Calculation and Selection Result ED Y COOL BE

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

Project Name CASA ED Y COOL BE

Peru ,lima
Date 2021 / 8 / 24

Calculation and Selection Result

A.Project Overview

Project Name CASA ED Y COOL BE


Country Peru
City lima
Address
Client Name
Client Address
Reference
Revision
Project Date 8 / 24 / 2021
Altitude m
Cooling Condition: Indoor Dry-bulb 23.9 °C
Cooling Condition: Indoor Rel. Humidity 55
Cooling Condition: Outdoor Dry-bulb 30.5 °C
Cooling condition: Outdoor wet bulb 23.4 °C
Heating Condition: Indoor Dry-bulb 20.0 °C
Heating Condition: Outdoor Dry-bulb 7.0 °C
Heating Condition: Outdoor Rel. Humidity 86.9

B.Material List

Model Quantity Description


MDVC-V170W/DVN1 1 Cooling Only Mini VRF All DC
Inverter
MI2-36GDHN1 5 Wall_mounted (2nd DC IDU)
FQZHN-01D 4 Branch Joint
Ø3/4 3.0 m Copper Pipe
Ø5/8 9.0 m Copper Pipe
Ø1/2 15.0 m Copper Pipe
Ø3/8 12.0 m Copper Pipe
Ø1/4 15.0 m Copper Pipe
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

System1

1.1 Material List

Model Quantity Description


MDVC-V170W/DVN1 1 Cooling Only Mini VRF All DC
Inverter
MI2-36GDHN1 5 Wall_mounted (2nd DC IDU)
FQZHN-01D 4 Branch Joint
Ø3/4 3.0 m Copper Pipe
Ø5/8 9.0 m Copper Pipe
Ø1/2 15.0 m Copper Pipe
Ø3/8 12.0 m Copper Pipe
Ø1/4 15.0 m Copper Pipe
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

1.2 Indoor Unit Specifications

IDU Name Model Sound (dB(A)) Weight(kg) Dimension(inch) Power Supply Rated Power(W) MCA(A) MFA(A)
WxHxD
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15

IDU Name Model Cooling AT Req.TC TC Req.SC SC Heating AT Req.HC HC Air flow ESP
(°C) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (°C) (Btu/h) (Btu/h) (CFM) (in.w.g.)
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,648 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,648 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,607 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,252 0 7,546 20.0 0 13,525 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,252 0 7,546 20.0 0 13,525 385.88(SSH) N/A
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

1.3 Outdoor Unit Specifications

Name Model Module Dimension(inch) Weight(kg) Base refr(kg) Add refr(kg) Power Supply MCA(A) MFA(A)
ODU1 MDVC- MDVC-V170W/DVN1 N/A 0.00 0.00 1.41 220V~60Hz~1ph N/A N/A
V170W/DVN1

Name Model CR% Temp(°C) CC(Btu/h) Req CC(Btu/h) Temp(H/RH)(°C) HC(Btu/h) Req HC(Btu/h)
ODU1 MDVC-V170W/DVN1 105.88 30.5 58,616 0 7.0/87% 0 0

Name Model EER COP Cooling Power(kW) Heating Power(kW)


ODU1 MDVC-V170W/DVN1 5.14 -1.#J 3.37 0
Req.TC: Required Total Cooling Capacity
Req.SC: Required Sensible Cooling Capacity
Req.HC: Required Total Heating Capacity
TC: Available Total Cooling Capacity
SC: Available Sensible Cooling Capacity
HC: Available Total Heating Capacity
AT: Ambient Temperature
ESP: External Static Pressure
Req.CC: Required Cooling Capacity
CC: Available Cooling Capacity
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

1.4 Piping and Mode Selection Devices

IDU Quantity 5/9


Combination Ratio 105.88%
Additional refrigerant charge 1.41 kg
= 15.00(1/4) * 0.022 + 12.00(3/8) * 0.057 + 4 *
0.1
Factory refrigerant charge 0.00 kg
Total refrigerant charge 1.41 kg
Total Pipe Length 29 m / 100 m
Furthest Actual 15 m / 60 m
Furthest Equivalent 17 m / 70 m
Furthest Equivalent from First Branch to IDU 13.5 m / 20 m
Drop Height between IDU and IDU 0m/8m
Drop height between IDU and ODU(Below 3 m / 30 m
ODU)
Available Capacity Cooling 58,616 Btu/h
Available Capacity Heating 0 Btu/h
Note:
1.The equivalent length of each branch joint is 0.5m.

Pipe
No. Length Gas Pipe Liquid Pipe
(1) 3.0 m Ø3/4 Ø3/8
(2) 3.0 m Ø5/8 Ø3/8
(3) 3.0 m Ø5/8 Ø3/8
(4) 3.0 m Ø5/8 Ø3/8
(5) 3.0 m Ø1/2 Ø1/4
(6) 3.0 m Ø1/2 Ø1/4
(7) 3.0 m Ø1/2 Ø1/4
(8) 3.0 m Ø1/2 Ø1/4
(9) 3.0 m Ø1/2 Ø1/4

Branch Joint
No. Load Btu/h Model
(1) 61,414 FQZHN-01D
(2) 49,131 FQZHN-01D
(3) 36,849 FQZHN-01D
(4) 24,566 FQZHN-01D
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

1.5 Piping Diagram

VRF 60Hz R410A


ODU:58,616/0 Btu/h IDU Total:56,595/37,957/68,238 Btu/h

MDVC-V170W/DVN1

IDU1
(1)
Ø3/4,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(1)3.0 m,0 (5)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,648 Btu/h
IDU1
(2)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(2)3.0 m,0 (6)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,648 Btu/h
IDU1
(3)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(3)3.0 m,0 (7)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,607 Btu/h
IDU1
(4)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(4)3.0 m,0 (8)3.0 m,0 TC:11,252 Btu/h
FQZHN-01D SC:7,546 Btu/h
HC:13,525 Btu/h
IDU1
Ø1/2,Ø1/4 MI2-36GDHN1
(9)3.0 m,0 TC:11,252 Btu/h
SC:7,546 Btu/h
HC:13,525 Btu/h

The piping size may be different with the actual situation because of the software's illustration limitation, please confirm the piping size according to the installation manual
before installation.
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24

1.6 Wiring Diagram

L1,L2 220V~60Hz~1ph
ODU1

3-core Cables PQE

IDU1

PQE

IDU1

PQE

IDU1

PQE

IDU1

PQE

IDU1

The wiring diagram may be different with the actual situation because of software's illustration
limitation, please confirm the wiring diagram according to the installation manual before installation.

You might also like