Professional Documents
Culture Documents
Datasheet N°3: Three Phase Transformer 33/0.415kV, 100kVA: No. Characteristics Unit Client Requirements Offered
Datasheet N°3: Three Phase Transformer 33/0.415kV, 100kVA: No. Characteristics Unit Client Requirements Offered
415kV, 100kVA
No. Characteristics Unit Client Requirements Offered
1 Country of Origin (*) INDIA
10 Mineral oil (Not ASKAREL nor Mineral oil (Not ASKAREL nor
Dielectric PCBs) PCBs)
11 Frequency Hz 50 50
12 Transformation Ratio kV 30-33/0.415 33/0.415
13 Power kV 70 70
frequency withstand
14 Impulse withstand voltage kV 170 170
15 Impedance voltage (%) % 4±10% 4±10%
16 Temperature rise for oil on °C ≤ 57 ≤ 57
the top
17 Temperature °C ≤ 62 ≤ 62
rise for Winding
18 No-load losses (W) kW 0.32 0.32
19 Load losses (W) kW 1.75 1.75
Short-circuit voltage % 4 4% IEC Tol.
No-load current % 2.5 2.5 approx
Continuous overload % 10 10
20 LV Winding material Copper Copper
21 MV Winding material Copper Copper
22 Bushing material porcelain porcelain
23 Creepage distance of MV mm ≥930 ≥930
bushings
24 Fixing to the pole Yes Yes
25 % minimum five minimum five
Tap changers
position:0,±2.5%,±5% position:0,±2.5%,±5%
26 - Temperature rise test - Similar / Higher rating test
Type test - BIL test report shall be submitted
27 Acceptance tests Requested Performed as per the Quality
plan
Operating environment Humid tropical climate with Noted
heavily polluted atmosphere
28 Drawings Submitted