Analysis of Column Loads ina
Building By Considering Beam
Support Reactions
BoE2008
® BS
6000 T 6000
Introduction
In the manual design of reinforced concrete structures, column loads are usually assessed
by considering the support reactions from beams they are supporting, or by the tributary
area method. The later is more populer due to its simplicity and speed, but usually fails to
capture all loads that are imposed directly on the columns, while the former is more
complex and time consurning, but very representative of all the possible loads that are
imposed on the column.
Steps on how to load a column from beam support reaction
(1) Load the floor slab adequately, and factor the loads at ultimate limit state, considering
the appropriate load combination.
(2) Transfer the loads from slab to the beam using the appropriate relationship. Based on
yield linas, the loads are usually triangular or trapezoidal, but this is cumbersome to
analyse manually. An equivalent UDL (reasonably accurate) can be used to transfer slab
loads by employing the formulas below;
One way slabs
Long span q = nlx/2Short span q = nlx/5
Two way slabs
Long span q = nix/2(1 ~ 1/3k*)
Short span q = nlx/3
Where;
= Load transferred from slab to the beam.
n= load at ultimate limit state
L4gk + 1.6qk (BS 6110)
1.350k + 1.5qk (Eurocode 2)
Ly = Length of long span of slab
Le = Length of short span of the slab
k= yikx
(3) Analyse the floor beams completely using any suitable method of your cheice, while
also considering any additional load that may be on the beam such as wall load and
finishes.
(4) Obtain the support reactions of the beam, which represents the load that is transferred
from the floor to the column.Design Example
tn this post, the lor plan shown below i fora shopping complex, and i desired to abtain
the column axial loads at ultimate lent state
PANEL 1 PANEL 2 PANEL 1
P3750 -h+3700 G32790
PANEL 1 PANEL 2 PANEL 1
pare dorm aa
6000 6000 6000
Design Data
‘ie ofall columns = 230 x 230mm
Sze of all beams ~ 450 x 220mm
Thknese of ab = 200mm
Unit weight of conerete = 25 kim?
Unt weight of sandrete block = 3.47 kin?
fee = 25 mica?
fk = 500 Njmer?
Loed combination = 1.359 + 15k
Design variable load (gh) = 4 ken?
k= Lyx = 6/5 = 1.2 (in all eases)
Only external beam are carrying block work leadLoad Analysis
Roof beam
Permanent load on roof beams gk = 6 kN/m
Variable load on roof beam qk = 1.5 kN/m
(These values are assumed)
At ultimate limit state, n = 1.35(6) + 1.5(1.5) = 10.35 kW/m
Slab Load Analysis
Concrete awn weight = 25 kN/m? x 0.2m =
Screeding and Finishes (say) = 4.35. kN/m?
Partition allowance = 1.5 kN/m?
Total (gk) = 7.85 kN/m?
Variable action (qk) = 4 kN/m?
0 kN/m?
n= 4.350k + 1.5qk = 1.35(7.85) + 1.5(4) =
6.6 KN/m?
Wall load on beam
Unit weight of sanderete block = 3.47 kN/m?
Height of wall = 3.5m
Wall load on beam = 3.47 kN/m? x 3.5m = 12.145 kN/m
Load on Beams
External Longitudinal beains (Axis 1:A-D and Axis 2:A-D)
Self weight of beam (factored) = 1.35 x 0.23m x 0.25m x 25 = 1.94 kN/m
Load from slab = nbx/2(1 ~ 1/3k*) = [(16.6 x 5/2] x (1 ~ 1/(3 x1.22)) = 31,893 kW/m
Load from block work = 12.145 kN/m
Total load = 45.978 KIN/m
External Transverse beams (Axis A:1-3 and Axis D:1-3)
Self weight of beam (factored) = 1.35 x 0.23m x 0.25m x 25 = 1.94 kN/m
Load from slab = nlx/3 = (16.6 x 5)/3 = 27.667 kN/m
Load from block work = 12.145 kN/m.
Total load = 41.752 KN/m
Internal Longitudinal Beam (Axis 2:4-D)
Self weight of beam (factored) = 1.35 x 0.23m x 0.25m x 25 = 1.94 kN/m
Load from slab = nbx/2(1 ~ 1/3k*) = [(16.6 x 5)/2] x (1 ~ 1/(3 1.2%) = 2 x 31.893
N/m = 63.786 kN/m (we multiplied by two because this beam is receiving slab load from
two directions.)
Load from block work = 0 (there are no block works inside the building)
‘Total load = 65.726 KN/mInternal Transverse beams (Axis B:1-3 and Axis C:1-3)
Self weight of beam (factored) = 1.35 x 0.23m x 0.25m x 25 = 1.94 kN/m
Load from slab = nlx/3 = (16.6 x 5)/3 = 2 x 27.667 kN/m = 55.334 kN/m (slab load is,
‘coming from two directions)
Load from block work
Total load = 57.274 KN/m
Self weight of Colurnns
Self weight of column (factored) = 1.35 x 0.23m x 0.23m x 3.75m x 25 kN/m? = 6.695
kN
‘Structural Analysis
‘A little consideration will show that the support reactions for the floor beams (equal spans)
can be obtained by considering the shear force coefficients given below;
akN/m
FRESE Eee eee eet eee eee eee eee sees esse ess sss ssy
——————————————————
Um) Um)
0.625q1
0.375ql f
°| 0.375ql
0.625ql
Fig 3: Shear force coefficient (2 ~ span bear)
a kN/m
pede be bees el eee ee ieee eile b esse bees ee essere eeedy
——e—————————EEEEE
Um) um) im)
0.500q1 0.60041
0.600q! ‘9.50081
Fig 4: Shear force coefficient (3 span beam)Analysis of the column axial loads
Load Analysis of Column AL
18 Floor
Load rom longitudinal roof beam (1:A-0) = 0.4 10.35 kW x 6m = 24.84 Kt
Load from transverse roof beam (1-3) = 0.375 x 10.35 ktm x Sm = 19.41 RN
‘Self weight of column = 6.595 4X
Total = 50.945 4
‘Ground Foor
ood from above = 50.945 KN
Load from longitudinal for beam (438-0) = 0.4 = 45,978 kW/m « én = 110.347 ka
Load from transverse flor beam (A:1-3) = 0.375 x 41.752 kN/m x 5m = 78.285 kN
Salf weight of column ~ 6.695 KN
Total = 246,272 KN
Load Analysis of Column A2
452 Floor
Lead from longitudinal rf beam (2:A-0) = 0.4 10.35 Kym 6m = 24.84 kN
Load from transverse rof beam (:1-3) = 2(0.625 = 10.35 kim x Sm) = 64.587 KN
Salt weight of column ~ 6.695 KN
Total = 96.222 kN
‘Ground Foor
Load from above = 96.222 KN
Load from longitudinal for beam (2:80) = 0:4 x 65,726 kW/m x 6m = 157.742 kN
Load from transverse flor beam (2:1-3) = 2(0.375 x 41.752 km x Sm) = 156.57 KN
Self weight of column = 6.695 KN
137.229 40
Load Analysis of Column BL
It Floor
Load rom longitudinal roof beam (1:A-D) = (0.5 x 10.35 KN/m x 6m) + (0.6 x 10.35
kW/m 6m) = 68.34 kN
Load from transverse raf beam (B:1-3) = 0.375 x £0.35 kan x Sm = 19.41 RN
‘Self eight of column = 6.695 KN
Total = 94.415 kN
‘Ground Foor
Leas from above = 98.415 0
Load from longitudinal lor beam (18-0) = (0.5 x 45.979 kfm 6m) + (0.6 « 45.978
Kivin « 6m). = 302.455 Kt
Load from transverse flor beam (6:
‘Self weight of column ~ 6.595 kX
Total = 511.953 &N
375 57.274 kN x Sm = 107-388 kN
2
Load Analysis of Column 02
et Floor
Load rom longitudinal raf beam (224-0)
Vem im) = 68.31 KN
Load from transverse roof beam (1-3) = 2(0.625 x 10.35 kW/m = Sm) = 64.687 KN
Salf weight of column ~ 6.695 KN
38.692 kN
(055 «10.35 kNVm x 6m) + (0.6 « 10.5
Lead from above = 139.692 KN
Load from longitudinal for beam (232-0) = (0.5 x 65.726 k/m x 6m) + (0.8 x
165.726 ke « 6m) = 433.7916 KN
Load from transverse flor beam (A:
“Self weight of column ~ 6.695 KN
357.9825 ka