Professional Documents
Culture Documents
Calculation and Selection Result ED Y COOL BE
Calculation and Selection Result ED Y COOL BE
Calculation and Selection Result ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24
A.Project Overview
B.Material List
System1
IDU Name Model Sound (dB(A)) Weight(kg) Dimension(inch) Power Supply Rated Power(W) MCA(A) MFA(A)
WxHxD
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU1 MI2-36GDHN1 33(SSH) 11.40 38-63/64*12-13/32*8-25/32 220-240,60,1 30 0.45 15
IDU Name Model Cooling AT Req.TC TC Req.SC SC Heating AT Req.HC HC Air flow ESP
(°C) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (°C) (Btu/h) (Btu/h) (CFM) (in.w.g.)
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,648 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,648 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,319 0 7,591 20.0 0 13,607 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,252 0 7,546 20.0 0 13,525 385.88(SSH) N/A
IDU1 MI2-36GDHN1 23.9/55.0% 0 11,252 0 7,546 20.0 0 13,525 385.88(SSH) N/A
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24
Name Model Module Dimension(inch) Weight(kg) Base refr(kg) Add refr(kg) Power Supply MCA(A) MFA(A)
ODU1 MDVC- MDVC-V170W/DVN1 N/A 0.00 0.00 1.41 220V~60Hz~1ph N/A N/A
V170W/DVN1
Name Model CR% Temp(°C) CC(Btu/h) Req CC(Btu/h) Temp(H/RH)(°C) HC(Btu/h) Req HC(Btu/h)
ODU1 MDVC-V170W/DVN1 105.88 30.5 58,616 0 7.0/87% 0 0
Pipe
No. Length Gas Pipe Liquid Pipe
(1) 3.0 m Ø3/4 Ø3/8
(2) 3.0 m Ø5/8 Ø3/8
(3) 3.0 m Ø5/8 Ø3/8
(4) 3.0 m Ø5/8 Ø3/8
(5) 3.0 m Ø1/2 Ø1/4
(6) 3.0 m Ø1/2 Ø1/4
(7) 3.0 m Ø1/2 Ø1/4
(8) 3.0 m Ø1/2 Ø1/4
(9) 3.0 m Ø1/2 Ø1/4
Branch Joint
No. Load Btu/h Model
(1) 61,414 FQZHN-01D
(2) 49,131 FQZHN-01D
(3) 36,849 FQZHN-01D
(4) 24,566 FQZHN-01D
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24
MDVC-V170W/DVN1
IDU1
(1)
Ø3/4,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(1)3.0 m,0 (5)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,648 Btu/h
IDU1
(2)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(2)3.0 m,0 (6)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,648 Btu/h
IDU1
(3)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(3)3.0 m,0 (7)3.0 m,0 TC:11,319 Btu/h
FQZHN-01D SC:7,591 Btu/h
HC:13,607 Btu/h
IDU1
(4)
Ø5/8,Ø3/8 Ø1/2,Ø1/4 MI2-36GDHN1
(4)3.0 m,0 (8)3.0 m,0 TC:11,252 Btu/h
FQZHN-01D SC:7,546 Btu/h
HC:13,525 Btu/h
IDU1
Ø1/2,Ø1/4 MI2-36GDHN1
(9)3.0 m,0 TC:11,252 Btu/h
SC:7,546 Btu/h
HC:13,525 Btu/h
The piping size may be different with the actual situation because of the software's illustration limitation, please confirm the piping size according to the installation manual
before installation.
Project Name CASA ED Y COOL BE
Peru ,lima
Date 2021 / 8 / 24
L1,L2 220V~60Hz~1ph
ODU1
IDU1
PQE
IDU1
PQE
IDU1
PQE
IDU1
PQE
IDU1
The wiring diagram may be different with the actual situation because of software's illustration
limitation, please confirm the wiring diagram according to the installation manual before installation.