Hydrogeology Journal (2014) 22: 189–203

DOI 10.1007/s10040-013-1060-6

Effect of thermal-hydrogeological and borehole heat exchanger


properties on performance and impact of vertical closed-loop
geothermal heat pump systems

S. Emad Dehkordi & Robert A. Schincariol

Abstract Ground-source geothermal systems are drawing Keywords Groundwater flow . Temperature . Thermal
increasing attention and popularity due to their efficiency, conditions . Thermal conductivity . Thermal recovery
sustainability and being implementable worldwide.
Consequently, design software and regulatory guidelines
have been developed. Interaction with the subsurface Introduction
significantly affects the thermal performance, sustainability,
and impacts of such systems. Reviewing the related Ground-source heat energy is a globally utilizable renewable
guidelines and the design software, room for improvement source of energy. It is driven by the nearly constant ground
is evident, especially in regards to interaction with ground- temperatures below ca. 10 m depth, which can be used to
water movement. In order to accurately evaluate the thermal extract heat in winters and serves as a heat sink in summers.
effect of system and hydrogeological properties on a Ground-source energy is usually used in conjunction with
borehole heat exchanger, a fully discretized finite-element geothermal heat pumps (GHPs) to bring the temperatures to
model is used. Sensitivity of the loop outlet temperatures and the desired level for heating/cooling. The emerging popu-
heat exchange rates to hydrogeological, system and meteo- larity of GHP technology has resulted in a call for improved
rological factors (i.e. groundwater flux, thermal conductivity design methods and regulatory measures.
and volumetric heat capacity of solids, porosity, thermal Thermo-geological factors are more frequently studied in
dispersivity, grout thermal conductivity, background and the research literature and reflected in design and regulations.
inlet temperatures) are analyzed over 6-month and 25-year Here, thermo-geological factors mean those that exclusively
operation periods. Furthermore, thermal recovery during 25 are related to heat transport and have no influence on
years after system decommissioning has been modeled. The groundwater flow, e.g. thermal properties of soil particles.
thermal plume development, transport and dissipation are Although computer codes able to model coupled groundwa-
also assessed. This study shows the importance of subsur- ter flow and heat transport exist, and there are some
face thermal conductivity, groundwater flow (flux>10−7 m/ regulations in place which consider thermo-hydrological
s), and background and inlet temperature on system factors in a superficial manner, the great majority of the
performance and impact. It also shows the importance of design methods and software do not account for the heat
groundwater flow (flux>10−8 m/s) on thermal recovery of transport by groundwater advection. Thermo-hydrological
the ground over other factors. factors are those that impact the groundwater flow and the
heat transport, e.g. hydraulic gradient.
According to Eskilson (1987) the vertical average
undisturbed ground temperature (i.e. background tempera-
ture) is sufficient for modelling borehole heat exchangers
Received: 5 October 2012 / Accepted: 17 September 2013 (BHEs), and the surface seasonal variations, as well as
Published online: 30 October 2013 geothermal gradient, can be neglected. Kurevija et al. (2011)
* Springer-Verlag Berlin Heidelberg 2013 found that this is valid when geothermal gradients are
relatively low, i.e. 1.62 °C/100 m, but can become important
Published in the theme issue “Hydrogeology of Shallow Thermal at higher gradients, i.e. 5 °C/100 m. The background
Systems” temperature can be measured by circulating the heat carrier
fluid in the borehole, without an external heat source/sink,
S. E. Dehkordi ()) : R. A. Schincariol through a thermal response test. The ground temperatures are
Department of Earth Sciences, University of Western Ontario, often fairly accurately known regionally from previously
London, Ontario N6A 5B7, Canada acquired data; however, the ground temperatures may
e-mail: sdehkord@uwo.ca significantly change in time due to urbanization (Ferguson
Tel.: +1-519-6612111
and Woodbury 2007) or by adjacent geothermal systems
R. A. Schincariol (Ferguson and Woodbury 2006). Thus, updating background
e-mail: schincar@uwo.ca temperature data for designing new installations and
190
quantifying the impact of such change on performance of changes temperature in and around a borehole. Their results
previously installed BHEs may be appropriate. Loop show approximately 5 and 2 °C change in loop temperatures
temperatures are also linked to the thermal performance of under groundwater velocities of 10−6 and 10−7 m/s respec-
the BHE as well as to the magnitude of its subsurface tively. These changes would approximately equal a ten and
temperature disturbance; however, in contrast to the back- two-fold increase in effective thermal conductivity.
ground temperatures, they are controlled by the system. Computations by Diao et al. (2004) show that groundwater
Thus, according to the review by Haehnlein et al. (2010) advection in the porous medium may alter the temperature
some geothermal guidelines, i.e. Austria, Germany and distribution compared to a conductive-dominated regime,
Denmark, set limits on loop temperatures. In this context, it leading to lower temperature disturbances and an eventual
is important to assess the effect of loop temperatures and heat steady-state condition around the BHE. They derive an
extraction rate on subsurface thermal impact and temperature analytical solution for a line heat source in an infinite
reversion. medium—comparable to Kelvin’s line source model—which
One of the most important properties of the grouting accounts for groundwater advection. Péclet numbers higher
material that affects the borehole thermal resistance is its than 0.1 are reported to enhance the heat extraction rate (Fujii
thermal conductivity (Zeng et al. 2003). Hellström (1998) et al. 2005). Furthermore, the influence of groundwater flow
shows that grout material with poor thermal conductivity on thermal response test (TRT) results was observed by Lee
significantly increases the borehole thermal resistance; and Lam (2009), who could rather confidently estimate the
however, its extent is sensitive to the spacing between the groundwater velocities over 2×10−7 m/s. A sensitivity
pipes (Hellström 1998; Wagner et al. 2012; Witte 2012). analysis on thermally affected zones (TAZ) around open
Although these studies are related in their use of thermally geothermal loops by Lo Russo et al. (2012) verifies that
enhanced grout to lower borehole thermal resistance, it hydraulic conductivity and gradient, and porosity, are highly
remains unknown as to how much thermally enhanced important in those systems. This was one of the few studies
grout can improve long-term BHE performance. that examined the effect of porosity on GHPs—but in an open
While the design and thermal sustainability of BHEs has loop. Open loops function similar to closed loops but extract
been studied for many years (e.g. Ingersoll and Plass 1948; the heat through direct withdrawal of groundwater and not
Ingersoll et al. 1950; Andrews 1978 amongst the earliest), through a heat exchanger; therefore, advective heat transport
today the literature is still dominated by studies where due to groundwater flow plays a more important role in open-
groundwater flow is not considered or presumed to be of loop systems. In some studies on closed loops, the porosity is
negligible importance. Even amongst the international either changed with hydraulic conductivity or is kept constant
standards, like the German VDI 4640 standard (VDI 2001) and the velocity varies strictly through varying the hydraulic
and the Swiss AWP-T1 (AWP 2007), thermal conductivity gradient and hydraulic conductivity (e.g. Chiasson et al. 2000;
and borehole specific heat extraction are related through the Wagner et al. 2012). A sensitivity analysis on artificial heat
underground material and its water content (but not its injection—not natural groundwater flow—by Vandenbohede
movement). Rybach and Eugster (2002) evaluated the et al. (2011) has found the process most sensitive to thermal
sustainability of a single BHE; and Signorelli et al. (2005) conductivity of the solid, porosity, heat capacity of the solid
extended this work to multiple BHEs so as to determine the and the longitudinal dispersivity, in that order.
borehole spacing at which there is no thermal interaction. The effect of the variability in subsurface flow and transport
Signorelli et al. (2005) determined that, for a single BHE, the properties, which if not explicitly included in a model is
time required for thermal recovery, i.e. returning of ground represented by dispersivity, has not been well addressed and
temperatures to their initial temperature after shutting down a remains controversial despite its potentially important effects
system, is equal to the operation time. Later Priarone et al. on heat distribution in the subsurface (Ferguson 2007; Hidalgo
(2009) studied performance of single and multiple BHEs et al. 2009). In heat transport, heterogeneity in thermal
both without and with complete seasonal thermal recharge, properties and perhaps hydrodynamic thermal dispersion are
i.e. completely balanced and unbalanced heat load functions. the related factors. In regards to the relationship of thermal
They concluded that for a single BHE, balanced heat load is dispersivity with groundwater flow, Ferguson (2007) and
not necessary while in an infinite field of BHEs it is essential Hidalgo et al. (2009) confirmed this connection, while, on the
to ensure the long-term sustainability. contrary, Doughty et al. (1982) considered it to be otherwise.
Recently, there has been an interest in evaluating the effect Sauty et al. (1982) suggests including the hydrodynamic
of groundwater flow on BHEs. A preliminary assessment of dispersion and correlation between the effective thermal
the effect of groundwater flow by Chiasson et al. (2000) conductivity and Darcy velocity. With this assumption, a
shows that the Péclet number is a relevant indicator but also thermal response test sensitivity study by Wagner et al. (2012)
mentions that its exact value depends on the choice of indicates that thermal dispersivity of the subsurface can affect
characteristic length. According to their simulations, heat the effective thermal conductivity measured in the test;
transport by groundwater flow can be significant in high although they assumed a rather high Darcy velocity of 0.1 m/
hydraulic conductivity materials. They also estimate the day (i.e. 1.15×10−6 m/s).
effective thermal conductivities and conclude that higher Groundwater flow can help to reduce the BHE
groundwater velocity increases effective ground thermal installation length and cost through increasing the effec-
conductivity. Gehlin (2002) concludes that groundwater flow tive thermal conductivity of the ground and enhancing the
(in continuum, porous zone or fracture form) significantly heat exchange process (Wang et al. 2012); therefore,

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


191
including it in the design procedure can increase the economic center node of the BHE and coupled with the rest of the model
sustainability of the system. According to Diersch et al. domain (Fig. 1). The discretized approach increases the
(2011b), in thermal storage systems, groundwater may have a computation time and amount of resources needed but the
rather significant impact on system thermal performance and detailed temperature distributions, within and near the
long‐term efficiency by transporting the stored heat away borehole, is a key benefit of this method. This makes it
from the BHEs. Given that the large majority of BHE systems especially suitable when analyzing the design features of a
are currently designed based on a heating/cooling load single borehole. As only one BHE is modelled here, accurate
balance (i.e. no groundwater flow), in reality, the loop will results can be achieved using a reasonable amount of
not function as designed. computational resources.
In order to have efficient and practical designs and
guidelines—which effectively integrate groundwater flow—
major parameters and thermo-hydrogeological factors
influencing the system performance as well as its impact Base scenario
have to be determined. This study includes assessment of The discretized finite-element model is comprised of the fluid
thermal plume growth and dispersion. Sensitivity analysis on inside the pipe, pipe wall, grout and the surrounding soil-
major hydrogeological, system and meteorological factors groundwater matrix. The horizontal model domain is
(groundwater flux, subsurface thermal conductivity, volu- 100 m×100 m. The element size varies from about 2 m at
metric heat capacity, thermal dispersivity and porosity, grout the borders down to 0.5 mm at the pipe and borehole walls.
thermal conductivity, background and loop inlet tempera- Discretization in vertical direction is done by inserting slices
tures) is performed to identify the key factors. Borehole every 1 m in depth. The modelled BHE depth is 100 m,
depth and loop flow rate are not included as they are the forming 101 slices. The flow inside the tubes is represented
dependent designed aspects and will affect the installation by 1D discrete feature elements (DFE) passing through the
and operation costs. The aim is to classify the main center of the pipes and connecting in the bottom in a U shape
parameters affecting thermal efficiency of BHEs. The results (Fig. 1). The loop flow rate and inlet temperature are assigned
will also provide a basic approximation of how much the at the DFE location in the top slice as boundary conditions. In
efficiency of a single BHE may change under different order to represent the almost instantaneous transverse heat
conditions. While some of the parameters studied have been transfer inside the tube due to the turbulent flow regime (to
evaluated by other authors, the approach in this paper— maximize the heat exchange through the pipe walls),
simulating all the parameters in one model over a system life relatively extreme values are assigned to thermal properties
time—allows for a sounder classification and comparison inside the tube (i.e. heat conductivity 1,000 J/m/s/K and
between them. Groundwater flow and geology can also specific heat capacity 0.001 MJ/m3/K) with an anisotropy
affect the thermal recovery—reversion of temperatures back factor of zero—to prevent vertical interference. This results in
to initial state—at the borehole, and surroundings after high thermal conductivities in the x and y directions and zero
system abandonment. This is important as environmental in z direction (depth) inside the tube. The heat extraction is
and thermal sustainability issues can extend beyond a defined by a constant loop inlet temperature of 0 °C; the
system’s lifetime. Examples of such issues are concerns subsurface initial and background temperature is 10 °C. These
with quality of drinking-water resources and thermal are both representative values as they are in agreement with
performance of future installations (Oriol 2010). Thermal the common practice and literature (Banks 2008, 2012; VDI
recovery is also relevant in the short-term when a system’s
thermal load includes a season with no net heating/cooling
load. Thus, in addition to the operation phase, recovery of
temperatures under different conditions is also studied.
Although for simplicity, this study is done for a single
borehole and the key findings can be extended to multi-
borehole arrays.

Model setup and scenarios


Modelling is performed in FEFLOW, which is a density-
dependent fully-coupled groundwater flow and heat transport
code (DHI-WASY 2013). In FEFLOW, modelling of the
vertical closed loop is possible under two different approaches
(Diersch et al. 2010, 2011a, b): (1) discretizing all borehole
elements and assigning flow and thermal material properties
on a nodal/element basis in, what is referred to as, a fully
discretized three-dimensional model (FD3DM)—selected for Fig. 1 Discretized BHE finite element mesh and the linear DFEs in
this study; and (2) a built-in module where a simplified one- the bottom slice. Vertical elements are denoted by the circles in pipe
dimensional (1D) element (BHE solutions) is inserted at the centers and the horizontal element is symbolized by the connecting line

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


192
2001). Total simulation time of the model is 25 years. The the Darcy velocity (q) is also equal to the product of porosity
borehole settings and material properties are presented in and groundwater pore velocity (v), increase in gradient is
Table 1. The assigned hydrogeological properties are the base seen as increase in velocity and affects the advective
values from Table 2 (Domenico and Schwartz 1998; transport through altering the pore velocity. Changes in
Hellström 1991). porosity, under the base scenario’s constant groundwater flux
in this study, will lead to corresponding variations in velocity
and thus unchanged heat transport by advection. It should be
Sensitivity analysis scenarios and fundamentals noted that this is valid under the assumption of porosity and
hydraulic conductivity being varied independently. In
In this study, the sensitivity analysis is done following the
general, porosity does not play a role in advective heat
one-factor-at-a-time method; all material properties and
transport when comparing cases with the same groundwater
boundary conditions are maintained constant at all times,
fluxes. Porosity (εf) controls the conductive portion of the
except the parameter on which sensitivity analysis is
heat transport through bulk thermal conductivity and
performed. Each variable is changed independently from
volumetric heat capacity (Eqs. 2 and 3).
the others. This approach allows maintaining full control
The dimensionless thermal Péclet number, as formu-
over the model inputs and simple analysis of the outputs.
lated by Domenico and Schwartz (1998), is expressed in
The three-dimensional (3D) governing equation of heat
Eq. (4). It is the ratio of advective heat transport by bulk
transport in two phases (solid–fluid) can be re-written as
fluid motion to conductive heat transport by the solid–
Eq. (1) (after Anderson 2005; Chiasson et al. 2000;
fluid matrix, i.e. bulk thermal conductivity (Eq. 3).
Domenico and Schwartz 1998; Saar 2011):
  ρ f c f qL
λ I þ αT ⋅jqj þ ðαL −αT Þ
q⊗q Pe ¼ ð4Þ
∂T ρ f ⋅c f jq j λ
þ ∇:ðT qÞ− ∇2 T ¼ QH
∂t ρ⋅c ρ⋅c
ð1Þ where L is characteristic length.
In this study, thermal dispersivity values are assigned
based on the scale of the problem domain, assumed to be in
where: the same order of solute dispersivity and have a αL/αT=10
ratio. Also here thermal dispersion is linked to the
ρc ¼ ε f ρ f c f þ εs ρs cs ð2Þ groundwater flux; therefore, longitudinal and transverse
thermal dispersion become more important in the heat
transport equation (Eq. 1) under higher groundwater flows.
λ ¼ ε f λ f þ εs λs ð3Þ Thermal diffusivity (α) is the ratio function of thermal
conductivity on volumetric heat capacity (see Table 3 for
notations):
are the bulk volumetric heat capacity and bulk thermal
conductivity, respectively (see Table 3 for notations). λ
α¼ ð5Þ
According to Eq. (1), the groundwater flux (q), the product ρc
of hydraulic conductivity (K) and hydraulic gradient (i)
defines the rate of heat transported by advection. In reality, In conduction-dominated heat transport, thermal diffusiv-
where porosity (εf) and K are constant material properties, as ity defines how quickly a material can come to thermal
equilibrium and how efficiently heat is conducted through
it. Therefore, increase in thermal conductivity and
Table 1 In-borehole setting and material properties for the base volumetric heat capacity will respectively improve and
scenario
deteriorate the heat conduction. Volumetric and specific
Parameter Unit Value heat capacity of soils and rocks are commonly considered
−3
Dynamic viscosity of refrigerant 10 kg/m/s 2.75 to be constant or otherwise varying in a narrow range.
Thermal conductivity of refrigerant J/m/s/K 0.415 Consequently, it is the thermal conductivity that controls
Heat capacity of refrigerant 10+3 J/kg/K 3.873 the thermal diffusivity of the subsurface. In Eq. (1), heat
Density of refrigerant 10+3 kg/m3 1.045
Flow discharge of refrigerant m3/d 25 conductivity and heat capacity appear in different compo-
Thermal conductivity of grout J/m/s/K 2 nents of the equation and will be studied individually here.
Volumetric heat capacity of grout 10+6 J/m3/K 1.5 While heat load function can be analysed as a separate
Borehole diameter m 0.1524 factor, it is especially influential regarding sustainability of
Pipe distance (center to center) m 0.075
Pipe outer diameter m 0.0381 multi-borehole systems. As a single BHE is modeled here,
Pipe wall thickness m 0.0035 to make the analysis more straightforward and to exclude
Thermal conductivity of pipe J/m/s/K 0.45 other sources of variation in the results, the thermal load
Depth m 100 has been simplified to a constant inlet temperature rather
Background temperature °C 10
Inlet temperature °C 0 than seasonal cyclic. Nonetheless, in most cases the heat
load will not be completely balanced, which leads to

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


193
Table 2 Parameters examined in the sensitivity analysis and their base scenario values as well as upper/lower limits. Flux values in
pretenses are products of hydraulic conductivities and gradients. Only one parameter is varied at a time
Parameter Unit Lower limit Base value Upper limit
Hydraulic conductivity m/s 10−10 10−6 10−3
Hydraulic gradient – 0 0.001 0.1
Darcy flux m/s 0 (and 10−13) 10−9 10−6 (and 10−7, 10−8)
Thermal conductivity of solids J/m/s/K 1.5 3 4.5
Volumetric heat capacity of solids 106 J/m3/K 1.5 2.5 3.5
Porosity – 0.05 0.3 0.5
Longitudinal thermal dispersivity m 0.1 0.5 1
Transverse thermal dispersivity m 0.01 0.05 0.1
Thermal conductivity of grout J/m/s/K 1 2 3
Background temperature °C 7.5 10 12.5
Inlet temperature °C −5 0 5

accumulation of the off-balance in the long-term; therefore, from the outlet temperature graph. The assessment is done
the constant heat extraction—without seasonal thermal at 6 months, comparable to one heating/cooling season in
recharge—will be the worst-case scenario. cyclic thermal load functions, and 25 years, representing
A summary of analysed variables and their range is the long-term conditions. Loop outlet temperatures are
presented in Table 2. While a wider range might be possible related to heat extraction through the following equations:
for some of the factors, the sensitivity analysis focuses on the X
system response to parameter variations in their typical ðT o −T i Þ⋅ρr cr ⋅Qr ⋅Δt
ranges (Domenico and Schwartz 1998; Hellström 1991) and Total energy extracted ¼ H ¼ X ð6Þ
aims at highlighting the influence of each variable in its Δt
range and, also, relative to other parameters.
The outlet temperature of the loop is considered as the
dependent analyzed variable since it is directly related to
the thermal efficiency of geothermal systems. In each 
scenario, the specific heat extraction rate is calculated Heat extraction power ¼ P ¼ H t
ð7Þ

Table 3 Notations used in the formulations


where t, operation time, is assumed to be 8 h/day.
Symbol Parameter Unit

Standard parameter notation Specific heat extraction rate ¼ S ¼ P L ð8Þ
c Specific heat capacity J/kg/K
H Heat energy J
h Hydraulic head m
I Identity matrix – where L is the borehole depth.
i Hydraulic gradient –
K Hydraulic conductivity m/s
L Characteristic length (in Eq. 4) m
L Borehole length (in Eq. 8) m Model validation and mesh convergence study
P Power J/s or W
q Darcy flux m/s A mesh convergence study is the key to obtaining a
Q Flow m3/s satisfactory level of accuracy in a reasonable time.
S Specific heat extraction J/s/m or W/m The sensitivity of results to mesh density is especially
t Time s important in problems with high groundwater veloci-
T Temperature K or °C
v Velocity m/s
ties and mesh Péclet numbers (Donea and Huerta
α Thermal diffusivity m2/s 2003). Thus, here the mesh convergence study is done
α Thermal dispersivity m for the scenario with highest groundwater velocity
(if with subscript) (3×10−6 m/s). The mesh is refined until no change in
ε Portion of volume in – outlet temperature and thermal plume size, the key
each phase, i.e. εf = porosity
λ Thermal conductivity J/m/s/K relational parameters for this study, result from further
ρ Density kg/m3 refinement. With an additional step in refinement of the
Subscripts and superscripts mesh—element size reduced to about half—no noticeable
f Fluid – change in the plume extent and loop temperature (±0.01 °C
H Heat –
i Inlet – accuracy) was observed.
L Longitudinal – To have further confidence in the accuracy of the
o Outlet – results, they are also validated against an analytical
r Refrigerant – solution. For this purpose, the method by Eskilson and
s Solid –
T Transversal –
Claesson (1988) is used, which is implemented in
FEFLOW and is chosen here due to its proven robustness

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


194

Fig. 2 Loop outlet temperatures by the FD3DM model vs. the analytical solution under no groundwater flow and 10−6 m/s groundwater flux (3×10‐6
m/s groundwater velocity)

and accuracy, especially when approaching steady-state comparison between modeling heat exchangers by analytical
conditions (Diersch et al. 2010), which is the case here as the solution and FD3DM approaches in FEFLOW see Diersch
inlet temperature is constant. The mesh convergence study et al. 2010, 2011a, b.
has been done for the analytical solution as well; the mesh
was refined except for nodes surrounding the BHE (see
Diersch et al. 2010 for more details) multiple times to Results and discussion
increase the accuracy under high velocities in this model.
The agreement of the FD3DM and analytical results in From this point forward, the term ‘plume’ is referring to
Fig. 2—under no groundwater flow conditions—validates the 9 °C contour line which corresponds to a 1 °C change
the model. Comparison between the analytical and FD3DM from the initial subsurface temperature unless otherwise
results under high velocity (i.e. 3×10−6 m/s) shows a slight stated. The base scenario results show that temperature
difference; however, the error is negligible (less than 5 %). gradients in proximity of the BHE are higher and approach
Since the two models are validated against each other under steady-state conditions quicker compared to those far from
no groundwater flow, and as mentioned in the preceding the borehole (Figs. 3, 4a,b). Similarly, they dissipate more
section ‘Model setup and scenarios’, the FD3DM approach rapidly after the BHE shut down. Conversely, for the 9 °C
is generally considered to be more accurate and is accepted isoline—far from the borehole—attenuation appears to
here as the reference solution. The performed FD3DM mesh begin after about 2 years, taking around 10 years to
convergence analysis under the case with highest ground- completely dissipate (Fig. 3). Temperatures closer to the
water velocity ensures accuracy and validity of the results background initial temperature recover at a slower rate,
under all of the modeled scenarios. For more in-depth while the extreme temperatures decline relatively quicker.

Fig. 3 Approximate radius of temperature isolines in production and abandonment phases at base-scenario conditions; groundwater flux
10−9 m/s, background temperature 10 °C

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


195
This can be important depending on different thermal/ solid matrix. Increasing the Darcy velocity from 10 to 10−7
−9

environmental concerns. For instance, maximum subsurface m/s (Fig. 4b,d), the 25-year thermal plume becomes slightly
temperature disturbance, which is addressed in some longer (to 39 from 36.5 m) and narrower (to 21 from 36.5 m).
geothermal guidelines—e.g. VDI 4640 (VDI 2001)—is However, the impact zone down-gradient spreads out a lot
more spatially limited and reversible compared to subtle farther than it does up-gradient (34 m compared to 18.25 m);
temperature changes that can affect aquatic ecosystems nevertheless, the plume, as already defined, decreases in area
farther away (Markle and Schincariol 2007). The implica- due to enhanced thermal dispersion and dilution by ground-
tions rise in multi-borehole and borehole thermal energy water flow. Further increasing the velocity to 10−6 m/s makes
storage (BTES) systems where the size and temperatures are the plume dramatically smaller (Fig. 4f). Comparing the
higher. plumes at 1 and 25 years under different groundwater fluxes
10−9, 10−7 and 10−6 m/s shows that under higher groundwater
flows, thermal plumes approach steady state considerably
quicker (Fig. 4).
Groundwater flux Analysis of the outlet temperature versus multiple
As mentioned in the preceding, groundwater flux, also Darcy velocities (Fig. 5) also shows that higher velocity
known as Darcy velocity (q), is the hydrogeological results in higher heat exchange efficiency and a quicker
parameter affecting the advective heat transport in the fluid– BHE thermal equilibrium (i.e. approaching steady-state

Fig. 4 Thermal plumes under groundwater flux (a–b) 10−9 m/s, (c–d) 10−7 m/s, and (e–f) 10−6 m/s after 1 and 25 years. Note the scale
difference. Flow direction is from bottom to top of all images

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


196

Fig. 5 Loop outlet temperature vs. time under various groundwater fluxes during operation and after abandonment

conditions). Under a velocity of 10−6 m/s, the equilibrium as they do not influence the heat transport logarithmically
is reached in ca. 90 days, while with no groundwater flow, (Eq. 1). Consequently, with every order of magnitude
i.e. 0 m/s flux, equilibrium is still not completely achieved increase in velocity it will have increasingly more impact
even after 25 years. The loop temperature gain (i.e. the on system efficiency.
difference between inlet and outlet temperatures) at 10−6 Similarly, under the recovery period, groundwater flow
m/s is almost doubled compared to no flow conditions. In drastically enhances the temperature to return to initial state
addition, calculated specific heat extractions in Table 4 (Fig. 5). Groundwater flow appears to be more effective in
show that under higher velocities the efficiency substan- thermal recovery as the conductive heat transfer by the BHE
tively heightens, which supports the hypothesis that diminishes and advective component by groundwater
hydrogeological factors may become central under certain dominates. As can be seen in Fig. 5, at 10−8 m/s groundwater
conditions. In general, the results indicate that groundwa- flux, impact on loop temperature is negligible during
ter influence on loop temperatures starts to become production but becomes noticeable during recovery period.
significant at ca. 10−7 m/s and higher fluxes (Fig. 5).
However, the impact on the loop temperature is less
significant than on the plume outline, which is because the
borehole wall temperature dictates the BHE heat exchange
Thermal conductivity of the ground
at any time, not the far-field temperature. Figure 5 also While the thermal conductivity of geological material can
indicates that the influence progressively escalates with range from approximately 0.5 to 6 W/m/K, it usually lies
every order of magnitude increase in groundwater flux. in the range of 1.5 to 4.5 W/m/K (Hellström 1991), as
There is no appreciable difference among the low-range studied here. The thermal gradient between BHE and
velocity. The common use of logarithmic scale for background lessens when thermal conductivity increases,
hydraulic conductivity and velocity may be misleading which can be observed as a larger plume (ca. 35 % larger

Table 4 Summary of average borehole specific heat extraction rates in sensitivity analysis scenarios over 6 months and 25 years, assuming
8 h/day operation
Parameter Average specific heat extraction rate (W/m)
Lower limit Base value Upper limit
6 months 25 years 6 months 25 years 6 months 25 years
Groundwater flux 79 58.5 79 58.5 106.5 83.25
Thermal conductivity of solids 55.5 37.5 79 58.5 99 75
Volumetric heat capacity of solids 79 58.5 79 58.5 79 58.5
Porosity 89.5 67.5 79 58.5 71 52.25
Thermal dispersivity of subsurface 79 58.5 79 58.5 79 58.5
Thermal conductivity of grout 73 54.5 79 58.5 82 60
Background temperature 60 45 79 58.5 104 72
Inlet temperature 119 88 79 58.5 40 29.5

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


197

Fig. 6 Thermal plumes under the subsurface thermal conductivity Fig. 8 Thermal plumes under the subsurface volumetric heat
increased from a 1.5 J/m/s/K to b 4.5 J/m/s/K after 1 year showing capacity increase from a 1.5×106 J/m3/K to b 3.5×106 J/m3/K, with
growth in size regionally and shrinkage locally 1 year showing more reduction in size regionally than locally

at 9 °C) and steeper temperature gradients close to the thermal conductivity (Fig. 7). The 25-year loop tempera-
BHE (Fig. 6). Thus, the plume scale disturbed-temperature ture gain nearly doubles when thermal conductivity of
zone enlarges but the local disturbance near the BHE, which solids increases from 1.5 to 4.5 W/m/K. The calculated
is closely linked to system performance, subsides. The average specific heat extractions over 6 months and
temperatures at the borehole wall are 1–1.5 °C improved. 25 years also shows a doubling rise both in the short
As the loop temperatures confirm, there is a direct term and long term, indicating the importance of subsur-
relationship between thermal performance of the BHE and face thermal conductivity (Table 4). Therefore, it is

Fig. 7 Loop outlet temperature vs. time under different thermal conductivities of the subsurface during operation and after abandonment

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


198

Fig. 9 Loop outlet temperature vs. time under different volumetric heat capacities of the subsurface during operation and after abandonment

essential to know the thermal conductivity of ground as confirm, variations in volumetric heat capacity have an
accurately as possible to have a proper BHE design. insignificant impact on BHE outlet temperatures under
Thermal conductivity has an analogous but significant- both production and abandonment times (Fig. 9).
ly weaker impact on the temperatures in the recovery
phase (Fig. 7). This is because the thermal gradient
between heat exchanger and the surrounding, which is
the driving force for the heat transfer by conduction, Porosity of the subsurface
diminishes when the borehole is shut down. Therefore, As mentioned in the preceding section ‘Sensitivity analysis
higher thermal conductivity improves the BHE perfor- scenarios and fundamentals’, variations in porosity affect
mance more effectively than it enhances its recovery. advective heat transport only if the pore velocity remains
constant; under the constant q assumption of this study,
porosity is solely influencing the heat transport by conduction.
Bulk volumetric heat capacity and thermal conductivity are
Volumetric heat capacity of the ground functions of porosity. Geological material in general has
Variation in specific heat capacity influences material’s higher heat conductivity and lower volumetric heat capacity
internal energy. The variation in density and especially (i.e. higher thermal diffusivity) than water. The results show
specific heat capacity in geological media is fairly small more loop temperature gain and heat extraction rates in less
(Hellström 1991). By increasing volumetric heat capacity porous material—under the same groundwater flux (Fig. 10
from 1.5×10+6 to 3.5×10+6 J/m3/K, the plume extent and Table 4). The significance of advective transport will
radius decreases in regional scale (at 9 °C) by 20 %; but vary under different groundwater fluxes. The less porous
the change is subtle locally in contours near the borehole subsurface also shows slightly faster thermal recovery.
wall (Fig. 8). Therefore, as the loop temperature results While porosity and hydraulic conductivity are often

Fig. 10 Loop outlet temperature vs. time under different subsurface porosity values during operation and after abandonment

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


199

Fig. 11 Loop outlet temperature vs. time under different subsurface longitudinal/transverse thermal dispersivity values during operation
and after abandonment

functionally dependent within the same type of geological reflects our lack of exact knowledge, or representation of,
material, here for the sensitivity analysis, porosity is varied heterogeneity in the permeability and thermal property fields.
independently from hydraulic conductivity. However, as the In any case, thermal dispersion remains controversial
earlier results (see section ‘Groundwater flux’) showed, at and necessitates further study. Some studies assume that
velocities below 10−7 m/s, order of magnitude the difference thermal and solute dispersivity have the same order of
can be overlooked. magnitude (deMarsily 1986; Molson et al. 1992).
Vandenbohede et al. (2009) found that thermal
dispersivity is smaller than solute dispersivity and that
scale dependency is less important; although, there are
Thermal dispersivity of the subsurface other studies which conclude that the effect of thermal
Dispersivity values are selected based on the scale of the BHE dispersivity is negligible compared to conduction and set
problem with a ratio of αL/αT=10. With the studied base thermal dispersivity to zero (Hopmans et al. 2002;
groundwater flux (10−9 m/s via the hydraulic conductivity and Hutchence et al. 1986). As mentioned in the
gradient in the base scenario), the loop outlet temperatures ‘Introduction’, the relationship between thermal
(Fig. 11) appear not to be sensitive to thermal dispersivity dispersivity and groundwater flow is debatable, although
values. Although, as previously discussed, the significance of recent studies (e.g. Ferguson 2007; Hidalgo et al. 2009)
thermal dispersivity rises as groundwater flow rate increases. confirm that connection; however, the spatial heterogene-
At the 10−6 m/s groundwater flux, the effect of thermal ity in thermal properties seems to be less important than
dispersivity is obvious. Increasing the longitudinal thermal that of permeability (Ferguson 2007). Considering the
dispersivity from 0.1 to 1 m (αL/αT=10) raises the thermal relationship between dispersion and groundwater flow and
efficiency by about 20 % (Fig. 11). However, precise the inaccuracy in related parameters, e.g. hydraulic
quantification of dispersivity is a problematic task as it generally conductivity, thermal dispersivity becomes less important.

Fig. 12 Loop outlet temperature vs. operation time for grouts with poor (1 J/m/s/K) and average (2 J/m/s/K) thermal conductivity as well
as thermally enhanced grout (3 J/m/s/K)

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


200

Fig. 13 Loop outlet temperature vs. operation time under different background temperatures

Grout thermal conductivity Background and inlet temperatures


Thermally enhanced grout is known to have a positive impact Although the ground temperatures may be relatively
on efficiency of geothermal heat-pump systems as it enhances accurately known in every region, they may vary by a
the heat exchange between the BHE and the surrounding few degrees in time or from locale to locale. The
ground. This is a similar effect as that of the subsurface thermal sensitivity analysis results show that a 2.5 °C deviation
conductivity. According to the results, modification of the grout of the average background temperature around the
thermal properties does alter the BHE efficiency (Fig. 12). The presumed value of 10 °C (25 %) changes the heat
results in Table 4 indicate that thermally enhanced grout extraction rate by ca. 25 % (Fig. 13 and Table 4). This
(λ=3 W/m/K) increases heat extraction by more than 10 % implies that it is critical for a sustainable BHE design to
compared to a grout with poor thermal conductivity (λ=1 W/m/ know the background temperature accurately.
K). However, this influence is limited compared to that of the Under extreme weather conditions, i.e. peak loads, a
ground thermal conductivity which can increase the perfor- geothermal system may have to operate for longer times in
mance by ca. 100 % (Table 4); nevertheless, it does not order to deliver the required energy, and the heat pump COP
contradict the importance of proper grout selection. While (coefficient of performance) will fall. Conversely, the
ground thermal properties are not controllable, other than underground portion of the system performs more efficiently
through siting the borehole, grout type is generally by choice. A when inlet temperatures are farther from the underground
thermally enhanced grout reduces the thermal gradient— background temperatures. This is because the thermal
similar to ground thermal conductivity—in immediate prox- gradient between loop temperature and borehole wall is an
imity of the tube and borehole, which makes the heat exchange essential element in BHE heat exchange. The results confirm
more efficient. that decreasing the inlet temperature from +5 to 0 °C and

Fig. 14 Loop outlet temperature vs. time under different inlet temperatures during operation and after abandonment

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


201
the borehole wall. The latent heat of water-ice phase
change (80 cal/g) improves the energy storage, which also
keeps temperatures near the borehole closer to the
groundwater freezing point for longer times thereby
lowering the thermal gradient drop between BHE and
surroundings. Additionally, thermal diffusivity of ice is
about 8 times that of water at 0 °C (James 1968). All
these effects indicate even better thermal performance
in reality compared to the FEFLOW modelled results
at below zero temperatures and ground freezing.
Analyzing the data provided by Nordell and Dikici
(1998) confirms that below-zero air temperature results in
higher energy extraction rates, while the loop temperatures
stay at 0 °C.

Conclusion
During the BHE operation, temperatures stabilize slower far
from the borehole, i.e. the plume keeps growing, compared
to near-BHE temperatures. The analysis shows that generally
the ground temperatures (thermal plume) are more sensitive
to changes than the loop temperatures. Thus, accurate
assessment of the subsurface properties is more important
concerning the BHE’s impact zone than its thermal
performance. After shutting the system, extreme tempera-
tures in the domain diminish the quickest and the rate of
recovery slows down as temperatures reach that of the
Fig. 15 Thermal plumes under inlet temperatures a +5 °C and b background. Moreover, the response to the borehole shut-
−5 °C after 1 year showing significant difference. Note the scale down and thermal recovery may occur with delay far from
difference the BHE, which is important in respect to controlling and
reversing different environmental and thermal impacts.
Of the parameters analyzed in this study, the most
important factors for BHE design include inlet and back-
further to −5 °C, radically increase the heat exchange ground temperature (i.e. temperature gradient), thermal
efficiency (Fig. 14). Borehole fluid temperatures are directly conductivity of the ground and Darcy velocity. Increased
related to the heat extraction rates. The heat extraction rate groundwater flow can substantially reshape and dissipate the
with −5 °C inlet temperature is about triple that with +5 °C thermal plume by altering the heat transport by enhancing
(Table 4); however, excessive temperature changes are advection and dispersion processes; it also reduces the time
prohibited under some guidelines—e.g. VDI 4640–2 (VDI to reach steady-state conditions. The impact becomes
2001). Comparing the plumes in the two cases proves that progressively more observable by every order of magnitude
the BHE thermal load has a distinct influence on the extent of increase in the groundwater flux. It becomes noticeable in
its thermal impact zone (Fig. 15). The difference in loop temperatures at velocities above 10−7 m/s range and is
recovered temperatures is about 2 °C after 1 year and substantial at 10−6 m/s level. Darcy velocities in this range—
0.5 °C after 25 years despite the initial 10 °C difference in 10−7 m/s and higher—cannot be disregarded as they also
loop temperatures (Fig. 14). This means that although the have a substantial impact on the plume shape and size. In a
recovery time is affected by the loop temperatures, it is not comparable way, but more effectively, groundwater flow
very sensitive to them in the long term. However based on enhances thermal recovery to initial conditions; the impact is
the preceding results, the 0.5 °C change in background noticeable in fluxes over 10−8 m/s. Groundwater flow proved
temperature is expected to correspond to 5 % change in to be the most important factor in thermal recovery.
system performance. Higher thermal conductivity of the ground solids greatly
It should be noted that FEFLOW is unable to model heightens the thermal efficiency of a BHE by improving the
multiple water phases and the latent heat for phase change. heat transport; conversely, it causes larger thermal plumes.
However, freezing the ground by lowering the temperature Since the thermal gradient drops severely and quickly when
below zero during the heating season is a possible the BHE is shut down, thermal conductivity has a relatively
practice. Ground freezing may also result in environmen- minor impact on thermal recovery. While enhancing the
tal and geotechnical concerns. Also the volume expansion thermal conductivity of the grout also increases the borehole
of freezing water can damage the heat exchanger pipes specific heat extraction, this effect is more limited in extent.
and modify the contact between grout encased pipe and Thus, the choice of using a thermally enhanced grout is

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


202
governed by balancing the costs, and changes in the grouts program and by the Natural Sciences and Engineering Research
non‐thermal characteristics (e.g. placement viscosity, Council (NSERC) of Canada.
sealing) along with efficiency gains.
Thermal impact of the volumetric heat capacity of soil solids
on functioning of BHE and its thermal recovery is negligible. References
However, there is an inverse relation between subsurface
volumetric heat capacity and the plume size. Thermal Anderson MP (2005) Heat as a ground water tracer. Ground Water
43(6):951–968
efficiency did not appear to be sensitive to thermal dispersivity Andrews CB (1978) The impact of the use of heat pumps on ground
values at the scale of a BHE domain at low groundwater water temperatures. Ground Water 16(6):437–443
velocities, i.e. 10−9 m/s, but becomes more sensitive only at AWP (Arbeitsgemeinschaft Wärmepumpen) (2007) Technische
higher rates, i.e. 10−6 m/s. Nonetheless, accurate measurement Merkblätter AWP T1 Wärmepumpenheizungsanlagen mit
of thermal dispersivities in situ is often not possible. Erdwär-mesonden [Heat pump heating system with geothermal
energy sampling probe]. AWP, Zürich, Switzerland
Under constant groundwater flux, e.g. this study, Banks D (2008) An introduction to thermogeology: ground source
increasing the porosity as an individual factor can have a heating and cooling. Wiley-Blackwell, Oxford
negative impact on a heat exchanger’s performance by Banks D (2012) An introduction to thermogeology: ground source
deteriorating subsurface bulk thermal properties, i.e. heating and cooling, 2nd edn. Wiley-Blackwell, Oxford
Chiasson AD, Rees SJ, Spitler JD (2000) A preliminary assessment
conductive heat transport. Comparing cases with equal of the effects of groundwater flow on closed-loop ground-source
pore velocities, higher porosity will also imply more heat heat pump systems. ASHRAE Trans 106:380–393
transport by advection. The natural link between porosity deMarsily D (1986) Quantitative hydrogeology. Academic, San
and hydraulic conductivity has to be considered but can be Diego, CA
DHI-WASY (2013) FEFLOW finite element subsurface flow and
neglected in velocities under 10−7 m/s. transport simulation system—user’s manual/reference manual/white
The current ground temperature should be accurately papers. Recent release 6.1. Technical report, DHI-WASY, Berlin
known prior to the BHE installation in order to assure a Diao N, Li Q, Fang Z (2004) Heat transfer in ground heat exchangers
thermally sustainable design and performance. Under short with groundwater advection. Int J Therm Sci 43:1203–1211
periods of extreme hot and cold weather conditions when a Diersch HJG, Bauer D, Heidmann W et al (2010) Finite element
formulation for borehole heat exchangers in modeling geother-
geothermal system has to deliver more heating load and the mal heating systems by FEFLOW. FEFLOW white papers vol
heat pump COP drops, peak inlet temperatures far from the V, DHI-WASY, Berlin
background temperature boost the heat exchange between Diersch HJG, Bauer D, Heidmann W et al (2011a) Finite element
BHE and the ground. However, changes in the loop fluid modeling of borehole heat exchanger systems: part 1, funda-
mentals. Comput Geosci 37(8):1122–1135
temperature may be undesirable in the long-term as the Diersch HJG, Bauer D, Heidemann W et al (2011b) Finite element
thermal impact zone extent is sensitive to the heat extraction/ modelling of borehole heat exchanger systems: part 2, numer-
input rates (i.e. loop fluid temperatures). At the lower end ical simulation. Comput Geosci 37(8):1136–1147
where temperatures fall below zero, freezing the groundwater Domenico PA, Schwartz FW (1998) Physical and chemical
hydrogeology, 2nd edn. Wiley, New York
can further enhance the energy exchange and storage. Donea J, Huerta A (2003) Finite element methods for flow
Although the duration and rate of thermal recovery depend problems, 1st edn. Wiley, West Sussex, UK
on loop temperatures, a thermal recovery time equal to the Doughty C, Hellström G, Tsang CF, Claesson J (1982) A dimension-
operation time appears to be a good estimation for ground less parameter approach to the thermal-behavior of an aquifer
temperatures to return close to the initial state, i.e. within 1 °C. thermal-energy storage-system. Water Resour Res 18(3):571–587
Eskilson P (1987) Thermal analysis of heat extraction boreholes.
Finally, while closed-loop BHEs do not have the potential PhD Thesis, University of Lund, Lund, Sweden
large environmental impacts, or direct strong reliance on Eskilson P, Claesson J (1988) Simulation model for thermally interacting
groundwater flow that open-loop heat exchangers do, they heat extraction boreholes. Numer Heat Transf 13:149–165
demand increased attention by hydrogeologists and regula- Ferguson G (2007) Heterogeneity and thermal modeling of ground
water. Ground Water 45(4):485–490
tors. Currently, regulations that impose guidelines on Ferguson G, Woodbury AD (2006) Observed thermal pollution and
temperature thresholds and minimum distance criteria for post-development simulations of low-temperature geothermal
thermal alterations, or recognize the inherent variability in systems in Winnipeg, Canada. Hydrogeol J 14(7):1206–1215
geologic material thermal properties, are largely lacking, Ferguson G, Woodbury AD (2007) The urban heat island in the
subsurface. Geophys Res Lett 34:L23713, 4 pp
which includes not explicitly addressing the effect of Fujii H, Itoi R, Fujii J et al (2005) Optimizing the design of large-
groundwater advection on effective thermal conductivity scale ground-coupled heat pump systems using groundwater
and recognizing at what groundwater velocities advection and heat transport modelling. Geothermics 34(3):347–364
becomes important. This has led to BHE design methodol- Gehlin S (2002) Thermal response test: method development and
ogies that often exclude heat transport by groundwater evaluation. PhD Thesis, Luleå University of Technology, Luleå,
Sweden
advection. This study clearly shows that quantifying the Haehnlein S, Bayer P, Blum P (2010) International legal status of
thermo-hydrogeological parameters in vertical closed-loop the use of shallow geothermal energy. Renew Sust Energ Rev
BHEs supports the design of sustainable efficient systems 14(9):2611–2625
while addressing the impacts on down-gradient BHEs or Hellström G (1991) Ground heat storage: thermal analyses of duct
storage systems. Department of Mathematical Physics,
water supply and ecological features. University of Lund, Lund
Hellström G (1998) Thermal performance of borehole heat exchangers.
Acknowledgements This research is funded by the Ontario In: Proceedings of the Second Stockton International Geothermal
Ministry of Environment (MOE) under the Best in Science (BiS) Conference. Galloway, NJ, March 1998

Hydrogeology Journal (2014) 22: 189–203 DOI 10.1007/s10040-013-1060-6


203
Hidalgo JJ, Carrera J, Dentz M (2009) Steady state heat transport in Priarone A, Lazzari S, Zanchini E (2009) Numerical evaluation of
3D heterogeneous porous media. Adv Water Resour 32:1206– long-term performance of borehole heat exchanger fields. In:
1212 Proceedings of the COMSOL Conference 2009, Milan, Italy
Hopmans JW, Simunek J, Bristow KL (2002) Indirect estimation of Rybach L, Eugster WJ (2002) Sustainability aspects of geothermal heat
soil thermal properties and water flux using heat pulse probe pumps. In: Proceedings of the 27th Workshop on Geothermal
measurements: geometry and dispersion effects. Water Resour Reservoir Engineering, Stanford University, CA, January 2002, pp
Res 38(1):7-1–7-14 50–64
Hutchence K, Weston JH, Law AG et al (1986) Modeling of a liquid Saar MO (2011) Review: geothermal heat as a tracer of large-scale
phase geothermal doublet system at Regina, Saskatchewan, groundwater flow and as a means to determine permeability
Canada. Water Resour Res 22:1469–1479 fields. Hydrogeol J 19:31–52
Ingersoll LR, Plass HJ (1948) Theory of the ground pipe heat Sauty JP, Gringarten AC, Fabris H et al (1982) Sensible energy
source for the heat pump. ASHVE Trans 47:339–348 storage in aquifers: 2. field experiments and comparison with
Ingersoll LR, Adler FT, Plass HJ et al (1950) Theory of heat theoretical results. Water Resour Res 18(2):253–265
exchangers for heat pump. ASHRAE Trans 56:167–188 Signorelli S, Kohl T, Rybach L (2005) Sustainability of
James DW (1968) The thermal diffusivity of ice and water between production from borehole heat exchanger fields. In: Proceedings
−40 and + 60°C. J Mater Sci 3(5):540–543 of World Geothermal Congress, Antalya, Turkey, April 2005
Kurevija T, Vulin D, Krapec V (2011) Influence of undisturbed Vandenbohede A, Louwyck A, Lebbe L (2009) Conservative solute
ground temperature and geothermal gradient on the sizing of versus heat transport in porous media during push–pull tests.
borehole heat exchangers. Proceedings of World Renewable Transport in Porous Media 76(2):265–287
Energy Congress, Linköping, Sweden, 8–13 May, 2011, Paper Vandenbohede A, Hermans T, Nguyen F et al (2011) Shallow heat
17, Linköping Electron Conf Proc 57(5):1360–1367. injection and storage experiment: heat transport simulation and
Lee CK, Lam HN (2009) Determination of groundwater velocity sensitivity analysis. J Hydrol 409:262–272
in thermal response test analysis. In: Proceedings of Effstock VDI (Verein Deutscher Ingenieur) (2001) Thermische Nutzung des
2009 conference, Stockholm, Sweden, June 14–17, 2009, Untergrundes: Richtlinie VDI 4640, Blatt 2—Erdgekoppelte
Paper 17, 8 pp Wärmepumpen [Thermal use of the underground: VDI 4640
Lo Russo S, Taddiaa G, Verdab V (2012) Development of the guideline, part 2—ground source heat pump systems]. Beuth, Berlin
thermally affected zone (TAZ) around a groundwater heat pump Wagner V, Bayer P, Kübert M et al (2012) Numerical sensitivity
(GWHP) system: a sensitivity analysis. Geothermics 43:66–74
study of thermal response tests. Renew Energy 41:245–253
Markle JM, Schincariol RA (2007) Thermal plume transport from
Wang H, Yang B, Xie J et al (2012) Thermal performance of
sand and gravel pits: potential thermal impacts on cool water
streams. J Hydrol 338(3–4):174–195 borehole heat exchangers in different aquifers: a case study
Molson JW, Frind EO, Palmer CD (1992) Thermal energy storage from Shouguang. Int J Low-Carbon Technol 2012:1–7
in an unconfined aquifer. 2. Model development, validation, and Witte H (2012) A parametric sensitivity study into borehole
application. Water Resour Res 28(10):2857–2867 performance design parameters. In: Proceedings of Innostock
Nordell B, Dikici D (1998) Winter air as a source for cold storage the 12th International Conference on Energy Storage, Lleida,
injection. In: Proceedings of Second International Stockton Spain, May 2012
Geothermal Conference, Galloway, NJ, 15–16 March 1998 Zeng H, Diao N, Fang Z (2003) Heat transfer analysis of boreholes
Oriol L (2010) Ground source heat pumps: development prospect in in vertical ground heat exchangers. Int J Heat Mass Transf
France. Royal Institute of Technology (KTH), Stockholm 46:4467–4481