
Fdt 0...250 0 min
LOC n/y n flag Only on models with this feature
Display - label diS
dt 0...250 0 min
label cLc
PA1 0...250 0 num Con -55.0...150.0 10 °C/°F
dFd n/y y flag
ndt n/y n flag CoF -55.0...150.0 10 °C/°F
FCO n/y/d.c. y num
CA1 -12.0...12.0 0 °C/°F dCE 0...3 3 num
Fod n/y n flag
CA2 -12.0...12.0 0 °C/°F FOLDER FnC: see FUNCTIONS section on page 3
FdC 0...99 0 min
ddL 0/1/2 2 num * only visible in models with two compressors
Fon 0...99 0 min
dro **See note on H2x parameters
FoF min 0/1 0 flag
0...99 0 ***Parameter ONLY visible on models with BUZZER
DESCRIPTION OF PARAMETERS
COMPRESSOR REGULATOR (folder with label “CP”) compressor is disabled during this period the 2nd compressor will
diF Compressor relay activation differential; the compressor stops not be activated. NOTES: only visible in models with two compres-
on reaching the setpoint value (as indicated by the adjustment probe) sors.Check the probes and models available
and restarts at a temperature equal to the setpoint plus the value of the DEFROST REGULATOR (folder with label “dEF”)
differential. DEFROSTING CONDITIONS
Note: this value cannot be 0. The instrument allows defrosting to be performed in the following conditions:
HSE Maximum possible setpoint. • The evaporator temperature is lower than the defrost end tempera-
LSE Minimum possible setpoint. ture set in parameter dSt;
NOTE: The two sets are interdependent: HSE (maximum set) cannot • Manual defrosting is not already activated (see); in this case the
be less than LSE (minimum set) and viceversa request for automatic defrosting will be cancelled.
OSP Temperature value to be added algebraically to the setpoint if reduced
set enabled (Economy function). The reduced set can be enabled by dty Type of defrost.
pressing a key, which must be specially configured for this purpose. 0=electrical defrost; 1=cycle inversion defrosting (hot gas)
HC Operation mode (Heating/ Cooling) 2=free mode defrost (independent of compressor).
If set to H, the regulator starts aheat function. Automatic defrosting
If set to C, the regulator starts a cold function. In this case, defrosting takes place at time intervals set by parameter dit (=0
Cit Minimum compressor activation time before defrosting will not take place at all).
disabling. If set to 0, it is not active. As mentioned above, if the parameter dit> 0 and defrosting conditions apply
CAt Maximum compressor activation time before (see parameter dSt), defrosting will take place at fixed intervals and according to
disabling. If set to 0, it is not active. the parameter dCt.
Ont Compressor start time in the event of faulty probe. If set to “1” with Oft
at “0”, the compressor remains on continuously, whilst with OFt >0 it dit Interval between the start of two subsequent defrosting operations.
runs in duty cycle mode. 0=the function is disabled (defrosting is NEVER performed)
OFt Compressor switch off time in the event of faulty probe. If set to “1” dCt Selection of count mode for the defrosting interval.
with Ont at “0” the compressor remains off whereas with Ont >0 it runs 0=compressor hours of operation (DIGIFROST® method);
in duty cycle mode. Defrosting active ONLY with the compressor on.
dOn Delayed start. This parameter indicates that protection has been enabled NOTE: compressor time of operation is counted regardless of the evapo-
on actuation of the general compressor relay. At least the indicated time rator probe (counting is active if evaporator probe is absent or faulty).
must elapse between switch-off of the compressor relay and the succes- 1=hours of appliance operation. Defrost counting is always active when
sive switch-on. the machine is on and starts at each power-on.
dOF Delay after switching off. The parameter indicates that the protection is 2=compressor stop. Every time the compressor stops, a defrosting cycle
active on compressor relay actuations. At least the indicated time must is performed according to parameter dty.
elapse between switch-off of the compressor relay and the successive dOH Defrost start delay time from start-up of instrument.
switch-on dSt Defrosting end temperature (determined by the evaporator probe).
dbi Delay between switch-ons; the indicated delay time must elapse between dEt Defrost time-out; determines the maximum duration of defrosting.
two consecutive switch-ons of the regulator.
OdO Delay time in activating the outputs after switch-on of the instrument or FAN REGULATOR (folder with label “FAn”) as applicable
after a power failure. 0=not active. FSt Fan lock temperature; if the evaporator probe reads a higher value than
dSC 2nd compressor activation delay. Delay time in activating the 2nd the set value, the fans are stopped. The value is positive or negative and,
compressor relay respect to 1st compressor relay activation. If 1st depending on parameter FPt, can represent the temperature as an
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
IWC 720
IWC 750 IWC 740 IWC 730
Release the three hooks as indicated in the drawing (from above and below, not
laterally) to remove the frame.
DISCLAIMER
This document is the exclusive property of Eliwell Controls srl and may not be
reproduced or circulated unless expressly authorized by Eliwell Controls srl.
All possible care has been taken to ensure the accuracy of this document;
Eliwell Controls srl cannot accept liability for any damage resulting from its
use. The same applies to any person or company involved in preparing and
editing this document. Eliwell Controls srl reserves the right to make changes
or improvements at any time without notice
ELECTRICAL CONNECTIONS
Important! Switch off the device before working on the electrical con-
nections.
The instrument is equipped with FASTON connectors for electrical cable con-
nection.
The relay outputs are voltage free. Do not exceed the maximum permitted
current; for higher loads, use a contactor with sufficient power capacity.
Make sure that power supply is the correct voltage for the device.
Probes have no connection polarity and can be extended using a normal bipo-
lar cable (note that the extension of the probes influences the instrument’s
electromagnetic compatibility (EMC): take great care with the wiring).
Probe cables, power supply cables and the TTL serial cables should be routed
separately from power cables.