Itron DTM System Solution
Itron DTM System Solution
Solution Brief
IEC 60076-7
Outdoor temperature
variation due to wind,
sunshine or rain is ignored.
This does not mean we do
not need ambient
temperature.
IEC 60076-7
MV LV
THERMAL MODEL : LOADED TRANSFORMER
Parameters of thermal model
3 IRMS R Pfer/Pcu
Tamb x 0.8
y 1.6
System
NLP
algorithm
Measured temperature
Estimated temperature w/o identification
Estimated temperature with identification
Temperature in °C
Time in min
» Accuracy of +/-7°C without identification (after transient) and +/-3°C with identification of parameters.
ELECTRICAL MODEL
Estimation of MV values & internal losses inside the transformer
MV LV
Outputs Outputs
Objective is to estimate the primary currents and voltages of the transformer, with an accuracy
of 1%, based on the secondary values (LV).
Estimation of transformer internal losses (active and reactive)
All parameters of this electrical model are derived from the transformer nameplate and test
report of the transformer
ELECTRICAL MODEL: LOADED TRANSFORMER
Parameters of electrical model
W Pulsation