The document provides measurements from relays at Stations G and H on a transmission line during a phase-to-ground fault. It asks to:
1) Determine if the ground directional relay at Station G indicates a forward or reverse fault.
2) Determine if the ground directional relay at Station H indicates a forward or reverse fault.
3) Conclude whether the fault is on the line or behind one of the stations, and identify the faulted phase(s) based on the relay measurements.
The document provides measurements from relays at Stations G and H on a transmission line during a phase-to-ground fault. It asks to:
1) Determine if the ground directional relay at Station G indicates a forward or reverse fault.
2) Determine if the ground directional relay at Station H indicates a forward or reverse fault.
3) Conclude whether the fault is on the line or behind one of the stations, and identify the faulted phase(s) based on the relay measurements.
The document provides measurements from relays at Stations G and H on a transmission line during a phase-to-ground fault. It asks to:
1) Determine if the ground directional relay at Station G indicates a forward or reverse fault.
2) Determine if the ground directional relay at Station H indicates a forward or reverse fault.
3) Conclude whether the fault is on the line or behind one of the stations, and identify the faulted phase(s) based on the relay measurements.
Consider a 161kV transmission line from Station G to
Station H (32 pts total) Station G Station H Et VT ratio=1400/1 CT ratio=240/1 V.=98 Zo � kV V=952-120 � kV V =82 Z120 � kV 19=428 Z-15 � A 1 =7192-127 � A c=1660272 A VT ratio=1400/1 CT ratio=240/1 V=9520 � kV V =962-120 � kV V =672120 � kV l=4552168 � A 1 =75259 A 1=15702-108 � A A phase-ground fault occurs somewhere in the area; your assignment to determine whether the fault is on the line G-H, or behind Station G, or behind Station H. The relays at Stations G and H protecting the line G-H measure the three-phase voltages and currents shown. The VT ratio is 1400/1 at both stations, the CT ratio is 1200/5 at both terminals. The ground directional element has a 60 degree lag type connection and requires polarizing voltage|3V. > 2V secondary and operating current 310 > 0.5A secondary: � Ground directional element: 31, with- 3V. NOTE: The ground directional element operates with maximum torque when 31. lags-3V. (negative 3V.) by 60 degrees, which indicates a forward fault. All phasor diagrams must show the reference phasor, maximum torque line, and operate and non-operate zones. Clearly label all phasors. a. Ground Directional Relay at Station G on Line G-H (12 pts) Using phasors and the characteristic of this zero sequence directional relay, determine whether the element will indicate a forward fault (operate decision) or a reverse fault (non-operate decision). b. Ground Directional Relay at Station H on Line G-H (12 pts) Using phasors and the characteristic of this zero sequence directional relay, determine whether the element will indicate a forward fault (operate decision) or a reverse fault (non-operate decision). C. Conclusion (8 pts total) Is the fault on the line, or behind Station G, or behind Station H? Why? (4pts) Which phase(s) is(are) faulted? Why? (4pts)
Power Electronics Lab Experiment-No. 6 Single-Phase Full and Half Wave Controlled SCR Rectifier Aim: To Study and Analyze The Properties and The Characteristics of A Single-Phase