Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

2.

Consider a 161kV transmission line from Station G to


Station H (32 pts total) Station G Station H Et VT ratio=1400/1
CT ratio=240/1 V.=98 Zo � kV V=952-120 � kV V =82 Z120 �
kV 19=428 Z-15 � A 1 =7192-127 � A c=1660272 A VT
ratio=1400/1 CT ratio=240/1 V=9520 � kV V =962-120 � kV V
=672120 � kV l=4552168 � A 1 =75259 A 1=15702-108 � A A
phase-ground fault occurs somewhere in the area; your
assignment to determine whether the fault is on the line G-H, or
behind Station G, or behind Station H. The relays at Stations G
and H protecting the line G-H measure the three-phase voltages
and currents shown. The VT ratio is 1400/1 at both stations, the
CT ratio is 1200/5 at both terminals. The ground directional
element has a 60 degree lag type connection and requires
polarizing voltage|3V. > 2V secondary and operating current
310 > 0.5A secondary: � Ground directional element: 31, with-
3V. NOTE: The ground directional element operates with
maximum torque when 31. lags-3V. (negative 3V.) by 60
degrees, which indicates a forward fault. All phasor diagrams
must show the reference phasor, maximum torque line, and
operate and non-operate zones. Clearly label all phasors. a.
Ground Directional Relay at Station G on Line G-H (12 pts)
Using phasors and the characteristic of this zero sequence
directional relay, determine whether the element will indicate a
forward fault (operate decision) or a reverse fault (non-operate
decision). b. Ground Directional Relay at Station H on Line G-H
(12 pts) Using phasors and the characteristic of this zero
sequence directional relay, determine whether the element will
indicate a forward fault (operate decision) or a reverse fault
(non-operate decision). C. Conclusion (8 pts total) Is the fault
on the line, or behind Station G, or behind Station H? Why?
(4pts) Which phase(s) is(are) faulted? Why? (4pts)

You might also like