LTAC Relay Manuals

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 89

High-Tech Range

IRI1-ER (Stablized Earth Fault Current Relay)

C&S Electric Ltd.


(Protection & Control Division)
IRI1-ER- Stablized Earth Fault Current Relay

Contents

1. Introduction 7. Housing

2. Applications 7.1 Individual housing


7.2 Rack mounting

3. Characteristics and features 7.3 Terminal connections

8. Relay testing and commissioning


4. Design

8.1 Power On
4.1 Connections
8.2 Checking the set values
4.1.1 Analog inputs
8.3 Secondary injection test
4.1.2 Output relays
8.3.1 Test equipment
4.2 Front plate
8.3.2 Example of a test circuit for a IRI1-3ER-
4.2.1 LEDs
relay
4.2.2 DIP-switches
8.3.3 Checking the pick-up and tripping values
4.2.3 <RESET> push button (IRI1-ER)
4.3 Code jumper 8.3.4 Checking the operating and resetting
values (IRI1-3ER)
8.4 Primary injection test
5. Working principle
8.5 Maintenance

6. Operations and settings


9. Technical Data

6.1 Layout of the operating elements


9.1 Measuring input
6.2 Setting of the pick-up value for the
differential current ID 9.2 Auxiliary voltage
6.2.1 Indication of fault 9.3 General data
6.3 Reset 9.4 Output relay
6.3.1 Reset by pressing the <RESET> push 9.5 System data
button 9.6 Setting ranges and steps
6.3.2 Automatic reset 9.7 Dimensional drawing
6.4 Calculation of the tripping current and
the stabilizing resistance
10. Order form
6.4.1 Sample calculation - alternator
6.4.2 Example calculation - transformer
6.5 Application of IRI1-3ER relay as High
Impedance Bus Differential Protection

2
IRI1-ER- Stablized Earth Fault Current Relay

Transformer
1. Introduction
L1
The application of powerful microprocessors with MR-
and IR-relays of the HIGH TECH RANGE provides a
large variety of advantages over power protection l L2
l l
systems of the traditional type.
The MR-protection relays are based exclusively on the
microprocessor technology. They represent our most l L3
l l
efficient generation of power protection systems.
Because of their capabilities to process measured l

values digitally and to perform arithmetical and logical


operations, they are superior to the traditional analog Rsr
systems.
Besides, the digital protection relays offer important I> IRI1-ER
additional advantages such as very low power
l
consumption, adaptability, flexible construction,
selection of relay characteristics etc. Fig. 2.1: Zero-current differential protection of
The IR-protection relays are based on the a transformer in star-connection (IRI1-ER)
microprocessor technology or on the analog Motor
technology. They represent a more cost saving Transformer
Alternator
generation of relays of the HIGH TECH RANGE, used L1
for basic equipment protection.
The IR-protection relays are superior to conventional
protective devices because of their following l
l l
L2
characteristics:
 Integration of multiple protective functions into l
one compact housing l l L3
l
 User-friendly setting procedure by means of DIP- l
switches l

 Compact construction type by SMD-technology Rsr Rsr Rsr

MR-protection relays are used for more complex


IRI1-3ER
protective functions, such as earth fault directional
detection, and also in cases where easy operation, l
quick fault-analysis and optimal communication
capabilities are required. Fig. 2.2: Highly stabilized differential
All relays of the HIGH TECH RANGE are available protection for alternators, transformers and
for flush mounted installation, as well as for 19“ rack motors (IRI-3ER)
mounting. Plug-in technology is used. Of course, all
relays comply with the IEC/DIN regulations required 3. Characteristics and features
for the specific protection application.  static protective device
2. Applications
 single-phase current measuring (IRI1-ER) as
The stabilized earth fault current relay IRI1-ER serves as zero-current differential protection (restricted
a supplement for the transformer differential earth fault 64 REF)
protection. It allows for example implementation of a
zero-current differential protection by integrating the  three-phase current measuring (IRI1-3ER) as
star-point current (IRI1-ER). With the view to its higher phase-current differential protection
resistance to disturbances from outside the protection  high stability by serial stabilizing resistor Rsr per
area, it can be set much more sensitively than the phase
simple transformer differential protection, in order to
prevent false trippings.  high sensitivity by low input burden of C.T.
The IRI1-ER can be used as:  extremely wide setting range with fine grading
 Zero-current differential protection of the star  wide range of operation of the supply voltage
point winding (restricted earth fault) of a (AC/DC)
transformer (IRI1-ER), see figure 2.1
 coding for the self-holding function or automatic
 Highly stabilized differential current relay for reset of the LED‘s and trip relays
alternator, transformers and motors (IRI-3ER),
see figure 2.2  frequency range 50/60 Hz
 rated current 1A or 5A
 output relay with 2 change-over contacts

3
IRI1-ER- Stablized Earth Fault Current Relay

4. Design
4.1 Connections

L+/L L-/N
L1 L2 L3 D9
C9 E9

Power
Supply

~
l l
P1 S1P1 S1P1 S1

P2 S2P2 S2P2 S2 ID
D1
l l Trip C1
ID
E1
Rsr D2
B1
l C2
ID E2
B2 50/60Hz
l

Reset

P1 S1

P2 S2
l

Fig. 4.1: Connection diagram IRI1-ER

L+/L L-/N
L1 L2 L3
C9 E9 D9

Power
Supply
~
l l
P1 S1P1 S1P1 S1

S2
P2 S2P2 S2P2
Rsr B1 ID D1
l
Trip C1
ID
B2 50/60Hz E1

Rsr D2
B3
l C2

~ l
B4 50/60Hz
ID l E2

Rsr B5
l

B6 50/60Hz Reset
l l
P1 S1P1 S1P1
S1

P2 S2P2 S2P2 S2
l l l

Fig. 4.2: Connection diagram IRI1-3ER


4.1.1 Analog inputs 4.1.2 Output relays
At three-phase measuring, the analog input signals of Both relay types are equipped with a trip relay with two
the differential currents are fed to the protective device change-over contacts.
via terminals B1 to B6 (IRI1-3ER), respectively at single Tripping I D : D1, C1, E1
phase measuring via terminals B1/B2 (IRI1-1ER).
D2, C2, E2
4
IRI1-ER- Stablized Earth Fault Current Relay

4.2 Front plate 4.2.1 LEDs


On the front plate of the IRI1-ER 2 LEDs are installed,
signalizing the following 2 service conditions:
 LED ON (green): readyness for service
 LED I D (red): tripping

4.2.2 DIP-switches
ID ON The set of DIP switches on the front plate serves for
setting the tripping value for the differential current ID.

RESET 4.2.3 <RESET>-push button


5 7.5%
0 5 The <RESET> push button is used for
0 10
0 20 acknowledgement and reset of the LED and the tripping
0 40
ID relay after tripping at the specifically preset value (see
4.3).

4.3 Code jumper


Behind the front plate, two coding jumpers are installed
at the bottom side for setting the LED-display, as well
as for the tripping function of the output relay.

IRI1-3ER

Front plate

Fig. 4.3: Front plate ID ON

The front plate of the IRI1-ER comprises the following


operation and indication elements:
ID

 1 set of DIP-switches for setting the tripping value


 2 LEDs for indication of faults- and readyness for
operation
 1 <RESET> push button
Code jumper
3 4

Code jumper ON

Code jumper OFF

Fig. 4.4: Code jumper

Code Function Position of Operating mode


jumper code jumper
3 Differential current OFF latching of the red LED ID
indication ON automatic reset of the red LED ID
4 Differential current OFF latching of the tripping relay
tripping ON automatic reset of the tripping relay

Table 4.1 Code jumper

5
IRI1-ER- Stablized Earth Fault Current Relay

5. Working principle The harmonics existing during a transformer saturation


and the DC-component are suppressed by a filter circuit
located in the input circuit of the relay; the filter circuit
The protection relay IRI1-ER is connected to the is adjusted to the mains frequency (50/60Hz).
differential circuit of the c.t.s as a current differential
protection relay. When used as zero-current differential
protection (restricted earth fault), the relay (IRI1-ER) is The IRI1-ER has a single-phase differential current
to be connected acc. figure 2.1. When used as highly supervision with an adjustable pick-up value. The
stabilized differential current relay, the relay (IRI1-3ER) current measured in the differential circuit is constantly
is to be connected acc. figure 2.2. compared with the set reference value.

The knee voltage UKn is an important characteristic of Measuring principle IRI1-ER


the transformer. The transformer does not work
The analog current signals are galvanically decoupled
linearly anymore above this voltage. Two transformers
via the input transformer and are led over a low pass
of the same class still show the same behavior below
with subsequent band-pass for suppression of the
UKn within the scope of their precision class. Above UKn
harmonics, then rectified and compared with the set
they can, however, show very different saturation
reference value of a comparator. In case the current
behavior.
measured exceeds the reference value, an
instantaneous tripping takes place (figure 4.1).
Connected in a differential current circuit an apparent
fault current can thus be measured at large primary
The IRI1-3ER has a three-phase differential current
current intensity which really results only from the
supervision with adjustable pick-up value. The currents
different saturation of both transformers.
measured in the individual differential circuits are
constantly compared with the set reference value.
An additional stabilizing resistor RST counteracts this
effect. It attenuates the current flow through the
Measuring principle IRI1-3ER
measuring device. This way the unsaturated
transformer drives part of its current into the saturated The analog current signals are galvanically decoupled
via three input transformers and led over a low pass
with subsequent band-pass for suppressing the
harmonics. Then rectified and compared with the set
IF IF
Protecting object
reference value of a comparator. In case one of the
three currents measured exceeds the reference value,
an instantaneous tripping takes place (figure 4.2).

RS RL RL RS 6. Operations and settings

6.1 Layout of the operating elements


Rsr US

Z IR Z The DIP-switch required for setting of parameters is


At saturated C.T.
R Z=0
located on the front plate of the relay.

6.2. Setting of the pick-up value for the


Fig. 5.1 Single line diagram IRI1-ER differential current ID

transformer and minimizes the faulty differential


current effect on secondary side. By small currents the The pick-up value of the differential current tripping ID
stabilizing resistor effects however also the accuracy of can be set by means of the DIP-switches set ID in the
the real fault current measurement. Because this effect range of 5% to 82.5% x IN with a grading of 2.5%.
lies in a linear range it can be taken into consideration
mathmatically by adjusting the protection device.
The pick-up value is calculated by adding up the values
(see para. 6.4).
of all DIP-switches.
For demonstrating the working principle, figure 5.1
shows the single-line diagram of the IRI1-ER.

6
IRI1-ER- Stablized Earth Fault Current Relay

Example: 6.4 Calculation of the tripping current


A pick-up value of 30% of the rated current is required. and the stabilizing resistance
Prior to setting the relay, the stabilizing resistance Rsr, as
5 7.5% ID = 5 + 5 + 20 = 30% x I N well as the tripping current I set must be calculated. For
5 the correct setting, the knee-point voltage in the
0 magnetizing circuit of the c.t. is of special importance.
10
0 In order to obtain a sufficient differential current for
20
tripping on account of internal faults, the knee-point
0 40
voltage U kn of the transformer should be twice as high
ID as the maximum expected stabilizing voltage US in case
of faults from outside the protection zone. From this
6.2.1 Indication of fault results the following calculation:
UKn = 2 × U S = 2 × If,sek × (R S + R L)

The fault alarm is shown by the LED ID on the front Explanation:


plate of the relay, which lights up red at tripping. Ukn knee-point voltage of the magnetizing circuit of
the transformer
Depending on the coding by means of the code jumper Us maximum stabilizing voltage in case of external
(see chapter 6.3.2), the fault alarm extinguishes faults
automatically or after pressing the <RESET> push
button, after the fault is eliminated. If,sek maximum expected fault current (secondary-side)
in case of external faults
6.3 Reset
RS secondary resistance of the transformer
RL Resistance of the connection line between c.t. and
6.3.1 Reset by pressing the <RESET>- relay
push-button

By pressing the <RESET> push button, the tripping The tripping current of the relay is then calculated, as
relay is reset and the LED-signal extinguishes. All follows:
coding switches must be plugged out for this (see ID > UKn
chapter 4.3). 2 . R Sr
6.3.2 Automatic reset Explanation:
RSr stabilizing resistance
Code jumper 1
The strength of the stabilizing resistance must be
If no code jumper is plugged in at coding place 1, the selected in a way to ensure that the tripping current is
red fault alarm LED ID is coded latching. within the setting range (5% to 82.5% of IN).
When the pick-up value is exceeded, nearly an
immediate tripping is initiated. With 30 ms the tripping
The fault signal can only be reset manually by pressing time is approx. five times as high as the tripping value.
the <RESET> push button. In case of lower currents, the tripping time is slightly
higher (about 100ms), in order to reach a stabilization
of the protective function against external faults (see
If the code jumper is plugged in at coding place 1, the also chapter 5).
red fault signal LED ID is automatically reset, after the
fault is eliminated. 6.4.1 Sample calculation - alternator
An IRI1-ER protection relay is used for the earth-fault
Code jumper 2 protection of an alternator. In the starpoint, the
following c.t. is provided:
The tripping relay is coded latching, if no code jumper transformation ratio : 100/1A
is plugged in on coding place 2.
class : 5 P 10

The tripping relay can only be reset manually by output : 2.5 VA


pressing the <RESET> push button. secondary resistance
If the code jumper is plugged in on coding place 2, the of the transformer : <0.7Ω
tripping relay is automatically reset after elimination of
the fault.

7
IRI1-ER- Stablized Earth Fault Current Relay

A primary-side fault current of 20% x IN shall be P N < I² x R sr = 0.2² A² x 61.6 Ω < 2.47 W
recorded. The secondary current is used for
calculation. In this case, PN represents the minimum output required
(pure current-heat losses). A considerably increased
Calculation of the knee-point voltage output P F is required in the event of a fault.
If the knee-point voltage is not indicated by the Example: The fault current is: I F,prim = 13.1 kA
manufacturer, as is the case in our example, the
If one neglects the transformer saturation, the following
approximate value can be calculated, as follows:
peak voltage U P occurs:
S×klu 2.5×10
Ukn = ⇒ = 25V I F,prim
IN 1 Up = (R Sr + 2 × RL + R r + RS)
n
Explanation: 13100A × 1
Up = × (62.5Ω) = 8187.5 V
100
S output of the c.t.
klu overcurrent factor of the c.t. If one considers the transformer saturation, a short-
IN secondary-side rated current of the transformer term peak voltage USS occurs, as shown in the following
calculation:
Calculation of the active resistances
USS = 2×(2×U Kn ×(U p - UKn))+0.5 < 3 kV
The relevant resistances in the differential circuit add
up to a total (circle-) resistance:
USS = 2×(2×25 V ×(8187.5 V - 25 V)) +0.5
UKn
R circuit = = R Sr + 2×RL+RS+R r = 1.28 kV
2×ISet
USS2 12802 V2
Pr = = 26.6 kW
Explanation: RSr 61.6 Ω
The calculation of P N and P F must be effected in any
Rkreis total resistance in the differential circuit case, in order to get the exact power range of the
Rsr stabilizing resistance stabilizing resistor.
Take over of power by the resistor in the event of a
RL resistance of the connection line between c.t. and
fault P F creates a short-term peak value.
relay
Rs secondary resistance of the transformer (<0.7Ω)
6.4.2 Example calculation -transformer
Rr relay input resistance (B1 - B2 = 0.02 W) An IRI1-ER protection relay is used for the earth-fault
ID tripping current protection of a 1.6 MVA-transformer (11000/415 V,
6%), see figure 2.1. The following c.t.s are used in the
The individual resistance values are: rigidly earthed starpoint:
2 x R L = 150 mΩ, at 20 m, 2.5 mm² Cu transformation ratio: 2 500/1A
2 ×R L + Rr + RS = 0.87 Ω class: X
Therefore, the following is valid: resistance Rs: 8 Ω
knee-point voltage: 250 V
25 V
Rkreis = = 62.5 Ω The relay is situated about 20m away from the c.t.s
2×0.2 A
and is connected with a 2.5 mm 2 cable.
Calculation of the stabilizing voltage
Calculation of the stabilizing resistance
The primary-side fault-current IF,prim is:
The stabilizing resistance is calculated from above
ratios, as follows: 1600000 VA
I F,prim = = 37.1 kA
√3 X 415 V X 6%
RS = Sr circuit - (2 × RL + Rr + RS)
Line resistance RL (2.5 mm² ~ 7.46 Ω /km)
= Rcircuit - 0.87 Ω
7.46 Ω
= 61.6 Ω RL = 20 m X = 0.15 Ω
1000 m
Additional resistance R r (ca. 0.02 Ω)
In operational mode < ID, the output requirement PN is
as follows:

8
IRI1-ER- Stablized Earth Fault Current Relay

From this results the stabilizing voltage for: 37.1 kA × 1


I F,prim Up = X (8 + 2 X 0.15Ω
2500
US = X (2 X R L + R S + R r)
n + 0.02Ω + 308.75Ω) = 4.7 kV
37100 A × 1 USS = 2 X (2 X 250 V X (4700 V X 250 V)) +0.5
US = X (2 X 0.15Ω + 8Ω+ 0.01Ω)
2500
=123.5 = 298

Since the knee-point voltage shall be Ukn = 2x US (2 x Since the requirement is met, the set values and the
123.5V = 247 V), the above transformer with U kn = resulting resistance values can be accepted.
250 V can be used. The calculation of the output requirement for the
Calculation of the set current and the stabilizing stabilizing resistance can be carried out similar to the
resistance (sample value) calculation of sample 6.4.1.

The rating for the set current of 20% is calculated:


ID = 20 % x I N = 0.2 x 1 A = 0.2 A
6.5 Application of IRI1-3ER relay as
High Impedance Bus Differential
From this results the stabilizing resistance for: Protection:

US 123.5 V
Rcircuit = ~ R Sr => = 617.5Ω IRI-1ER or IRI1-3ER (a 3-phase version of IRI1-1ER)
ID 0.2 A
relays also offers reliable Bus protection based on High
Impedance Differential Principle.
In the event of a fault, the stabilizing resistance must
withstand a secondary-side false current of: The figure below indicates a typical Single Bus system
using IRI-ER relay for Bus Protection. This sample system
incorporates two incoming and two outgoing bays.
IF sek = = 14.84 A In case of normal operation, following Kirchoff’s law, the
1600000 VA
currents terminating on bus and going put adds up to Zero
√3 X 415 V X 6% X 2500 with corresponding reproduction on CT secondary side of
respective bays. As the vector summation of the currents
The calculation of the short-term peak voltages balances each other out, the Relay does not operate.
provides the following result:

37.1 kA × 1
US = X (8Ω + 2 X 0.15Ω
2500

+ 0.02Ω + 615Ω) =9.25 kV


Thus, the ratio
USS = 2 X (2 X UKn X (U p - U Kn))+0.5 < 3 kV
USS = 2X(2X250 V X(9250 V - 250V))+0.5
Fig. 6.1
= 4.24 kV
is not reached and the calculation must be repeated In case of internal faults, as the fault currents will be fed
with a higher set current. from all sources possible, the differential current will
Calculation of the set current and the stabilizing operate the relay.
resistance (actual value) For External fault, though the amount of current flowing
The rating for the set current of 40% is calculated into the fault will increase, the net summation of the
again: current again will zero and the relay will restrain.
ID = 40 % x I N = 0.4 x 1 A = 0.4 A Here, it is important to consider unequal saturation
characteristics of the Current transformers involved. It is
From this results the stabilizing resistance for: also important to ascertain that the relay remains stable
in presence of Harmonics and DC currents.
US 123.5 V
Rcircuit = ~ RSr =>
ID 0.4 A

= 308.75 Ω
Thus, the requirement of the short-term peak voltage
is met.

9
IRI1-ER- Stablized Earth Fault Current Relay

Especially for a Bus Differential relay, following factors 0.02


are vital: RL : = 0.5 Rct : = 6 Zr : = Zr = 0.125
Id2
 Because of higher concentration of fault MVA, the Kpv : = Ifs . (Rct + 2.RL)
Relay should operate very fast for heavy internal
faults. Kpv : = 186.667

 The Relay should be reliably stable in presence of Knee point required for the CT core should higher than,
Harmonics – especially 2nd and 3rd harmonics – and
presence of DC currents. KpvCT : = 2 . Kpv KpvCT = 373.333

IRI1-ER relays ensure:

 Operating time of less than 15 milliseconds at more Rs : = [( Kpv


Id
) -Zr ] Rs = 466.542
than 5 times of the setting.

 2nd Harmonic rejection ratio of more than 4.


Up : = Ifs . (Rs + 2.RL + Rct + Zr)
 rd
3 Harmonic rejection ratio of more than 40.
Up = 1.263 x 104 1.594 . 10000 = 1.594 x 104
 Remains very stable against superimposed DC
Uss : = 2 . [2 . Kpv. (Up - Kpv]0.5
currents.
Rs : Stabilising Resistance in Ohms Uss = 4.311 x 103

Id : Differential Current Setting


Kpv
Up : Peak Voltage neglecting Saturation =0.2
2.Rs
Uss : Short term peak Voltage considering Saturation

Ifs: Secondary value of Fault Current The use of Metrosil can be avoided as the relay can
reliably withstand Uss up to 5 kV. For fault currents
Ifmax : 40000 kV : = 220 CTR : = 1500 exceeding this level, the Metrosils should be used.

MVAf : =√3.kV.Ifmax MVAf = 1.524 x 107 Id : = 4


Ifmax
Ifs : = Ifs = 26.667
CTR

10
IRI1-ER- Stablized Earth Fault Current Relay

7. Housing The following figure shows the terminal block of IRI1-


ER:
The IRI1-ER can be supplied in an individual housing
for flush-mounting or as a plug-in module for
installation in a 19" mounting rack according to DIN
41494.
Both versions have plug-in connections.
Relays of variant D are complete devices for flush
mounting, whereas relays of variant A are used for 19“
rack mounting.
7.1 Individual housing
The individual housing of the IRI1-ER is constructed for
flush-mounting. The dimensions of the mounting frame
correspond to the requirements of DIN 43700 (76 x
142 mm). The cut-out for mounting is 68.7 x 136.5
mm.
The front of the IRI1-ER is covered with a transparent,
sealable flap (IP54).
7.2 Rack mounting
The IRI1-ER is in general suitable for installation in a
modular carrier according to DIN 41494. The
installation dimensions are: 12 TE; 3 HE.
According to requirements, the IRI1-ER-devices can be
delivered mounted in 19" racks.
Fig. 7.1: Terminal block of IRI1-ER
If 19" racks are used the panel requires protection
class IP51.
8. Relay testing and commissioning
7.3 Terminal connections
The following instructions should help to test the
The plug-in module has very compact base with plug protection relay performance before or during
connectors and screwed-type connectors. commissioning of the protection system. To avoid a
relay damage and to ensure a correct relay operation,
 max. 15 poles screw-type terminals for voltage
be sure that:
and current circuits (terminal connectors series A
and B with a short time current capability of 500  the auxiliary power supply rating corresponds to
A / 1 s). the auxiliary voltage on site
 27 poles tab terminals for relay outputs, supply  the rated current and rated voltage of the relay
voltage etc.(terminal connectors series C, D and correspond to the plant data on site
E, max. 6 A current carrying capacity).
 the current transformer circuits are connected to
Connection with tabs 6.3 x 0.8 mm for cable up
the relay correctly
to max. 1.5 mm 2 or with tabs 2.8 x 0.8 mm for
cable up to max. 1 mm 2.  all signal circuits and output relay circuits are
connected correctly
By using 2.8 x 0.8 mm tabs a bridge connection
between different poles is possible. 8.1 Power On
The current terminals are equipped with self-closing NOT E !
short-circuit contacts. Thus, the IRI1-ER-module can
Prior to switch on the auxiliary power supply, be sure
be unplugged even with current flowing, without
that the auxiliary supply voltage corresponds to the
endangering the current transformers.
rated data on the type plate.
Switch on the auxiliary power supply to the relay
(terminal C9/E9) and check that the LED „ON“ on the
front plate lights up green.
8.2 Checking the set values
Check the DIP-switch positions, in order to verify the
parameterized set value. If necessary, the set value
can be corrected by means of the DIP-switch.

11
IRI1-ER- Stablized Earth Fault Current Relay

8.3 Secondary injection test  switching device

8.3.1 Test equipment  timer

 ammeter 8.3.2 Example of a test circuit for a


 auxiliary power supply with a voltage IRI1-3ER -relay
corresponding to the rated data on the type plate For testing the IRI1-3ER-relay, only power signals are
 single-phase AC-power supply (adjustable from 0 required. Fig. 8.3.1 shows an example of a test circuit
- 2.0 x IN) with adjustable power supply. The phases are tested
individually one after the other.
 test leads and tools
 potentiometer
L+/L L-/N
C9 E9 D9

Power
Supply
~

+
1 4 2
B1 ID D1
A
Trip C1
5 ID E1
B2 50/60Hz

Current source D2
B3
C2

ID l E2
B4 50/60Hz

B5

B6 50/60Hz Reset
Start
+ Timer
6

Stop
-
3
1. Current source
2. Amperemeter
3. Relay under test
4. Potentiometer adjust resistor
5. Switching device
6. Timer

Fig. 8.3.1 Test circuit IRI1-3ER

8.3.3 Checking the pick-up and tripping 8.3.4 Checking the operating and
values ( IRI1-ER ) resetting values (IRI1-3ER)
With the IRI1-ER, the analog input signal of the With the IRI1-3ER, all analog input signals of the
singlephase testing AC must be supplied to the relay via single-phase current must be supplied to the relay via
the terminals B1/B2 for checking the pick-up value ID. the terminals B1/B2; B3/B4; B5/B6 one after another
For testing the differential current pick-up value, first for checking the pick-up value I D in similar manner as
the injected current must be set below the set pick-up indicated above in para 8.3.3.
value I d. Then the injected current is increased 8.4 Primary injection test
gradually, until the relay trips. This is indicated by the Principally, a primary injection test (real-time test) of a
LED I D lighting up red, with the relay tripping at the c.t. can be carried out in the same way as a secondary
same time. Check that the value shown at the ammeter injection test. Since the cost and potential hazards may
does not deviate by more than +/- 3% from the set be very high for such tests, they should only be carried
pick-up value ID. out in exceptional cases, if absolutely necessary.
The resetting value of the differential current pick-up 8.5 Maintenance
value is determined, by slowly decreasing the testing Maintenance testing is generally done on site at regular
AC, until the output relay I D trips. The LED I D intervals.These intervals may vary among users
extinguishes (supposed the respective coding was depending on many factors: e.g. type of protective
effected). relays employed; type of application; operating safety
Check that the resetting value is greater than 0.97 of the equipment to be protected; the user’s past
times the pick up value, i.e. the resetting ratio of the experience with the relay etc.
differential current supervision is below 1. For static relays such as the IRI1-ER/-3ER,
maintenance testing once per year is sufficient.

12
IRI1-ER- Stablized Earth Fault Current Relay

9. Technical Data
9.1 Measuring input
Rated data:
Nominal current IN : 1A/5A
Nominal frequency f N : 50/60 Hz
Power consumption : <1 VA/at IN = 1A
in current circuit : <5 VA/at I N = 5 A
Thermal withstand : dynamic current withstand (half-wave) 250 x IN
capability of current : for 1 s 100 x IN
circuit : for 10 s 30 x IN
continuously 4 x IN
9.2 Auxiliary voltage
Rated auxiliary voltage U H :
24 V - working range : 16 - 60 V AC / 16 - 80 V DC
110 V - working range : 50 - 270 V AC / 70 - 360 V DC
Power consumption:
24 V - working range : standby approx. 3 W operating approx. 6 W
110 V - working range : standby approx. 3 W operating approx. 6 W
9.3 General data
Permissible interruption of
the supply voltage without
influence on the function : 50 ms
Dropout to pickup ratio : >97%
Returning time : 30 ms
Minimum operating time : 30 ms
9.4 Output relay
The output relay has the following characteristics:
Maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A
Breaking capacity for DC:
Ohmic L/R = 4 ms L/R = 7 ms
300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W
250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W
110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.20 A / 22 W
60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.30 A / 17 W
24 V DC 6.0 A / 144 W 4.2 A / 100 W 2.50 A / 60 W

Max. rated making current : 64 A (acc. VDE 0435/0972 and IEC 65 / VDE 0860 / 8.86)
Making current : minimum 20 A (16ms)
Mechanical life span : 30 x 106 switching cycles
Electrical life span : 2 x 105 switching cycles at 220 V AC / 6 A
Contact material : silver-cadmium-oxide

13
IRI1-ER- Stablized Earth Fault Current Relay

9.5 System data


Design standard : VDE 0435, part 303, IEC 255.4, BS 142
Specified ambient service
Temperature range:
for storage : - 40°C to + 85°C
for operating : - 20°C to + 70°C
Environmental protection
class F as per DIN 40040
and per DIN IEC 68 2-3 : relative humidity 95 % at 40°C for 56 days
Insulation test voltage, inputs
and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2/50 Hz; 1 min.
(except supply voltage inputs)
Impulse test voltage, inputs
and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2 / 50 μs; 0.5 J
High frequency interference
test voltage, inputs and outputs
between themselves and to the
relay frame as per DIN IEC 255-6 : 2.5 kV / 1MHz
Electrostatic discharge (ESD)
test as per DIN VDE 0843, part 2
IEC 801-2 : 8 kV
Electrostatic discharge (ESD)
test as per DIN VDE 0843, part 4
IEC 801-4 : 4 kV / 2.5 kHz, 15 ms
Radio interference suppression
test as per EN 55011 : limit value class B
Radio interference field
test as per DIN DVE 0843, part 3
IEC 801-4 : electrical field strength 10 V/m
Mechanical tests:
Shock : class 1 acc. to DIN IEC 255-21-2
Vibration : class 1 acc. to DIN IEC 255-21-1
Degree of protection - front of relay : IP 54 by enclosure of the relay case and front panel
(relay version D)
Weight : approx. 1.5 kg
Degree of pollution : 2 by using housing type A
3 by using housing type D
Overvoltage class : III
Influence variable values:
Frequency influence : 40 Hz < f < 70 Hz: <3 % of set value
Auxiliary voltage influence : no influence within the admissible range

9.6 Setting ranges and steps

Relay type Parameter Setting range Steps Tolerances


IRI1-ER ID 5 % ... 82.5 % x I N 2.5 % ± 3 % of set value
IRI1-3ER ID 5 % ... 82.5 % x I N 2.5 % ± 3 % of set value

14
IRI1-ER- Stablized Earth Fault Current Relay

9.7 Dimensional drawing

260
230 76
36 16 68.7

136.5
142

142
76
Cut Out Dimensions
Installation Depth : 275mm
All dimensions in : mm

Please note:
A distance of 50 mm is necessary when the units are mounted one below the other in order to allow easy opening
of the front cover of the housing. The front cover opens downwards.

10. Order form

Stabilized earth-fault current relay IRI1-

Measuring of earth current 1 phase measuring 1ER


3 phase measuring 3ER

Rated current in the earth-fault phase 1A 1


3 phase measuring 5

Auxiliary voltage 24 V (16 to 60 V AC/16 to 80 V DC) L


110 V (50 to 270 V AC/70 to 360 V DC) H

Housing (12TE) 19” rack A


Flush mounting D

Technical data subject to change without notice!

15
Range of Protection Relays

BASIC RANGE
 Micro-controller based compact economical design
 DIN rail mounted
 Status indication via LED
 Step-less settings through front potentiometer

FUNCTIONAL RANGE
 Genset Supervision & Control
 Auto Synchroniser
 Load Balancing & Control
 Related Protection

HIGH-TECH RANGE
 Microprocessor based numerical protection
 Event & fault recording
 RS 485 communication
 Bright alpha-numeric display

INTEGERATED RANGE
 Numeric protection, solution for sub-station in association
with INGETEAM T&D, Spain
 Distance protection
 Comprehensive transformer protection –
a. Three winding transformer
b. Two winding transformer
 Multi-functional relay: variety of protection combination

C&S Electric Ltd.


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
HR/IRI1-ER/12.12.2008

E-mail: cspc@controlsindia.com Web : www.cspcindia.com

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34
High-Tech Range
IRI1- WD (Overcurrent, Short-circuit and
Earth Fault Relay)

C&S Electric Ltd.


(Protection & Control Division)
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

Contents

1 Introduction

2 Application

3 Characteristics and Features

4 Design
4.1 Analog input
4.2 Front Panel
4.2.1 LCD
4.2.2 Keypad

5 Working Principle
5.1 Analog circuits
5.2 Digital circuits
5.3 Power supply
5.4 Demands imposed on the main current transformers

6 Operation and Settings


6.1 Layout of operating elements
6.2 Calculation of the setting values
6.2.1 Phase-over-current stage ( I > )
6.2.2 Dependent over-current time protection
6.2.3 Phase-over-current stage ( I >)
6.2.4 Time multiplier setting
6.2.5 Fast tripping short circuit protection ( I >>)
6.2.6 Fault Recording

7 Housing
7.1 Flush mounting
7.2 Rack mounting
7.3 Terminal Details
7.4 Circuit Diagram

8 Test and Maintenance

9 Technical Data
9.1 Measuring Input
9.2 Auxiliary voltage
9.3 General data
9.4 Setting Ranges and Steps
9.4.1 Independent time over current, earth fault and short circuit protection
9.4.2 Dependent time over-current, earth fault and short circuit protection
9.5 Tripping Characteristics
9.6 Setting Procedure
9.7 Output Relays
9.8 System Data
9.9 Mechanical Tests
10.0 Dimensional Drawing

2
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

1. Introduction  Selectable protective functions between: definite


The application of powerful microcontroller opens a time over-current relay and inverse time over-
new chapter for power protection systems. Because of current relay.
their capabilities to process the measuring values digitally  Selectable inverse time characteristics according
and to perform arithmetical and logical operations, the to BS 142 and IEC 255-4:
digital protective relays are superior to the traditional Normal inverse
analogue devices. In addition, the digital protective relays Very inverse
offer some additional advantages such as very low power Extremely inverse
consumption, adaptability, possibilities for self supervision,  Field selectable 1A/5A CT
flexible construction, selection of relay characteristics etc.  Independent stage for the fast tripping of short-
circuit (protection)
The development of microcontroller-based protective  Two stage over-current time protection for phase
relays and their introduction into the market are stimulated current
by the trend nowadays to replace analogue with digital  Two stage over-current time protection earth fault
protective equipment. current
 Extremely wide setting ranges and fine steps for
The superiority of digital protective relays to the traditional
current and time settings
systems is enhanced by the MR relay family which has
 Continuous self-supervision of software and
the following characteristics:
hardware
 Integration of multiple protective functions into  Wide operating ranges of the supply voltage
one compact housing (AC/DC)
 High measuring accuracy due to digital processing
of measuring values 4. Design
 Digital relay setting with very wide setting ranges 4.1 Analog Input
and the fine setting steps The analog input signal of the conductor currents as per
 Operation reliability due to continuous self- the terminal detail section 7.3, are fed to the protective
supervision device via separate input transformers.
The continuously measured current values are galvanically
The digital time relay IRI-WD was designed as a universal isolated, analog filtered and finally fed to the analog/
over-current relay for application to medium voltage digital converter.
networks.
4.2 Front Panel
2. Application The front panel of the protective device IRI-WD comprises
The digital over-current time relay IRI-WD is a universal the following operation and indication elements:
protection device for low and medium voltage networks.  1 LCD- Liquid crystal display ( 8 x 2)
It is used in radial networks and combines the following  4 keypads- for the setting of the tripping
functions in one unit: values and time.
 3 LEDs for the fault indication.
 Independent (Definite) time over-current relay  1 RESET button
 Inverse definite minimum time over-current relay
with following selectable characteristics: 4.2.1 LCD
 Normal inverse The over-current, short-circuit and earth fault relay IRI-
WD is equipped with a back-lit LCD display having two
 Very Inverse
lines of eight alpha-numeric characters to display current,
 Extremely inverse
faults, setting parameters names and values etc.
 Integrated independent and dependent over
current time protection for the earth fault 4.2.2 Keypads
The front panel keypad consists of five soft-touch keys.
Furthermore, the device, providing the above functions, These keys are marked as “RESET”, “+”, “-” “” and
can be employed as back-up protection for differential “”. The “RESET” key provides reset functions to the
and distance protection relays relay. The keys marked “” and “” are meant for
backward and forward scrolling respectively. The keys
3. Characteristics and Features marked “+” and “-” are used for decrementing and
 Digital processing of the sampled measuring incrementing selected parameter value.
values
 Digital filtering of the measured values by using 4.2.3 LEDs
discrete Fourier analysis to suppress the high On the front panel there are 3 LEDs. Their functions are
frequency harmonics and transient dc indicated by the appropriate inscriptions along with them.
components during short circuit. At the time of pickup the Alarm LED starts blinking.

3
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

On fault trip LED gives the indication. Similarly when there The lower consumption of the IRI--WD i.e. 0.2 VA, has a positive
is a pickup in any of the phase, one can’t change the effect on the rating of the current transformers. It implies that,
setting of the relay. At that time all functions will be blocked if an electromechanical relay is replaced by IRI-WD, a high
& this is indicated by BLOCK LED. accuracy limit factor is automatically obtained by using the
same current transformer.
5. Working Principle
5.1 Analog circuits 6. Operation and Settings
The incoming currents from the main current transformers 6.1 Layout of operating elements
on the protected objects are converted to voltage signals All keys and “RESET” button required for the setting of
in proportion to the currents via the input transducers and parameters are located on the front panel.
shunt resistors. The noise signals caused by inductive and
capacitive coupling are suppressed by an analog R-C filter 6.2 Calculation of the Setting values
circuit. The analog voltage signals are fed to the A/D- 1A / 5A choice is site selectable. Separate terminals are
converter of the microprocessor and transformed to digital provided for 1A and 5A CTs. User must make correct choice
signals through Sample and Hold circuits. All the from front panel.
processing is carried out on these digitized values. The
measuring values are detected with a sampling frequency 6.2.1 Phase-over-current stage (I >)
of 1600 Hz, a sampling rate of 625 μs for each The main criterion for the setting of the over-current response
measurement (at 50 Hz). value is the normal maximum operating current which is
therefore adjusted to about 20% for power line, about 50 %
5.2 Digital circuits for transformers and motors, above the maximum expected
The protective device is equipped with an efficient load currents. The delay of the trip signal is selected according
microprocessor which is the main processing unit. It to the selectivity and time grading, and the system overload
digitally carries out all of the operations, from the capacity of the protected object.
digitization of the measuring values to the protective
tripping. 6.2.2 Dependent over-current time protection
The relay program is located in an EPROM (Read-Only- Apart from the selection of the tripping characteristics, the
Memory). With this program the microprocessor processes response value for the phase-current is also adjustable.
the voltages at the analog inputs and calculates the
fundamental components of the current. For the 6.2.3 Phase-over-current stage (I >)
calculation of the current value an efficient digital filter The starting current is determined according to the maximum
based on the Fourier Transformation (DEFT-Discrete Fast expected load current. For example:
Fourier Transformation) is applied to suppress high
frequency harmonics and d.c. components during a short Current transformer ratio: 400/5 A
Maximum expected load current: 300 A
circuit. Overload coefficient: 1.2 (assumed)
The measured current values are continuously compared Starting current setting: IS = (300 / 400) x 1.2 = 0.9 x IN
with the set values and when activated, the over-current
tripping time is determined according to the selected 6.2.4 Time multiplier setting
characteristic curve. When the calculated time delay has The time multiplier setting for inverse time over-current is a
elapsed, a tripping command is given. scale factor for the selected characteristics. The characteristics
for two adjacent relays should have a time interval of about
5.3 Power Supply 0.3 - 0.4 s.
It has a universal auxiliary supply. The voltage range is
(16 to 270) VAC & (16 to 360) VDC 6.2.5 Fast tripping short circuit protection (I >>)
The high-set current setting is set as a multiplier of the nominal
5.4 Demands imposed on the main current current. The time delay is always independent to the fault
transformers current.
The current transformers have to be rated in such a way, Short Circuit Protection: The Current setting range is from
that a saturation should not occur within the following 0.5 x In to 25 x In. It is possible to have selectable time delayed/
operating current ranges: Instantaneous protection.
Independent time over-current function K1 = 2 High set E/F protection: The Earth fault current setting
Inverse time over-current function K1 = 20 range is from 0.5 to 15 x In.
High-set function K1 = 1.2 - 1.5
K1 = Current factor related to set value with the current 6.2.6 Fault Recording
transformer not yet operating in the saturation range. IRI records last three faults. It saves following information

Moreover, the current transformers have to be rated Type of fault : SC / OL


according to the maximum expected short circuit currents Faulty phase / Earth : R / Y / B / E
of the network or the object to be protected. Value at Fault : Ir, Iy, Ib, Ie in Amps
Fault1 is the latest fault & Fault 3 is the oldest fault.
(True RMS record available when trip time > 40msec.)

4
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

6.2.7. Reset Delay 7.4 Circuit Diagram


This parameter (RST-D) introduces a delay in opening of
relay contacts, when the current goes below the drop up
value for overload and short circuit.

7. Housing
The IRI-WD can be supplied in an individual housing for
flush-mounting for installation in a 19" mounting rack
according to DIN 41494. Both versions have plug-in
connections.

7.1 Flush mounting


The individual housing of the IRI-WD is constructed for
flush-mounting. The dimensions of the mounting frame
correspond to the requirements of DIN 43700 (76 x 142
mm). The cut-out for panel mounting is 68.7 x 136.5
mm.

The front panel of the IRI-WD is covered with a transparent,


sealable flap (IP54).

For case dimensions and cut-out refer to “technical data”.


The individual housing is fixed with the supplied clasps
from the rear of the panel.

7.2 Rack mounting


The IRI-WD is in general suitable for installation in a
modular carrier according to DIN 41494. The installation
dimensions are: 12 TE; 3 HE. According to requirements,
The IRI-WD devices can be delivered mounted in 19" racks.

7.3 Terminals 8. Test and maintenance


The following figure shows the terminals back of IRI-WD. The measuring input circuits are of completely static design
and the relay functions are entirely digital so that the IRI-
WD has no requirement for maintenance.

A B

C D E
1

5
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

9. Technical Data

9.1 Measuring input

Rated data : Rated current IN 1A or 5A


Rated frequency FN 50Hz
Power consumption in : At IN = 1A 0.2 VA
current circuit At IN = 5A 0.1 VA
Thermal withstand capability : dynamic current withstand 250 x IN
in current circuit (half-wave)
for 1 s 100 x IN
for 10 s 30 x IN
continuously 4 x IN

9.2 Auxiliary voltage

Rated auxiliary voltage UH : Universal 16 VAC to 270 VAC


16 VDC to 360 VDC
Power consumption : Quiescent approx. 3W Operating approx. 6W

9.3 General data

Dropout ratio : > 97 %


Returning time : 30 ms
Time lag error class index E : ± 10 ms
Minimum operating time : 30 ms
Transient overreach at
instantaneous operation : 5%

9.4 Setting ranges and steps

9.4.1 Independent time phase over-current, earth fault and short circuit protection

Parameter Display Setting Range Step Tolerances

I> IS 0.20 - 2.5xIN 0.05 x IN +


_ 5% from set value
t> 0.1 - 150s 0.01S +
_ 3% +
_ 10 ms

I>> IS 0.5-25 x IN 0.5 x IN +


_ 5% from set value
t>> 0.02-20S 0.01S +
_ 3% +
_ 10 ms

IE> IS 0.05-2.5 x IN 0.5 x IN +


_ 5% from set value
tE> 0.03-150S 0.01S +
_ 3% +
_ 10 ms

IE>> IE>> 0.05-15 x IN 0.5 x IN +


_ 5% from set value
tIE>> 0.02-20S 0.01S +
_ 3% +
_ 10 ms

Reset Deley RST-D 0-20 Sec 0.1 Sec +


_ 3% or +
_ 10 ms
(Which ever is higher)

6
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

9.4.2 Dependent time phase over-current and earth fault protection

Parameter Display Setting Range Step

I> IS 0.20 - 2.5xIN 0.05 x IN


ti> 0.1 - 1.500 0.005

IE> IS 0.05-2.5 x IN 0.05 x IN


tiE 0.01-1.500 0.005

Reset Deley RST-D 0-20 Sec 0.1 Sec

Tripping characteristics according to IEC 255-4 or BS 142

0.14
Normal Inverse 3.0 t = ti [s]
(I / IS) 0.02 – 1

0.061
Normal Inverse 1.3 t = ti [s]
(I / IS) 0.02 – 1

13.5
Very Inverse t = ti [s]
(I / IS) 2 – 1

80
Extremely Inverse t = ti [s]
(I / IS) 2 – 1

Where t = Tripping time ti = Time multiplier

I = Fault current IS = Setting value of current

Tripping Time Tolerance: Accuracy as per IEC-255-3 I/Is > 2 to I/Is < 20
For VINV / NINV :(+ 5% or + 20msec which ever is higher)
For EINV (+ 7.5% or + 20msec which ever is higher)

7
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

9.5 Tripping characteristics

100
100

tI>=
10
10
t[s]
tI>=
t[s]

1.5
1.3
1.0
0.8
1 1.5
0.6 1.3
0.5 1.0
1 0.4 0.8
0.3 0.6
0.5
0.2 0.4
0.3

0.2
0.1
0.1
1 2 3 4 5 6 7 8 9 10 20
0.1
I/IS
1 2 3 4 5 6 7 8 9 10 20
I/IS

Normal inverse Very inverse

100
100

I>
0.5 2.05

10
10

t[s] 150
t[s]
tI>= tI >

1
1 0.1
I>>
2.0 33.5
1.5
1.3 1.55
1.0
0.8
0.6 0.1 t l >>
0.1 0.5
0.4
0.3
0.05
0.2
0.1

1 2 3 4 5 6 7 8 9 10 20
0.01
I/IS 1 10
I/IN
Extremely inverse Definite time overcurrent relay

8
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

9.6 Setting Procedure


Menu Frames
Menu 1 Menu 8 # In #
Ir Iy Ib Ie XX XX A (RMS)
Default Page Pressing Reset Key 1A
<PICKUP> OL Status / SC Status
(Running Parameters) on In selection) 5A
#STATUS#  BACK
<FAULT1>
<FAULT2> Menu 9 # E-HIGH #
Menu 2 <FAULT3> Pressing Reset Key I : X.XX In
(Pressing Reset Key) <EDIT> on E-High selection) t : XXX . X s
<In>  BACK
CHG PSWD
 BACK < TRIP>
OL : R Y B E
Menu 3 #EDIT# Menu 10 SC : R Y B E
(Pressing Reset Key <CHAR> Pressing Reset Key [F] Ir XX.XXA (Fault Current)
on EDIT selection) <O/L> on FAULT 1, 2, 3 [F] Iy XX.XXA (Fault Current)
<S/C>
selection) [F] Ib XX.XXA (Fault Current)
<Earth>
<E-High> [F] Ie XX.XXA (Fault Current)
RST-D  BACK
Menu 11 ?PSWD?
#CHAR# Pressing Reset Key Loading...
Menu 4: DEFT on LOAD DEFAULT)
(Pressing Reset Key EINV
?PSWD?
on CHAR selection) VINV Menu 12 New PSWD
NINV1.3
NINV3.0 Pressing Reset Key
on CHG PSWD Re PSWD
 BACK
selection) SUCCESS
# O/L # PSWD CHG
Menu 5: I : X.XX In
Menu 13 Save ?
(Pressing Reset Key ti : X.XXX s
t : XXX . X s YES NO
on O/L selection) ?PSWD?
 BACK Menu 14
SAVING ...
Menu 6 # S/C #
I : X.XX In Menu 15 PSWD
(Pressing Reset Key
t : XXX . X s ! INVALID
on S/C selection)  BACK
Menu 7 # EARTH #
(Pressing Reset Key I : X . XX In ti : Time multiplier setting only for Inverse
on Earth selection) ti : X.XXX s time characteristic
t : XXX.X s t : Timer setting only for definite time
 BACK characteristic

Basic Key Functions

KEY FUNCTION
Reset annunciation / Enter Key
confirm selection of item in the
RESET menu & save value

Up scroll for the menu
+ Increment selected parameter
- Decrement selected parameter

 Down scroll for the menu

NOTE: All keys can be used in selecting / specifying password Pressing Reset key for 1 sec,
cursor will go back to the default page

9
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

9.7 Output Relays

Number of relays : 4
Contacts : 2 change-over contacts each for trip relay I > and
I >> , IE > and IE >>
Max. breaking capacity : 1250 VA / 150 W resistive
500 VA / 90 W inductive
Max. breaking voltage : 400 V AC, 125 V DC
Max. continuous current : 5A
Max. making current (16 ms) : 20 A

9.8 System data

Design standard : VDE 04335, part 303, IEC 255-4, BS 142


Specified ambient service Temp. range
 For storage - 40 ºC to + 85 º C
 For operation - 20 ºC to + 70 ºC
Environmental protection class F as per : Relative humidity 95 % at 40 ºC for 56 days
DIN 40040 and per DIN IEC 68, part 2.3
Isolation test voltage, inputs and outputs between : 2.5 kV (eff.) / 50 Hz, I min.
themselves and to the relay frame as per
VDE 0435, part 303
Impulse test voltage, inputs and outputs between : 2.5 kV (eff.) / 50 Hz, I min.
themselves and to the relay frame as per
VDE IEC 0435, part 303
High frequency interference test voltage, inputs and : 2.5 kV / 1 MHz
outputs between themselves and to the relay frame as per
DIN IEC 255, part 22-1
Electrical fast transient (Burst) test as per : 4 kV / 2.5 kHz, 15 ms
DIN VDE 0843, part 4
Radio interference suppression test as per : Limit value class B
DIN VDE 57 871
Electrostatic discharge (ESD) test as per : 8 kV
DIN VDE 0843 part 2
Radiated electromagnetic field test : 10 V / m
as per VDE 0843 part 2

Mechanical Tests

Shock : As per DIN IEC 41 B (CO) 38 : class 1


Vibration : As per DIN IEC 41 B (CO) 35 : class 1
Protection-front panel : IP 54
Protection-rear panel : IP 00
Weight : Approx. 1.5 kg

10
IRI1- WD - Overcurrent, Short-circuit and Earth Fault Relay

10.0 Dimensional Drawing

11
Range of Protection Relays

BASIC RANGE
 Micro-controller based compact economical design
 DIN rail mounted
 Status indication via LED
 Step-less settings through front potentiometer

FUNCTIONAL RANGE
 Genset Supervision & Control
 Auto Synchroniser
 Load Balancing & Control
 Related Protection

HIGH-TECH RANGE
 Microprocessor based numerical protection
 Event & fault recording
 RS 485 communication
 Bright alpha-numeric display

INTEGERATED RANGE
 Numeric protection, solution for sub-station in association
with INGETEAM T&D, Spain
 Distance protection
 Comprehensive transformer protection –
a. Three winding transformer
b. Two winding transformer
 Multi-functional relay: variety of protection combination

C&S Electric Ltd.


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
E-mail: cspc@controlsindia.com Web : www.cspcindia.com
IRI-WD/20.11.07

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34
IRI Pro
Over-current, Short-Circuit and Earth Fault Relay

L1 : 01.00A
L2 : 00.00A

IRI-PRO

C&S Electric Ltd.


(Protection & Control Division)
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Characteristics and Features Power Supply

 Microcontroller based Numeric Relay It has a universal auxiliary supply. The voltage range is
24V to 260VAC and 24V to 360VDC.Power supply
 Digital filtering of the measured values to suppress connections are not polarized.
the high frequency harmonics and transient dc
components during short circuit
Fault Recording
 Selectable protective functions between: definite time
over-current relay and inverse time over-current relay IRI-PRO records last three faults. It saves following
information with secondary CT current in non-volatile
 Selectable inverse time characteristics according to
memory in following sequence.
BS142 and IEC 255-4:
Normal inverse3.0 Type of fault : SC / OL
Normal inverse1.3 Faulty phase / Earth : L1 / L2 / L3 / E
Normal inverse0.6 Value at Fault : L1, L2, L3, Ie Amps
Very inverse (True RMS recording guaranteed only if trip time >= 40msec)
Extremely inverse
 Two stage over-current time protection for phase Reset Delay
current / earth fault current
This parameter [RST-D] introduces a delay in opening of
 Separately selectable characteristic for Earth fault relay contacts, when the current goes below the dropout
 Continuous self-supervision of software and hardware value for overload and short circuit & earth faults. This
parameter will not work when manual reset mode is selected.
 Wide operating ranges of the supply voltage [AC/DC]
24V-270V AC/DC
Housing
 Last three faults recording
The IRI-PRO is supplied in an individual housing for flush-
 Relay assignment configurable from HMI mounting for installation in a DIN standard of 96 x 96
 Relay reset configurable from HMI mm.

IRI-PRO
 Self supervision output contact
1 2 3 4 5 6 7 8 9

Relay1 NO
Relay4,3 COMM
Power Supply

Relay1 COMM
Power Supply

Relay4 NO

Relay3 NO

Relay2 NO
Relay2 COMM
Design
Front Panel
The front panel of the protective device IRI-PRO comprises
the following operational and indication elements:
Terminal Description
 1 LCD- Liquid Crystal Display ( 16 x 2)
CT_L2.1

CT_L3.1
CT_L2.2

CT_L3.2
CT_L1.1

CT_L1.2

 Touch keypads- for parameter setting


Earth
N2

N1

 8 LEDs for annunciation


10 11 12 13 14 15 16 17 18
LEDs
On the front panel there are 8 LEDs. Their functions are
indicated by the appropriate inscriptions. On fault I>, I>>, Trip Test
Ie> & Ie>> LEDs with appropriate phase lamps L1/ L2 /
This feature allows the user to check contact operation.
L3 give the fault indication. Flashing of the green LED
TRIP test can be used while commissioning the relay to see
marked ON gives the indication of healthiness of relay in
the operation of contacts of IRI-PRO. It is selectable from
terms of watchdog.
front LCD menu and becomes active only when currents
are below all pickup levels and trip levels. Selecting trip
Output Contacts test, gives the momentary operation of all four available
Relay1 is fixed for CB tripping, common for all type of contacts in IRI-PRO one by one with LED flashing indications.
faults. Relay2, Relay3 and Relay4 are user configurable
for annunciations like OL / SC /E /EH /Self supervision.
Reset function of all output contacts is individually
programmable [Auto Reset / Manual Reset] from HMI.
RESET DELAY is available with all output contacts but get
disable in Manual Reset mode.

2
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Contact Details Circuit Diagram

Number of relays 4 [Relay 1,2,3,4]


Aux Supply
L1 L+/L L-/L

Type of Contact For] (SPST-NO, type A ) common for L2 1 2 18 181


L3
CB Trip [Relay 1 trip on I > and I >> , IE > and
IE >>
Supply
Max. breaking capacity 1250 VA / 150 W resistive
For CB Trip 500 VA / 90 W inductive 9
( CB TRIP) RELAY -1
8

Max. breaking voltage 400 V AC, 125 V DC (ANN.) RELAY -2


6
7

For CB Trip
4
S1 16 N2 (ANN.) RELAY -3
P1 5
Max. continuous 10 A IE
4
current For CB Trip P2
S2 17 N1 (ANN.) RELAY -4
3

C i r c u i t
Max. making current 20 A
(16 ms) For CB Trip
IRI-Pro-EO
Contact For Annunciation (SPST-NC, type B) Group

[ Relay 2 , 3, 4] [Relay 2]
(SPST-NO, type A ) IRI-PRO-EO
[Relay 3]
(SPST-NO, type A )
[Relay 4]
[All are configurable for O/L,
S/C ,E,EH, Self supervision ] Aux Supply
L1 L+/L L-/L

L2 1 2 18
Max. breaking voltage 240V AC L3

For Annunciation

Max. continuous current 2A 10 L1.1 Supply

For Annunciation P1 S1
11 L1.2
I1

P2 S2 9
( CB TRIP) RELAY -1
8

6
(ANN.) RELAY -2
7

D i a g r a m
Technical Data 4
(ANN.) RELAY-3
5

Measuring input (ANN.) RELAY- 4


4

Rated data Rated current 1A or 5A50Hz


INRated IRI-Pro-I
Group

frequency FN
IRI-PRO-I
Power At IN = 1A 0.2 VA
consumption in At IN = 5A 0.1 VA
current circuit

Thermal for 1 s 100 x IN L1


Aux Supply
L+/L L-/L

withstand for 10 20 x IN L2

L3
1 2 1
18

capability in scontinuously 4 x IN N

current circuit
10 L1.1 Supply
S1
P1

11 I1
Dropout ratio > 96 % P2 S2 L1.2

( CB TRIP) RELAY -1 911

810
S1 12 L2.1
P1 612
(ANN.) RELAY- 2
713
Returning time 30 ms P2 S2 13 L2.2
I2

414
(ANN.) RELAY- 3
14 515
S1 L3.1

Minimum 30 ms P1

P2 S2 15 L3.2
I3
(ANN.) RELAY- 4
414

316

operating time
S1 16 N2
P1
IE
P2 S2 17
N1

Group IRI-Pro-3I-EI/3O-EO

IRI-PRO-3I-EI/3O-EO

3
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Parameter Display Setting range Step

I> IS 0.20 – 2.5 x IN 0.05 x IN


t> 0.1 –150 s 0.01 s
ti > 0.01 – 1.500 0.005

I >> I 0.5 – 25 x IN 0.5x IN


t >> 0.02 – 20 s 0.01 s

IE> Is 0.05 -2.5 x IN 0.05x IN


tE > 0.03 - 150s 0.01s
tiE 0.01 – 1.500 0.005

IE >> IE >> 0.5 – 15x IN 0.05 x IN


tIE >> 0.02 – 20 s 0.01s

Reset Delay RST-D 0 – 20sec 0.1sec

Trip Time ± 5% or + 20msec for VINV,NINV3.0/1.3, ± 3 % or ± 20 ms for DEFT


Tolerances (whichever is higher)
±7.5% or + 30msec (whichever is higher) for EINV , NINV0.6
Accuracy as per IEC-255-3 in band of (I/Is > 2 to I/Is<20)

Pickup Tolerances ± 5% from set value

0.14
Normal Inverse 3.0 t = ti [s]
(I / IS) 0.02 – 1

0.061
Normal Inverse 1.3 t = ti [s]
(I / IS) 0.02 – 1

0.028
Normal Inverse 0.6 t = ti [s]
(I / IS) 0.02 – 1

13.5
Very Inverse t = ti [s]
(I / IS) – 1

80
Extremely Inverse t = ti [s]
(I / IS) 2 - 1

CAUTION

O/L, S/C, E and EH protections are available


with DISABLE option in HMI.

4
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Dimensional Drawing

9 mm

8 mm
120 mm
130 mm

30 mm

12 mm

95 mm
89 mm
12 mm
30 mm

8 mm

8 mm

110 mm
120 mm
95 mm

91 mm

TRIP

RS 485

91 mm

95 mm

120 mm
95 mm
89 mm
79 mm

110 mm
120 mm

5
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Models Diagram

IRI-PRO EO IRI-PRO I
(1 E/F with High Set)

IRI PRO EO IRI PRO I

ON
+ ON
+ I>I>

L1 I>>
Ie>
RESET RESET

Ie>
- -
Ie>>
Ie>>

IRI-PRO 3I-EI IRI-PRO 3O-EO


(3O/C + 1 E/F with high set) (3 O/C, 1E/F without High-Set )

IRI PRO 3I-EI IRI PRO 3O-EO

ON + I> ON + I>

L1 I>> L1
RESET RESET

L2 Ie> L2 Ie>
- -
L3 Ie>> L3

6
IRI-Pro : Over-current, Short-Circuit and Earth Fault Relay

Order Form

IRI-PRO Protection Phase Rated Earth Rated

m
1 E/F with High set EO
3/OC + 1 E/F Without High set
r
3O-EO

o
F
3/OC +1 E/F with High set 3I-EI
1 O/C + High set

er I1

d
1

r
Rated Current(O/C Element) Amp
5

Rated Current(E/F Element) Amp O 1


5

7
Range of Protection Relays

BASIC RANGE
n Micro-controller based compact economical design
n DIN rail mounted
n Status indication via LED
n Step-less settings through front potentiometer

FUNCTIONAL RANGE
n Genset Supervision & Control
n Auto Synchroniser
n Load Balancing & Control
n Related Protection

HIGH-TECH RANGE
-
n Microprocessor based numerical protection
n Event & fault recording
n RS 485 communication
n Bright alpha-numeric display

INTEGERATED RANGE
n Numeric protection, solution for sub-station
in association with INGETEAM-T&D, Spain
n Distance protection
n Comprehensive transformer protection –
a. Three winding transformer
b. Two winding transformer
n Multi-functional relay: variety of protection combination

C&S Electric Ltd.


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
E-mail: cspc@controlsindia.com Web : www.cspcindia.com

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34
High-Tech Range
IRP1- Directional Power Relay

PR1 PR2 ON

RESET

2.0 2.5% 2.0 2.5%


0 1 0 1
0 2 0 2
PR1 0 4 PR2 0 4
0 8 0 8
D

0 0.1s 0 0.1s
0 0.2 0 0.2
tPR1 0 0.4 tPR2 0 0.4
0 0.8 0 0.8
0 1.6 0 1.6
X1 X20 X1 X20
D D

IRP1-1IU

C&S Protection & Control Ltd.


IRP1- Directional Power Relay

Contents

1. Introduction and application 6.3.1 Manual reset


6.3.2 Automatic reset
2. Features and characteristics
7. Housing
3. Design
7.1 Individual housing
3.1 Connections 7.2 Rack mounting
3.2 Analog input circuits 7.3 Terminal connections
3.3 Output relays
3.4 Front plate 8. Relay testing and commissioning
3.5 LEDs
3.6 <RESET>-pushbutton 8.1 Power-On
8.2 Checking the set values
4. Relay adjustment 8.3 Secondary injection test
8.3.1 Test equipment
4.1 Code jumpers 8.3.2 Test circuit
4.2 Y/Δ - DIP switch adjustment 8.3.3 Checking the operating and
resetting values of the relay
4.3 Coding of the phase shifter
8.3.4 Checking the trip delay
8.4 Primary injection test
5 . Working principle
8.5 Maintenance

5.1 Calculation of the setting value


9. Technical Data
9.1 Measuring input
6. Operations and settings
9.2 Auxiliary voltage
9.3 General data
6.1 Setting of the parameters by means
of DIP-switches 9.4 Output relays
6.1.1 Setting of the pickup value 9.5 System data
6.1.2 Setting of the trip delays 9.6 Setting ranges and graduation
6.2 Fault indication 9.7 Dimensional drawing
6.3 Reset
10. Order form

2
IRP1- Directional Power Relay

1. Introduction and applicaiton power forward power of Turbo generators and Diesel
generating sets if prime mover fails.
For the generator operating in parallel with a mains or
When compared with traditional protection systems the another generator, it is imperative to supervise the
protective relaying with IR - relays offer several power direction. If for example the prime mover fails
advantages. the alternator operate as a motor and drive the prime
IR - protection relays are based on microprocessor and mover (Diesel engine/Turbine). The IRP1 recognises
some on analog technique. They present our low priced the power direction and switches off the alternator. This
protection relay generation and are used for all basic way, power losses and damages to the prime mover
protection applications. are avoided.
The following properties of the IR-protection relays,
such as : 2. Features and characteristics

 Integration of multiple protection functions into  Static protection relay


one compact housing.
 User friendly setting procedure by means of DIP  Directional power measuring unit P R1 and P R2.
switches.  Sensitive power measuring with fine graded
 Compact design due to SMD technique. adjustment

 Separate adjustable trip delay for P R1 and PR2.


These are their superiority over the traditional  Phase shifting adjustment.
protection systems.
 Wide operating ranges of the supply voltage (AC/
DC).
All relays of this HIGH TECH RANGE are available
for through panel mounting and in 19" racks.  Plug in technology with self-shorting CT circuits.
Connection terminals are of plug in type. All IEC/DIN  Coding plug for presetting of LED indications and
regulations required for the individual applicaiton are the trip relays.
reliably met by this relay.
 Codable additional phase shifting.

The directional power relay IRP1 is used for reverse


power or forward power supervision in low voltage and
medium voltage systems. The relay may be used for
active power or reactive power application. The load is
measured in one phase only on assumption that the
phases are loaded symmetrically.
Among other applications the relay can be used as
directional power relay for protection against reverse

3
IRP1- Directional Power Relay

3. Design

3.1 Connections

The connection diagrams are given in the fig. 3.1 and fig. 3.2.

L+/L L-/N
L1 L2 L3
C9 E9 D9

Power
Supply ~
PR1 tPR1
PR1 Trip

D1
C1
P1 S1 B3 L1.1 P

U
l l E1
tPR1
I1 D2

P2 l C2
S2 B4 L1.2 E2

Reset

D3
C3

Phase Shift l E3
tPR2 D4
A a A3 L1.1
l C4
E4
B b A4 U1
l PR1 tPR1
300
600
900

L1.2 PR2 Trip


00

C c
l +5V l l l

Fig. 3.1: Connection diagram IRP1 for phase to neutral supply voltage

L+/L L-/N
L1 L2 L3
C9 E9 D9

Power
Supply ~
PR1 tPR1
PR1 Trip

D1
C1
P1 S1 B3 L1.1 P

U
l l E1
tPR1
I1 D2

P2 l C2
S2 B4 L1.2 E2

Reset

D3
C3

Phase Shift l E3
tPR2 D4
A a A3 L1.1
l C4
E4
B b A4 U1
l PR1 tPR1
0

900

PR2 Trip
30
60

L1.2
00

C c
l +5V l l l

Fig. 3.2: Connection diagram for phase to phase supply voltage

4
IRP1- Directional Power Relay

3.2 Analog input circuits

The analogue input signal of the phase current IL1, is


led to the protection relay via B3- B4. The phase-to-
phase or phase-to-neutral voltage are connected via
terminals A3 - A4. For medium voltage and high
voltage systems a voltage transformer is needed for PR1 PR2 ON
this. The system voltage of low voltage systems can be
connected directly to the measuring inputs.

RESET

3.3 Output relays 2.0 2.5% 2.0 2.5%


0 1 0 1
0 2 0 2
PR1 0 4 PR2 0 4
0 8 0 8
D
The IRP1 is equipped with two trip relays each with two
0 0.1s 0 0.1s
change-over contacts: 0 0.2 0 0.2
tPR1 0 0.4 tPR2 0 0.4
0 0.8 0 0.8
0 1.6 0 1.6
X1 X20 X1 X20
D D
 P R1 Tripping relay : C1, D1, E1 and C2, D2, E2
 P R2 Tripping relay : C3, D3, E3 and C4, D4, E4

3.4 Front plate


IRP1-1IU

The front plate of the protection relay IRP1 comprises


the following operation indication elements: Fig. 3.3: Front plate

3.5 LEDs
 4 DIP switches for the setting of the tripping values
and times
 5 LEDs for pick up/trip indication and readiness There are 5 LEDs at the front plate of the protective
for service relay IRP1 which indicate the following operational
modes:
 1 pushbutton <RESET>

 Readiness for operation, LED ON (green)


The detail of the front plate the relay IRP1 is shown in
the fig. 3.3.  Pickup of PR1, upper LED ON (yellow)
 Pickup of PR2, upper LED ON (yellow)
 Trip of PR1, lower LED ON (red)
 Trip of PR2, lower LED ON (red)

3.6 <RESET> Push button


Pushbutton <RESET> is used for acknowledgement
and reset after fault clearance.

The LEDs and output relays which are encoded for


latching must be reset manually by pressing the
pushbutton <RESET>.

5
IRP1- Directional Power Relay

4. Relay adjustment The position of the coding socket is shown in the fig. 4.3
and the function of the relay with different coding
4.1 Code jumpers jumper adjustment is given in the Table 4.1 below

There are 4 code jumpers behind the front plate


of the IRP1 at the lower part for presetting the LED
indications and the trip behaviour of the output
Front plate
relays.

The yellow pickup LEDs cannot be coded, they light PR1 PR2 ON

up as soon as the setting value is exceeded and


extinguish automatically when the setting value is
fall short. Before leaving the factory, all code
jumpers are pluged into their sockets.
PR1 PR2

The coding sockets are allocated to the functions


as follows: tPR1 tPR2

 Coding socket 1 + 2 = Reverse power


tripping PR1. Code jumper

 Coding socket 3 + 4 = Reverse power 1 23 4

tripping PR2.
Code jumper ON

Code jumper OFF

Fig. 4.3: Code jumper/socket

Code Junction Code jumper Mode


jumper position

1 Reverse power indication PR1 OFF latching of red LED PR1


ON automatic reset of red LED PR1

2 Reverse power tripping PR1 OFF latching of trip relay PR1

ON automatic reset of trip relay PR1


3 Reverse power indication PR2 OFF latching of red LED PR2

ON automatic reset of red LED PR2

4 Reverse power tripping PR2 OFF latching of trip relay PR2


ON automatic reset of trip relay PR2

Table 4.1: Function of code jumpers

6
IRP1- Directional Power Relay

Δ switch adjustment
4.2 Y/Δ Δ DIP switch and related phase shifting) is increased by
the set value. In this manner a certain characteristical
angle can be preadjusted. So, the maximum sensitivity
IRP1 relay can be used for active or reactive of the relay can be set to cos ϕ = 0.87 and 0.5
directional power protection. inductive or capacitive. Together with Y/Δ DIP switch
adjustment any phase shifting between 0° - 180° is
possible in 30° steps between current and voltage. This
For desired applicaiton (Active/Reactive), the phase can be helpful if, for instance, U 1N or U 23 are not
shift is required to be adjusted with the help of X11 available for measuring. It is also possible to use
jumper and Y/Δ Dip switch adjustment. The connection currents and voltages of other phases. In such a case
shall be made as per the fig. 3.1 or fig. 3.2. sketching of a vector diagram is very useful.

When connecting voltage inputs phase to neutral The four coding facilities X11 jumper are on the PCB
voltage, the current vector I L1 is parallel to the voltage left to the front plate, shown in the fig. 4.4.
vector UIN.

1
For forward active power application, Y/Δ Dip switch 4
must be at Y position and X11 jumper position at 0°. 5

X11 8

For reverse active power application, Y/Δ Dip switch


must be at Δ position and X11 jumper position at 90°.

For reverse reactive power application, Y/Δ Dip switch Fig. 4.4: Code jumpers for phase shifting
must be at Y position and X11 jumper position at 90°.

When connecting voltage inputs to phase to phase There is no phase shift adjusted with the initial
voltage, the current vector I L1 is perpendicular to adjustment (0°), i.e. coding plug applied one, two or
voltage vector U 23. three positions further to the left this means the phase
is shifted 30°, 60° or 90°. The trip function is blocked
if either a second coding plug is applied or there is no
For forward active power applicaiton, Y/Δ Dip switch coding plug at all. The total phase shifting together with
must be at Y position and X11 jumper position at 90°. Y/Δ DIP switch and X11 jumper are mentioned in the
Table 4.2.

For forward reactive power applicaiton, Y/Δ Dip switch


must be at Y position and X11 jumper position at 0°. Y/Δ Adjustment Angular displacement
between IL1 and U1N
For reserve reactive power applicaiton, Y/Δ Dip switch
0° 0°
must be at Δ position and X11 jumper position at 90°.
Y 30° 30°
Using the voltage and current for other phases, the 60° 60°
above mentioned application can be achieved by
making proper phase shift adjustment. 90° 90°

0° 90°
4.3 Coding of phase shifter
Δ 30° 120°

60° 150°
Phase shifting between current and voltage can be
adjusted from 0 to 90° by 30° steps. Consequently the
90° 180°
actual phase shifting (dependent on the connection Y/

Table 4.2 : Phase shifting with DIP Switch and


Jumper.

7
IRP1- Directional Power Relay

5 Working principle Calculation example 1: Medium voltage 10 kV


The IRP1 is provided with two output relays P R1 and PR2  generator apparent power: SG = 1875 kVA
, having separate adjustable pickup values and trip
 rated power factor: cos(ϕ) = 0.8
delays.
Measuring principle:  rated voltage of IRP1 : Un = 110 V

Voltage and current measured are galvanically (phase-to-phase voltage)


decoupled via the input CT. Dependent on relay
connection (Y or Δ) and encoding, either phase-to-
When the relay is expected to trip at a generator
neutral voltage U1N or phase-to-phase voltage U23 is
reverse power of 6 %, calculation of the setting value
used as reference voltage for load calculation. Current
is as follows:
is measured in phase L1.
1875 kVA. 0.8
For the IRP1 a stable system voltage is required. The
load is calculated by evaluating value and phase angle √3.20.100
of the current. If the set thresholds P R1 or P R2 are PR> (%) = .6(%) = 5 %
exceeded, the respective supervision circuit picks up 100V.5A
and the corresponding LED lights up yellow. After the
set trip delay has elapsed, the relay trips and respective According to the above example, the IRP1 has to be set
LED lights up red. to 5 % so that it trips at a generator reverse power of
6 % (rated generator active power).
5.1 Calculation of the setting value
Connection of the IRP1 to phase-to-
Should the relay, for instance, trip at a generator
neutral voltage
reverse power of 10 %, this does not mean that the
setting value of the IRP1 is 10 %. Based on the Conversion of the generator phase power PGS based on
transformer transformation ratio, the switching point the transformer secondary side:
has to be calculated.
The IRP1 measures the power in one phase of the SG. cos ( ϕ)
PGS =
transformer secondary side. The power is assumed to
√3.nu.ni
be symmetrical.
The generator phase power must be related to the With the permissible generator reverse power PRG, the
transformers secondary side. setting value PR is then calculated as follows:
Essential data SG. cos ( ϕ)
SG [kVA] rated generator apparent power
3.nu.ni
cos(ϕ): rated generator power factor PR> (%) = .P RG(%)
Un.In
In: rated current of IRP1
Un: rated voltage of IRP1 Calculation example 2: Low voltage 400 V, connection-
to-phase voltage
nI : transformation ratio of the CT
 generator apparent power: SG = 625 kVA
nU : transformation ratio of the VT
 rated power factor: cos(ϕ) = 0.8
 rated current of IRP1 : I n = 5 A
Connection of the IRP1 to phase-to-phase
 rated voltage of IRP1 : U n = 230 V
voltage:
(phase-to-neutral voltage)
Conversion of the generator phase power PGS based on  transformation ratio of the CT: nI = 1000 A/5 A
the CT secondary side:
 no VT required
SG. cos ( ϕ) When the relay is expected to trip at a generator
PGS = reverse power PRG of 5 %, calculation of the setting
√3.nu.ni value PR> is as follows:

With the permissible generator reverse power PRG, the 625 kVA. 0.8
setting value PR is then calculated as follows:
3.1.200
.5(%) = 3.6% = 4 %
SG. cos ( ϕ) PR> (%) =
230V.5A
√3.nu.ni According to the above example, the IRP1 has to be set
PR>(%) = .P RG(%) to 4 % so that it trips at a generator reverse power of
Un.In
5 % (rated generator active power).

8
IRP1- Directional Power Relay

6 Operations and settings


0 0.1s
0 0.2
6.1 Setting of the parameters by means 0 0.4
of DIP-switches 0 0.8 T : (0.1 + 0.2 + 0.4) x 20 = 14s
0 1.6
x1 x20
All DIP-switches required for setting of the parameters
are located on the front plate.
Fig. 6.2: Setting of the delay times

6.1.1 Setting of the pickup value


6.2 Fault indication
There are four LEDs at the front plate of the IRP1 for
The pickup values for reverse power tripping PR1 or P R2 indicating faults. The pickup LEDs above PR1 and P R2
can be adjusted by the DIP switches in a range from2% light up yellow, and LEDs below PR1 and PR2 light up red
to 17.5 % PN in 0.5 % steps. The pickup value is when the respective output relay trips.
calculated from the total of all DIP switch positions.

6.3 Reset
Example:
A pickup value PR1 of 5.5 % of the rated power is to be
adjusted 6.3.1 Manual reset

When the <RESET> push button is pressed, the trip


2.0 2.5
relay is reset and the LED indication extinguishes. This
0 1
on condition that all code jumpers are unpluged.
0 2
0 4 PR> : 2.5 + 1 + 2 = 5.5%
0 8 6.3.2 Automatic reset

Code jumpers 1 and 3:


Fig. 6.1:Adjustment example
The yellow and red fault indications (LED PR1 and P R2)
are coded for latching if the code jumpers are not
applied to sockets 1 and 3. Therefore any fault
indication can only be reset manually by pressing the
6.1.2 Setting of the trip delays <RESET> push button.

The trip delays t PR1 and t PR2 can be adjusted by the DIP If the code jumpers are applied to sockets 1 and 3, the
switches in a range from 0.1 s to 62 s with a grading fault indication is automatically reset as soon as the
of 0.1 s or 2 s. The pickup value is calculated from the fault is removed.
total of all DIP switch positions.

Code jumpers 2 and 4:


Example:
The trip relays are coded for latching if the code
A delay time of 14 s is to be adjusted: jumpers are not applied to sockets 2 and 4. Therefore
any fault indication can only be reset manually by
pressing the <RESET> push button. If the code
jumpers are applied to sockets 2 and 4, the fault
indication is automatically reset as soon as the fault is
removed.

9
IRP1- Directional Power Relay

7 Housing The following figure shows the terminal block of IRP1


The IRP1 can be supplied in an individual housing for
flush-mounting or as a plug-in module for installation
in a 19" mounting rack according to DIN 41494. Both
versions have plug-in connections.
Relays of variant D are complete devices for flush
mounting, whereas relays of variant A are used for A B
19“ rack mounting. Housing variant A to be installed in
switchboards of protection class IP51. For switch- C D E

boards of lower protection classes housing variant D 1

can be used. 2

7.1 Individual housing 3

The individual housing of the IRP1 is constructed for 4

flush-mounting. The dimensions of the mounting frame 5


correspond to the requirements of DIN 43700 (76 6
x142 mm). The cut-out for mounting is 68.7 x 136.5
7
mm.
8
The front of the IRP1 is covered with a transparent,
sealable flap (IP54). 9

For case dimensions and cut-out refer to “technical F


data”. The individual housing is fixed with the supplied
clasps from the rear of the switchboard panel.
7.2 Rack mounting
The IRP1 is in general suitable for installation in a
modular carrier according to DIN 41494. The Fig. 7.1: Terminal block of IRP1
installation dimensions are: 12 TE; 3 HE.
According to requirements, the IRP1-devices can be
8 Relay testing and commissioning
delivered mounted in 19" racks.
The following test instructions should help to verify the
If 19" racks are used the panel requires protection
protection relay performance before or during
class IP51. For switchboards with lower degree of
commissioning of the protection system. To avoid a
protection must be used individual housing.
relay damage and to ensure a correct relay operation,
7.3 Terminal connections be sure that:
The plug-in module has a very compact base with plug  the auxiliary power supply rating corresponds to
connectors and screwed-type connectors. the auxiliary voltage on site.
 max. 4 poles screw-type terminals for voltage  the rated current and rated voltage of the relay
and current circuits (terminal connectors series A correspond to the plant data on site.
and B with a short time current capability of 500  the current transformer circuits are connected to
A / 1 s). the relay correctly.
 27 poles tab terminals for relay outputs, supply  all signal circuits and output relay circuits are
voltage etc.(terminal connectors series C, D and connected correctly.
E, max. 6 A current carrying capacity).
Connection with tabs 6.3 x 0.8 mm for cable up 8.1 Power-On
to max. 1.5 mm 2 or with tabs 2.8 x 0.8 mm for
Prior to switch on the auxiliary power supply, be sure
cable up to max. 1 mm 2.
that the auxiliary supply voltage corresponds with the
By using 2.8 x 0.8 mm tabs a bridge connection rated data on the type plate.
between different poles is possible.
Switch on the auxiliary power supply to the relay
The current terminals are equipped with self-closing (terminals C9/E9) and check that the LED “ON” on the
short-circuit contacts. Thus, the IRP1 -module can be front lights up green.
unplugged even with current flowing, without
8.2 Checking the set values
endangering the current transformers connected.
Check all relay set values and see if they are set
correctly as you have desired. Set values can be
modified by means of the DIP-switches on the front.

10
IRP1- Directional Power Relay

8.3 Secondary injection test 8.3.2 Test circuit


8.3.1 Test equipment
For testing power relays, you need both current and
 Voltmeter with class 1 or better voltage input signals with adjustable phase shifting.
Figure 8.1 shows an example of a single phase test
 Ammeter with class 1 or better
circuit with adjustable voltage and current energizing
 Powermeter with class 1 or better the IRP1 relay under test.

 Auxiliary power supply with the voltage For testing the power relay, the input voltage shall be
corresponding to the rated data on the type plate applied to the relay via terminals A3/A4. The input
current (B3/B4) and phase angle shall be appropri-
 Single-phase current supply unit (adjustable from
ately varied.
0 to > 2.0 x I N )

 Single-phase voltage source

(adjustable from 0 to > 1.2 x UN )

 Timer to measure the operating time

 Switching device

 Test leads and tools

Supply

L+/L L-/N
C9 E9 D9

4 IRP1
2 6
* A
B4
~
1
* I1
B3

Supply +

+ D1
PR1 C1
Trip Signal E1

Timer D2
Start 8
- C2
7 W E2
Pr2 D4
A3 Trip Signal C4
- E4
Stop * U1 D5
A4 C5
3 5
* E5

2 V

Variable voltage source


Variable voltage source with phase shifting
Switching device
Series resistor
Voltmeter
9
Ammeter
Wattmeter
Timer
Relay under test

Fig. 8.1: Test circuit

With regard to the right polarity great care must be


taken when applying the test current and test voltage to
the relay. In figure 8.1 the relay and test source polarity
are indicated by a * mark near the terminals. If the
voltage and current sources are connected acc. to the
above test circuit diagram, the reverse power will be
measured correctly.

11
IRP1- Directional Power Relay

8.3.3 Checking the operating and 8.4 Primary injection test


resetting values of the relay
Generally, a primary injection test could be carried out
in the similar manner as the secondary injection test
A test voltage equal to the rated voltage has to be above described. Since the cost and potential hazards
applied to terminals A3/A4. For checking the operating are very high for such a test, especially if staged fault
and resetting values the test current must be increased tests are intended, primary injection tests are usually
until the relay picks up. LED PR1 or PR2 lights up. limited to very important protective relays in the power
system.
The deviation of power measurement related to the
reading of the power meter must not exceed 5% (refer 8.5 Maintenance
to 5.1)

Maintenance testing is generally done on site at regular


The reset value is ascertained by decreasing test
intervals. These intervals vary among users depending
current gradually until the relay PR1 or PR2 releases
on many factors: e.g. the type of protective relays
(with the relevant coding, see chapter 6.3.2). The reset
employed; the importance of the primary equipment
value must not exceed 0.95 times the operating value.
being protected; the user’s past experience with the
relay, etc.
8.3.4 Checking the trip delay For static relays like IRP1, maintenance testing will be
performed at least once a year according to the
experiences.
To check the trip delay, a timer to is be connected to the
trip relay contact. The timer should be started
simultaneously with the current injection in the current
input circuit and stopped by the trip relay contact. Apply
rated voltage to the relay and set the current to a value
corresponding to twice the pickup value and inject the
current instantaneously. The trip delay measured by
timer should have a deviation <3% of the set value or
20 ms (in case of a short trip delay).

12
IRP1- Directional Power Relay

9 Technical Data

9.1 Measuring input

Rated data:
Nominal voltage : 100 V; 230 V; 400 V
Nominal current IN : 1 A or 5 A
Nominal frequency f N : 50/60 Hz
Thermal withstand capability
in current circuit : dynamic current withstand (half-wave) 250 x IN
for 1 s 100 x I N
for 10 s 30 x I N
continuously 4 x IN
Thermal withstand capability
in voltage circuit : continuously 2 x UN
for 400 V 1.2 x U N

9.2 Auxiliary voltage

Rated auxiliary voltages U H : 24 V operating range 16 - 60 V AC / 16 - 80 V DC


110 V operating range 50 - 270 V AC / 70 - 360 V DC
Power consumption : at 24 V standby approx. 3 W operating approx. 6 W
at 110 V standby approx. 3 W operating approx. 6 W

9.3 General data

Permissible interuption of the


supply voltage without
influence on the function : 50 ms
Dropout to pickup ratio : >95 %
Returning time : 30 ms
Minimum operating time : 30 ms

9.4 Output relays

The output relays have the following characteristics:


maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A

for DC-voltage:
ohmic L/R = 40 ms L/R = 70 ms
300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W
250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W
110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.2 A / 22 W
60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.3 A / 17 W
24 V DC 6 A / 144 W 4.2 A / 100 W 2.5 A / 60 W

Max. rated making current : 64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86)
mechanical life span : 30 x 106 operating cycles
electrical life span : 2 x 105operating cycles at 220 V AC / 6 A
Contact material : silver cadmium oxide (AgCdO)

13
IRP1- Directional Power Relay

9.5 System data

Design standard : VDE 0435, part 303, IEC 255-4, BS 142

Specified ambient service

Temperature range
for storage : - 40°C to + 85°C
for operation : - 20°C to + 70°C

Environmental protection
class F as per DIN 40040 and
per DIN IEC 68 2-3 relative humidity 95 % at 40°C for 56 days

High voltage tests :

Insulation test voltage, inputs


and outputs between themselves
and to the relay frame as per
VDE 0435, part 303; IEC 255-5 : 2.5 kV (eff.), 50 Hz; 1 min

Impulse test voltage, inputs


and outputs between themselves
and to the relay frame as per
VDE 0435, part 303; IEC 255-5 : 5 kV; 1.2 / 50 μs; 0.5 J

High frequency interference


test voltage, inputs and outputs
between themselves and to the
relay frame as per DIN IEC 255-6 : 2.5 kV / 1MHz

Electrical fast transient (Burst)


test as per DIN VDE 0843, part 4;
IEC 801-4 : 4 kV / 2.5 kHz, 15 ms

Radio interference suppression


test as per DIN VDE 57 871 : limit value class B
Electrostatic discharge (ESD)
test as per DIN VDE 0843 part 2
IEC 801-2 : 8 kV

Radiated electromagnetic field


test as per VDE 0843 part 3;
IEC 801-2 : electrical field strength 10 V/m

Mechanical tests:

Shock : class 1 acc. to DIN IEC 255 part 21-2


Vibration : class 1 acc. to DIN IEC 255 part 21-1
Degree of protection : IP54 by enclosure of the relay case and front panel
(relay version D)
Weight : approx. 1.5 kg

Pollution degree : 2 where design A is used


3 where design D is used

14
IRP1- Directional Power Relay

Overvoltage class :
Influencing parameters:
Frequency : 40 Hz < f < 70 Hz: <3% of the set value
Temperature : -20°C bis +70°C
Aux. voltage : no influence in the permissible range

9.6 Setting ranges and graduation

Parameter Setting range Graduation Tolerance

P R1 and PR2 2% ... 17.5% x PN 0.5% ±5% of setting value

tPR1 and t PR2 0.1 s ... 3.1 s 0.1 s ±3% or ±20 ms


2.0 s ... 62 s 2.0 s

9.7 Dimensional drawing

260
230 76
36 16 68.7
136.5
142

142
76

Cut Out Dimensions


Installation Depth : 275mm
All dimensions in : mm

Please observe:
A distance of 50 mm is necessary when the units are mounted one below the other for the housing bonnet to be
easily opened. The front cover can be open downwards.

15
10 Order form

Directional power relay IRP1 - 1 I U

Power measuring

Rated current: 1A 1
5A 5

Rated voltage: 100 V 1


230 V 2
400 V 4

Auxiliary voltage (AC/DC):


24 V (16 V to 60 V AC / 16 V to 80 V DC) L
110 V (50 V to 270 V AC / 70 V to 360 V DC) H

Housing (12TE): 19“- rack A


Flush mounting D

For further information, please contact :

C&S Protection & Control Ltd.


44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
E-mail: cspc@controlsindia.com Web : www.cspcindia.com
HR/IRP1/07-05-2008

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34
High-Tech Range
IRU1- AC Voltage Relay

U< U> ON

RESET
30 31% 50 52%
0 2 0 4
0 4 0 8
U< 0 U> 0 16
8
0 16 0 32
X1 X2 X1 X2
0 0.1s 0 0.1s
0 0.2 0 0.2
tU< 0 0.4 tU> 0 0.4
0 0.8 0 0.8
0 1.6 0 1.6
X1 X20 X1 X20

IRU1-UO

C&S Protection & Control Ltd.


IRU1- AC Voltage Relay

Contents

1. Introduction 7. Housing

2. Applications 7.1 Individual housing

7.2 Rack mounting


3. Characteristics and features 7.3 Terminal connections

4. Design 8. Relay testing and commissioning

4.1 Connections 8.1 Power on


4.1.1 Voltage measuring inputs 8.2 Checking the setting value
4.1.2 Output relays 8.3 Secondary test
4.2 Front plates 8.3.1 Test equipment
4.2.1 LEDs 8.3.2 Example test circuit with IRU1-relay
4.2.2 DIP-switches 8.3.3 Testing of pickup- and reset values (IRU1-
UO)
4.2.3 Push-button <RESET>
8.3.4 Trip delay test (IRU1-UO)
4.3 Code jumper
8.3.5 Pickup- and reset value test for the earth-
fault element (IRU1-E)
5. Working Principle
8.3.6 Trip delay test for the earth-fault element
(IRU1-E)
6. Operations and settings
8.4 Primary test

6.1 Layout of the operating elements 8.5 Maintenance

6.2 Setting of parameters by means of DIP-


switches 9. Technical Data

6.2.1 Setting of the pickup value for


overvoltage supervision U> 9.1 Measuring input

6.2.2 Setting of the pickup value for the 9.2 Auxiliary voltage
undervoltage supervision U<
9.3 Common Data
6.2.3 Setting of the pickup value for the earth-
fault voltage supervision UE> (IRU1-E 9.4 Output relays
only)
9.5 System data
6.2.4 Setting of trip delay
9.6 Setting ranges and steps
6.2.5 Indication of faults
9.7 Dimensional drawing
6.3 Reset

6.3.1 Reset by pressing pushbutton <RESET> 10 Order Form

6.3.2 Automatic reset

2
IRU1- AC Voltage Relay

1. Introduction 2. Application
The voltage supervision relay IRU1 generally protects
When compared with traditional protection systems the power generating systems, consumers or electrical
protective relaying with MR - and IR -relays of our equipment in case of under or overvoltage.
HIGH TECH RANGE offers several advantages.
Among other the relay can be used:
All MR protection relays are based on microprocessor
technology. They present the generation of our most
efficient protection relays, because of their capabilties  to detect voltage increase or decrease in power-
to process the measuring values digitally and to generating systems and energy supply networks
perform arithmetical and logical operation.
 to protect from dangerous overvoltage in case of
a faulty voltage controller
Additional advantages such as very low power  to protect motors against undervoltage
consumption, adaptability, possibilities for self-
supervision, flexible construction, selection of relay  to protect the generator stator against earth-fault
characteristics are completely utilized. (IRU1-E only)

 earth-fault supervision in isolated or compensated


Some IR protection relays are based on microprocessor networks (IRU1-E only)
and some on analog technology. They present our low-
priced protection relay generation and are used for all
basic protection application. 3. Characteristics and features

The following properties of the IR protection relays,  Static protective device


such as:
 Three phase voltage supervision

 Voltage supervision with one stage under- and


 Integration of multiple protection functions into
overvoltage function
one compact housing,
 Extremely wide setting ranges and fine steps
 User-friendly setting procedure by means of DIP-
switches,  Separately adjustable, independent timers for U<
and U> (IRU1-UO)
 Compact design due to SMD-technique, are their
superiority over the traditional protection systems.  Independent trip delays of the individual elements

 One - phase voltage supervision for earth-fault


For all applications of a more complex nature, e.g. protection (IRU1-E)
directional earth fault detection and where operating
convenience, fault analysis and communication ability  Sensitive earth-fault detection with suppression of
are required, MR-relays are used. the third harmonic (IRU1-E)

 Independent tripping characteristic


All relays of the HIGH TECH RANGE are available  Connection facility to phase-to-neutral or phase-
for through panel mounting and in 19“ racks. to-phase voltage
Connection terminals are of plug-in type. All IEC/DIN
regulations required for the individual application are  Wide operating ranges of the supply voltage (AC/
reliably met by these relays. DC)

 Coding plugs for latching or auto-reset of LED


indications and output relays

3
IRU1- AC Voltage Relay

4. Design

4.1 Connections

L1 L2 L3 L+/L L-/N
C9 E9 D9

Power
Supply
~

U< D1
A a A3
Trip C1
l l U< tU<
E1
U12
A4 D2

B b A5 C2
l l U< E2
tU<
U23
A6

C c A7
l l
Reset
A8 U31

Fig. 4.1: Connection diagram IRU1-U

L1 L2 L3 L+/L L-/N
C9 E9 D9

Power
Supply
~

U> D3
A a A3
Trip C3
l l U> TU>
E3
U12
A4 D4

B b A5 C4
l l >U E4
TU>
U23
A6

C c A7
l l
Reset
A8 U31

Fig. 4.2: Connection diagram IRU1-O

4
IRU1- AC Voltage Relay

L+/L L-/N
L1 L2 L3
C9 E9 D9

Power
Supply
~
U<
D1
A a Trip
A3
l l l U< tU<
C1
E1
U12
A4 D2
C2
B b A5
l l l U< l E2
U23
tU<
A6

A7
C c l
l l
Reset
A8 U31

D3

U> l C3
tU>
E3
D4

U> C4
U> tU> Trip E4

Fig. 4.3: Connection diagram IRU1-UO

L1 L2 L3 L+/L L-/N
C9 E9 D9

Power
Supply
~

UE>
D1
Trip C1
A e E1
l UE> tUE> D2
C2
A3
E2
B
l A4 UE> l
50/60Hz tUE>

C n
l Reset

Fig. 4.4: Connection diagram IRU1-E

In the following the IRU1 functional description always


refers to the version IRU1-UO. With a few exceptions
(no overvoltage supervision for the IRU1-U, no
undervoltage supervision for the IRU1-0 , only earth-
fault voltage supervision for the IRU1-E) all functions
are valid for the other units, too.

5
IRU1- AC Voltage Relay

4.1.1 Voltage measuring inputs 4.1.2 Output relays

Via terminals A3 to A8, the analog input signals of the Output relay IRU1-UO
phase-to-neutral or phase-to-phase voltages are fed to
the protective device. In medium- and high-voltage
networks voltage transfomers are necessary. In low- The IRU1-UO is equipped with one tripping relay for
voltage networks the mains voltage can be applied overvoltage and one for undervoltage supervision each
directly to the measuring input circuits. with two change-over contacts:

Both connections of each input transformer are led to Tripping U<: D1, C1, E1; D2, C2, E2
terminals. Due to this phase-to-neutral or phase-to- (also available at the IRU1-U)
phase voltage supervision is possible.

Tripping U>: D3, C3, E3; D4, C4, E4


The rated voltage declaration of the relay obtains the
voltage between these terminals (e.g. A3/A4). (also available at the IRU1-0)

Output relay IRU1-E

The IRU1-E provides one tripping relay with two


change-over contacts:
Tripping U E>: D1, C1, E1; D2, C2, E2

6
IRU1- AC Voltage Relay

4.2 Front plates

U< U> ON U> ON

RESET RESET
30 31% 50 52% 50 52%
0 2 0 4 0 4
0 4 0 8 0 8
U< 0 U> 0 U> 0 16
8 16
0 16 0 32 0 32
X1 X2 X1 X2 X1 X2

0 0.1s 0 0.1s 0 0.1s


0 0.2 0 0.2 0 0.2
0.4 0.4 tU> 0 0.4
tU< 0 tU> 0
0 0.8 0 0.8 0 0.8
0 1.6 0 1.6 0 1.6
X1 X20 X1 X20 X1 X20

IRU1-UO IRU1-O

Fig. 4.5: Front plate IRU1-UO Fig. 4.7: Front plate IRU1-O

U< ON UE> ON

RESET RESET
30 31% 0 1%
0 2 0 2
0 4 0 4
U< 0
8
UE> 0 8
0 16 0 16
X1 X2 X1 X2

0 0.1s 0 0.1s
0 0.2 0 0.2
tU< 0 0.4 tUE> 0 0.4
0 0.8 0 0.8
0 1.6 0 1.6
X1 X20 X1 X20

IRU1-U IRU1-E

Fig. 4.6: Front plate IRU1-U Fig. 4.8: Front plate IRU1-E

7
IRU1- AC Voltage Relay

The front plate of IRU1-UO comprises the following 4.3 Code jumper
operation- and indication elements:
At the rear of the front plate, are coding plugs for pre-
 4 DIP-switches sets of for the setting of tripping adjustment of the LEDs’ function as well as for the trip
values and trip delays relays function.
 5 LEDs for the indication of faults and the
readiness for service  IRU1-UO four coding plugs
 1 pushbutton <RESET>  IRU1-E two coding plugs

4.2.1 LEDs The function of alarm-LEDs (yellow) is not codeable.


They light up as soon as threshold is exceeded and they
will extinguish automatically, if the threshold falls below
The IRU1-UO front plate provides five LEDs, for the setting value.
indication of the following operation modes:

Note:
 ready for service LED ON (green)
At delivery of the relay all coding plugs are equipped
 undervoltage alarm U<, top LED (yellow) with code jumpers.
 overvoltage alarm U>, top LED (yellow) The coding plugs are used for the following functions:
 undervoltage trip U<, bottom LED (red)  coding plugs 1 + 2 undervoltage-element (U<)
 overvoltage trip U>, bottom LED (red)  coding plugs 3 + 4 overvoltage-element (U>)

The IRU1-E front plate provides three LEDs, for For further information please refer to 6.3.2
indication of the following operation modes:
Front plate
 ready for service LED ON (green)
 residual voltage alarm UE> , top LED (yellow)
 residual voltage trip UE>, bottom LED (red) U< U> ON

4.2.2 DIP-switches
U< U>
The 4 sets of DIP-switches on the front plate of the
IRU1-UO serve to adjust tripping values and times.
tU< tU>

4.2.3 Push-button <RESET>

Code jumper
The pushbutton <RESET> is used to acknowledge and
1 23 4
reset the LEDs and the tripping relay after a tripping
with the appropriate pre-adjustment (see 4.3). Code jumper ON
Indications and output-elements, which are coded on
latching, have to be reset manually by pressing Code jumper OFF

pushbutton <RESET>.
Fig. 4.9: Code jumper

Code Function Code jumper Operation mode


jumper position
1 Undervoltage OFF Latching red LED U<
indication ON Auto-reset red LED U<
2 Undervoltage OFF Latching for trip element U<
element ON Auto-reset for trip element U<
3 Overvoltage OFF Latching red LED U> (UE> at IRU1-E)
indication ON Auto-reset red LED U> (UE> at IRU1-E)
4 Overvoltage OFF Latching for trip element U> (UE> at IRU1-E)
element ON Auto-reset for trip element U> (UE> at IRU1-E)

Table 4.1: Coding possibilities

8
IRU1- AC Voltage Relay

5. Working Principle 6.2 Setting of parameters by means of


The IRU1-UO is equipped with a one-step independent
DIP-switches
over- (U>) and undervoltage (U<) supervision with 6.2.1 Setting of the pickup value for
separately adjustable pickup values and time delays. In overvoltage supervision U>
delta connection the phase-to-phase voltages and in
With the aid of DIP-switch U> it is possible to adjust the
star connection the phase-to-neutral voltages are
pickup value for the U> tripping element in the range
continuously compared with the set reference values.
of 50 - 224 % U N. The pickup value is calculated from
Measuring principle: the sum of the individual factors multiplied by the
The incoming analog voltages are galvanically adjusted multiplication factor.
decoupled via the input voltage transformers and Example:
subsequently filtered in order to minimize the influence
A tripping value of 128 % U N is to be adjusted.
of disturbing voltages. The voltages are then compared
to an internal reference voltage. If the voltage value
falls below or exceeds the set reference value a time
circuit is activated and the appropriate output relay 50 52%

trips. 0 4
0 8
For the overvoltage supervision, the highest value of
0 16 U>: (52+4+8) x 2 = 128% U N
the three voltages, for the undervoltage supervision,
0 32
the lowest value of the three voltages is evaluated.
x1 x2
The IRU1-E is equipped with a one-phase and one-
step voltage supervision (U E>) with adjustable pickup
values and time delays. The extremely wide voltage Fig 6.1: Setting example
setting range has fine steps. Hereby the residual voltage
is continuously compared with the set reference values. 6 . 2 . 2 Setting of the pickup value for
the undervoltage supervision U<
Measuring principle of IRU1-E :
With the aid of DIP-switch U< it is possible to adjust the
The incoming analog voltage is galvanically decoupled pickup value for the U< tripping element in the range
via the input voltage transformer with subsequently of 30 - 122 % UN. The pickup value is calculated from
electronic data acquisition. the sum of the individual factors multiplied by the
With the help of a low-pass filter and a following band- adjusted multiplication factor.
pass filter the 3rd harmonic will be suppressed. The Example:
measured values will be compared with the set
reference value. The relay picks up the trip delay will A tripping value of 90 % U N is to be adjusted.
be activated and the corresponding LED lights up if the
measured value exceeds the set reference value. After 30 31%
the trip delay has expired the relay trips. 0 2

0 4
6. Operations and settings 8
U<: (31+2+4+8) x 2 = 90% U N
0
16
6.1 Layout of the operating elements 0

x1 x2
All DIP-switches required for the setting of parameters
are located on the front plate.
Fig 6.2: Setting example

9
IRU1- AC Voltage Relay

6.2.3 Setting of the pickup value for the 6.2.5 Indication of faults
earth-fault voltage supervision
UE> ( IRU1-E only) For the fault indication the IRU1-UO front plate
provides two LEDs for each function:
With the aid of DIP-switch UE> it is possible to adjust the
pickup value for the earth-fault voltage supervision in U>: upper LED indicates alarm (yellow),
the range of 1 - 62 % of U N. The pickup value is
lower LED indicates trip (red)
calculated from the sum of all individual values
multiplied by the adjusted multiplication factor. U<: upper LED indicates alarm (yellow)
lower LED indicates trip (red).
Example:
A tripping value of 20 % of U N is to be adjusted. 6.3 Reset

6.3.1 Reset by pressing pushbutton


0 1% <RESET>
0 2
0 4
0 8 UE>: (4+16) x 1 = 20% U N By pressing the pushbutton <RESET> the tripping relay
0 16 is reset and LED U< or U> will extinguish. For this
x1 x2
purpose, it is necessary that all code jumpers are in
position “OFF” (see also chapter 4.3).

6.3.2 Automatic reset


Fig. 6.3: Setting example

Code jumper 1+3


6.2.4 Setting of trip delay
The red fault indication LEDs U</U> are coded on
latching, if no code jumper is used on coding plug
Each according to the unit type, the trip delay can be 1 or 3.
set with the aid of the DIP-switch t in the range of 0.1
- 62 s. The appropriate tripping value is calculated
from the sum of the individual factors multiplied by the The fault indication can only be reset manually by
adjusted multiplication factor (1 or 20). actuating the pushbutton <RESET>.
The red fault indication LEDs will be reset automatically
after clearance of the fault, if code jumpers are used
Example:
on coding plug 1 or 3.
A trip delay of 14 s is to be adjusted.

Code jumper 2+4


The tripping elements are coded on latching, if no code
0 0.1s jumper is used on coding plug 2 or 4.
0 0.2
The corresponding tripping element can only be reset
0 0.4
t: (0.1+0.2+0.4) x 20 = 14 s
manually by actuating the pushbutton <RESET>. The
0 0.8
tripping elements will reset automatically after
0 1.6
clearance of the fault, if code jumpers are used on
x1 x 20
coding plug 2 or 4.

Fig. 6.4: Setting example

10
IRU1- AC Voltage Relay

7. Housing 7.3 Terminal connections

The IRU1 can be supplied in an individual housing for The plug-in module has a very compact base with plug
flush-mounting or as a plug-in module for installation connectors and screwed-type connectors.
in a 19" mounting rack according to DIN 41494. Both
versions have plug connectors.
 8 poles screw-type terminals (terminal connectors
series A with a short time current capability of
Relays of variant D are complete devices for flush 500 A/1s) for voltage circuits.
mounting, whereas relays of variant A are used for  27 poles screw-type terminals for relay outputs,
19“ rack mounting. Housing variant A to be installed in supply voltage etc. (terminal connectors series C,
switchboards of protection class IP51. For switch- D and E, max. 6 A current carrying capacity).
boards of lower protection classes housing variant D Connection with tabs 6.3 x 0.8 mm for cable up
can be used. to max. 1.5 mm 2 or with tabs 2.8 x 0.8 mm for
cable up to max. 1 mm 2.
7.1 Individual housing
By using 2.8 x 0.8 mm tabs a bridge connection
The individual housing of the IRU1 is constructed for between different poles is possible.
flush-mounting. The dimensions of the mounting frame
correspond to the requirements of DIN 43700 (76 x The following figure shows the terminal block of IRU1
142 mm). The cut-out for panel mounting is 68.7 x
136.5 mm.

The front plate of the IRU1 is covered with a


transparent, sealable flap (IP54).
A B

For case dimensions and cut-out refer to “technical C D E


data”. The individual housing is fixed with the supplied 1
clasps from the rear of the panel.
2

3
7.2 Rack mounting
4

5
The IRU1 is in general suitable for installation in a
modular carrier according to DIN 41494. The 6

installation dimensions are: 12 TE; 3 HE. 7

8
According to requirements, the IRU1-devices can be 9
delivered mounted in 19" racks.
F

If 19" racks are used the panel requires protection


class IP51. For switchboards with lower degree of
protection must be used individual housing.

Fig. 7.1: Terminal block

11
IRU1- AC Voltage Relay

8. Relay testing and commissioning 8.2 Checking the setting value


The following test instructions should help to verify the Due to a check of the DIP-switch positions, the actual
protection relay performance before or during tresholds can be established.
commissioning. To avoid a relay damage and to ensure
The setting values can be corrected, if necessary by
a correct relay operation, be sure that:
means of the DIP-switches.
 the auxiliary power supply rating corresponds to
the auxiliary voltage on site 8.3 Secondary test
 the rated voltage corresponds to the plant data on 8.3.1 Test equipment
site,  Voltmeter
 the voltage transformer circuits are connected to  Auxiliary power supply with the voltage
the relay correctly corresponding to the rated data on the type plate,
 all control- and measuring circuits as well as the  Three-phase voltage supply(adjustable from 0 -
output relays are connected correctly. 2.4 x UN)
8.1 Power on  Single-phase voltage supply(adjustable from 0 -
Note! 1.2 x U N (only IRU1-E)
Prior to switch on the auxiliary power supply, be sure  Timer to measure the operating time
that the auxiliary supply voltage corresponds with the  Switching device
rated data on the type plate.
 Test leads and tools
When the auxiliary power supply is switched on
(terminals C9/E9) please observe that the LED “ON” is 8.3.2 Example test circuit with IRU1 -
alight. relay
For testing IRU1 only voltage signals are used. Figure
8.1 shows an example of a single-phase test circuit
with variable voltage source.

Voltage Supply
L+/L L-/N
C9 E9 D9

1 IRU1-UO
2
3 A3
L1 l l ~
V U1
A4
N l l
A5
l
U2 +
l A6
A7 D1
+ U3 C1
Timer U< Trip Signal
Start A8 E1
- 4
D2
C2
E2
- D3
Stop U> Trip Signal C3
E3
D4
C4
E4

1. Variable voltage source


2. Switching device
3. Voltmeter
4. Timer
5. Relay under test

Fig. 8.1: Test circuit

12
IRU1- AC Voltage Relay

8.3.3 Testing of pickup- and reset values When testing the trip delay of the overvoltage pickup
(IRU1-UO) value, the test voltage must be higher than the pickup
value itself (e.g. pickup value +20 %). Same
procedure has to be done in the similar manner for
For testing the pickup values of U> and U<, the test testing the trip delay of the undervoltage pickup value.
voltage (AC) has to be connected to the relay (terminals
A3 / A4). When testing the overvoltage pickup value,
at first the test voltage has to be lower than the set The measured trip delay must not deviate from the set
pickup value for U>. Then the test voltage has to be trip delay by more than ±3 % or ±20 ms.
gradually increased until the relay picks up. This will be
indicated by the upper LED U> (yellow). Reading of the
voltmeter must not deviate from the pickup value U> 8.3.5 Pickup-and reset value test for the
by more than ±1%. earth-fault element (IRU1-E)

For ascertaining the reset value of the overvoltage For testing the earth-fault element a single-phase test
pickup value, the test voltage has to be slowly voltage has to be connected to the relay (terminals A3/
decreased until the output relay U> is de-energized A4). This test can be carried out in the similar manner
(on condition of appropriate encoding). Upper LED U> as described in chapter 8.3.3.
then extinguishes.

8.3.6 Trip delay test for the earth-fault


The reset value must not be greater than 0.97 times element (IRU1-E)
the pickup value i.e. the resetting ratio of the
overvoltage supervision is <1.
Testing the trip delay for the earth-fault element has to
be done in the similar manner as described in chapter
When testing the undervoltage pickup value, at first the 8.3.4.
test voltage has to be higher than the set pickup value
for U<. Then the test voltage has to be gradually
decreased until the relay is de-activated. This will be For testing the trip delay for the earth-fault element a
indicated by the upper LED U< (yellow). single-phase test voltage has to be connected to the
relay (terminals A3/A4).
Reading of the voltmeter must not deviate from the
pickup value U< by more than ±1 %.
8.4 Primary test
For ascertaining the reset value of the undervoltage
pickup value, the test voltage has to be slowly increased
Generally, a primary injection test could be carried out
until the output relay U< is energized (on condition of
in the similar manner as the secondary injection test
appropriate encoding).
above. Since the cost and potential hazards are very
high for such a test, primary injection tests are usually
Upper LED U< then extinguishes. limited to very important protective relays in power
system.
The reset value must not be greater than 1.03 times
the pickup value i.e. the resetting ratio of the
undervoltage supervision is >1. 8.5 Maintenance

8.3.4 Trip delay test (IRU1-UO) Maintenance testing is generally done on site at regular
intervals. These intervals vary among users depending
on many factors: e.g. the type of protective relays
For testing the trip delay a timer has to be connected employed; the importance of the primary equipment
to the output relay U> or U<. being protected; the users past experience with the
The timer has to be started at the same time as the test relay, etc.
voltage will be switched on, and be stopped in the For static relays like IRU1, maintenance testing will be
instant of relay trip. performed at least once a year according to the
experiences.

13
IRU1- AC Voltage Relay

9. Technical Data
9.1 Measuring input
Rated data
Nominal voltage UN : 100, 230, 400 V
Nominal frequency f N : 50/60 Hz
Power consumption in
voltage circuit : <1 VA/per phase at U N
Thermal withstand capability in
voltage circuit : Continuously 2 x UN (IRU1)
Continuously 1.2 x U N (IRU1-E)
9.2 Auxiliary voltage
Rated auxiliary voltage U H : 24 V working range 16 - 60 V AC / 16 - 80 V DC
110 V working range 50 - 270 V AC / 70 - 360 V DC
Power consumption at 24 V : at 24 V standby approx. 3 W operating approx. 6 W
at 110 V standby approx. 3 W operating approx. 6 W
9.3 Common Data
Permissible interruption of the
supply voltage without influence
on the unit function : 50 ms
Drop-out ratio : U>: > 97 %
U<: < 103 %
UE> : > 97 %
Returning time : 30 ms
Min. response time : 30 ms
9.4 Output relays
The output relays have the following characteristics:
maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A
for DC-voltage:

ohmic L/R = 40 ms L/R = 70 ms


300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W
250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W
110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.2 A / 22 W
60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.3 A / 17 W
24 V DC 6 A / 144 W 4.2 A / 100 W 2.5 A / 60 W

Max. rated making current : 64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86)
mechanical life span : 30 x 106 operating cycles
electrical life span : 2 x 10 5 operating cycles at 220 V AC / 6 A
Contact material : silver cadmium oxide (AgCdO)

9.5 System data


Design standard : VDE 0435, part 303, IEC 255.4, BS 142
Specified ambient service
Temperature range
for storage : - 40°C to + 85°C
for operation : - 20°C to + 70°C
Environmental protection class F
as per DIN 40040 and per
DIN IEC 68 2-3 : relative humidity 95 % at 40°C for 56 days
Insulation test voltage, inputs
and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 : 2.5 kV (eff.), 50 Hz; 1 min.

14
IRU1- AC Voltage Relay

Impulse test voltage, inputs


and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 : 5 kV; 1.2 / 50 μs; 0.5 J
High frequency interference
test voltage, inputs and outputs
between themselves and to the
relay frame as per
DIN IEC 255, part 22-1 : 2.5 kV / 1MHz
Electrostatic discharge (ESD)
test as per VDE 0843 part 2 : 8 kV
Electrical fast transient (Burst)
test as per VDE 0843, part 4 : 4 kV / 2.5 kHz, 15 ms
Radio interference suppression
test as per DIN 57 871 and
VDE 0871 : limit value class B
Radio interference radiation test
as per VDE 0843, part 3 : 10 V/m
Mechanical tests:
Shock : as per DIN IEC 255-21-2: class 1
Vibration : as per DIN IEC 255-21-1: class 1
Degree of Protection:
- front plate : IP54 if front cover is closed (only D-Version)
Weight : approx. 1.5 kg
Degree of pollution : 2 by using housing type A
3 by using housing type D
Overvoltage class : III
Influence quantities:
Influence of frequency : 40 Hz<f< 70 Hz:> 3% of the set value
Influence of temperature : 20°C... 70°C
Influence of auxiliary voltage : no influence within the tolerable range

9.6 Setting ranges and steps

Relay type Parameter Setting range Steps Tolerances


IRU1-U U< 30...61 % U N 1 % UN ± 1 % of rated value
60...122 % U N 2 % UN ± 1 % of setting value
t U< 0.1...3.1 s 0.1 s ± 3 % or ± 20 ms
2...62 s 2.0 s

IRU1-O U> 50...112 % U N 2 % UN ± 1 % of rated value


100...224 % U N 4 % UN ± 1 % of setting value
t U> 0.1...3.1 s 0.1 s ± 3 % or ± 20 ms
2...62 s 2.0 s

IRU1-E UE> 1...31 % UN 1 % UN ± 0.5 % of rated value


2...62 % UN 2 % UN (min. 0.1 V)
tUE> 0.1...3.1 s 0.1 s ± 3 % or ± 20 ms
2...62 s 2.0 s

IRU1-UO U< 30...61 % U N 1 % UN ± 1 % of rated value


60...122 % U N 2 % UN ± 1 % of setting value
t U< 0.1...3.1 s 0.1 s ± 3 % or ± 20 ms
2s...62 s 2.0 s

U> 50...112 % U N 2 % UN ± 1 % of rated value


100...224 % U N 4 % UN ± 1 % of setting value
t U> 0.1...3.1 s 0.1 s ± 3 % or ± 20 ms
2...62 s 2.0 s

15
9.7 Dimensional drawing

260
230 76
36 16 68.7

136.5
142

142
76
Cut Out Dimensions
Installation Depth : 275mm
All dimensions in : mm

Please observe:
A distance of 50 mm is necessary when the units are mounted one below the other for the housing bonnet
to be easily opened. The front cover can be opened downwards.

10. Order form

AC voltage relay IRU1-

Function Undervoltage AC U
Overvoltage AC O
Zero voltage (Earth fault detection) E
Under and overvoltage AC UO
Rated Voltage 100 V 1
230 V 2
400 V 4
Auxiliary voltage 24 V (16 to 60 V AC/16 to 80 V DC) L
110 V (50 to 270 V AC/70 to 360 V DC) H
Housing (12TE) 19” rack A
Flush mounting D

Technical data subject to change without notice!

C&S Protection & Control Ltd.


44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
E-mail: cspc@controlsindia.com Web : www.cspcindia.com
HR/IRU1/05.11.07/

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34

You might also like