This document provides load loss and no-load loss calculations for a 40MVA 220/11.5 kV two winding transformer. The load loss calculation determines the load loss to be 110.76 kW based on winding resistances and currents, within the guaranteed maximum of 111 kW. The no-load loss calculation determines the no-load loss to be 17.95 kW based on the core weight and material properties, within the guaranteed maximum of 18 kW.
This document provides load loss and no-load loss calculations for a 40MVA 220/11.5 kV two winding transformer. The load loss calculation determines the load loss to be 110.76 kW based on winding resistances and currents, within the guaranteed maximum of 111 kW. The no-load loss calculation determines the no-load loss to be 17.95 kW based on the core weight and material properties, within the guaranteed maximum of 18 kW.
This document provides load loss and no-load loss calculations for a 40MVA 220/11.5 kV two winding transformer. The load loss calculation determines the load loss to be 110.76 kW based on winding resistances and currents, within the guaranteed maximum of 111 kW. The no-load loss calculation determines the no-load loss to be 17.95 kW based on the core weight and material properties, within the guaranteed maximum of 18 kW.