40MVA 220/11.

5 kV TWO WINDING TRANSFORMER

i) Load Loss Calculation:

Phase Current HV- 104.97 Amps


LV- 2008.18 Amps

HV winding resistance = 1.495 ohms/phase approx.


LV winding resistance = 0.0035 ohms/phase approx.

I2 R loss (3 phases) = 3 x (104.972 x 1.495 + 2008.182 x 0.0035) / 1000


= 91.76 kW approx.

Eddy Current & Stray loss = 19 kW approx.

Total Load Loss = 91.76 + 19 = 110.76 kW

Guaranteed Load loss = 111 kW Max.

ii) No-Load Loss Calculation:

Core Weight = 30600 kg approx.


Building factor = 1.086
Watts per kg = 0.54 approx.

No-load loss = 30600 x 1.086 x 0.54 / 1000


= 17.95 kW approx.

Guaranteed Load loss = 18 kW Max.