Professional Documents
Culture Documents
FACP Methodology
FACP Methodology
Extinguished Inc
Project Name :
Project Location :
Introduction : Statements below are general guidelines on the installation of FIRE ALARM CONTROL Panel
System. The system may not be a full blown FACP system, apply only on equipment present on site. Some
area may not require Duct detector or beam detector, adjust accordingly. Refences are given to a particular
1) The required amount of cable should be transferred from Stores to the Site access point by pick-up
2) All the cables should be clipped in surface or and to the particular floor with a wheelbarrow as required to
the workplace.
3) The correct size and type of cable should be identified and cut to the required length only. installed in
4) Proper identifications to be provided for loop in / loop out of Fire Alarm cables.
5) The earth cables to all the outstations to be appropriately terminated with earth sleeve in the proper terminal
6) The junction boxes for and back boxes FACP/FAS installation to the outstations such as smoke detectors
(SD), Manual Call Points (MCP’s) and modules should be installed as per the approved shop drawings.
7) Adequate and additional cable lengths to be provided during cabling for the detectors, which are coming in
False ceiling.
8) All the Fire Alarm Control Panels such as Main Control Panels, Mimic Panels, Repeater Panels should be
10) All Smoke Detectors (SD’s) to have a cover on it after installation and before handing over of the area, to
11) All cables to be properly identified in the Fire Alarm control panel before termination.
14) Work Inspection Request shall be raised for the Consultant's inspection and sign off.
15) The devices/peripherals (Smoke detectors, heat detectors, break glass, duct detectors, beam detectors,
control and monitoring modules) are connected in Class A circuit with the Control panels.
16) The speakers & speaker with strobes are connected in Class A circuit with the Control panels.
17) 2 Core TF 16AWG cable to be utilized for cabling the Initiating Device Circuits to the panel, extra 2c
16AWG cable is needed for the Smoke Detector (SD) with sounder base for the activation of the Sounders
Units (SU’s).
18) 2 core TF 16AWG cable to be used for cabling the Speakers with the panel, additional 2c x 16AWG cable
is required from the FACP for the speaker with strobe for the activation of the strobe unit allied in vertical
Always comply with National Fire Protection Association (NFPA 72), "Smoke-Sensing Fire Detectors
(SSFD’s)" & "heat-sensing Fire Detectors (HSFD’s)". Smooth ceiling spacing shall not more than 30 feet (9
meters).
floor.
Annunciator: Install with top of the panel not more than 72 inches (1830 mm) above the finished floor.
Double-Check that hardware and devices are Nationally Recognized Testing Laboratory (NRTL)
listed for use with Fire Alarm System (FAS) before making connections. Make Addressable Connections
(AC’s) with a Supervised Interface Device (SID) to the Following devices and systems. Then Install the
Interface Device (ID) less than 3 feet from the device controller (DC). When such Feedback is available at the
Fire Alarm-Initiating Connection (FAIC) to activate emergency shutoffs for gas and Fuel supplies.
Battery Charger Supply (BCS) incorrect to correctly measure the output voltage you will require to
To prevent infect to the system, disconnect the DC power immediately (batteries & power down the
system, disconnect the power & harnesses from the Power Supply).
Connect the Multi-meter to the battery leads (with batteries disconnected}, power up & measure the
voltage. Calculate the difference between the measured voltage & 27.6v.
Remember: After 90 seconds approximately, the voltage will drop to <24v. If this happens, power down &
start again.
Fire Panels can detect positive or negative Earth Ground Faults. An Earth Ground Fault occurs when
All inspection and testing for a fire alarm system shall be carried out following specifications. Work
shall be carried out by the experienced site team under the guidance of engineer and shall further be checked
Check all devices installed as per the specifications & approved Drawings.
The inspection shall be based on completed and approved drawings and system documentation as per
NFPA.
Adhere to "Visual Inspection Frequencies (VIF” s)" Table in the "Inspection" section of the
"Inspection, Testing and Maintenance (ITM)" Chapter in NFPA 72; retain the "initial/Reacceptance" column
FA System Testing:
Comply with the "Test Methods" Table in the "Testing" section of the "Inspection, Testing and
Test audible devices for the Public Operating Mode (POB) as per the manufacturer's written
instructions & recommendations. Perform the test by using a Portable Sound-Level Meter (PSLM) adhering to
Test audible appliances for the private operating mode according to the manufacturer's written
instructions.
Test visible appliances for the public operating mode according to the manufacturer's written
instructions.
Factory- certified FACP service representative shall prepare the "Fire Alarm System (FAS) record of
Completion" in the "Documentation" section of the "Fundamentals of Fire Alarm Systems (FAS)" Chapter in
National Fire Protection Association (NFPA 72) and the "Inspection and Testing Form (ITF)" in the "Records"
section of the "Inspection, Testing and Maintenance (ITM)" Chapter in NFPA 72.
Re-Acceptance Testing:
Perform re-acceptance testing to authenticate the appropriate operation of added or replaced devices
and appliances. Test all the field loop devices with the Fire Alarm Control Panel (FACP).
Double-check the detectors with the artificial test smoke spray or other alternatives. Utilize forms
Field tests for FACP installations shall be validated by authorities having jurisdiction.
Manufacturer's Field Service
Engage a factory-certified service representative to observe, inspect, test, and adjust factors,
Perform tests and inspections. After testing & commissioning provide training demonstration to the
Plan and carry out Cause effect inspection as per programmed cause & effect matrix. Test all the
Identify system components, wiring, cabling, and terminals. Comply with req for identification
specified in specifications.
Install framed instructions in a location visible from the fire-alarm control unit.