" Power Details ": Project Name
" Power Details ": Project Name
SITE ID : V16
ASSESSMENT:
APPROVED REMARKS:
DISAPPROVED REMARKS:
V16 SL
MALVAR-BULIHAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
AC POWER DETAILS
Electrical Connectivity: Permanent Temporary Tap to neighbor
Others pls specify
Genset
Genset 1 Brand: Powercity Genset 1 capacity: 60 KVA With Pad & Fuel Line (Y/N): N
Genset 1 Brand: Genset 2 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 3 capacity: With Pad & Fuel Line (Y/N):
KWHR Meter Rating: CL200 ATS Brand: Powercity ATS Capacity: 225A, 3P
MTS: 2x150AT
Main breaker capacity( inside radio room ): 150 AT Wire size: 2-50mm²THHN
MCB ACPDB
Rating ON/OFF LOAD Rating ON/OFF LOAD
150 ON SPACE
70 ON RECTIFIER
50 ON RECTIFIER
50 OFF SPARE
40 OFF SPARE
*put NO LABEL for those
without proper labelling 20 ON COMBA REPEATER
40 ON PERIMETER LIGHT
40 ON TOWER LIGHT
32 ON ACU2
32 ON ACU 1
20 ON C.O.
20 ON ROOM LIGHT
SITE SURVEY REPORT
DOCUMENT NO PAGE
SHELTER TYPE (VAN, CONCETE SHELTER, BLDG):VAN AC Loading @ MAIN (AMPERES): L1-45.7 / L2-40.6
SHELTER AREA: LOT SITE SIZE OF WIRE @ ACPDB - MAIN (mm²/AWG): 2-50mm²
TYPE OF VAN (COLLAPSIBLE, RIGID) : LENGTH OF WIRE: 25 m
TRANSFORMER QUANTITY & CAPACITY (KVA): 37.5 KVA
ACPDB RATING (AT): 150 MAIN BREAKER RATING(AT): 150
Breaker Ratings (AT) Load AMP Load Description
SPACE
70 17.5 RECTIFIER
50 14.1 RECTIFIER
50 SPARE
40 SPARE
20 COMBA REPEATER
40 1.0 PERIMETER LIGHT
40 1.3 TOWER LIGHT
32 9.1 ACU 2
32 6.5 ACU 1
20 0.3 C.O.
20 0.8 ROOM LIGHT
AC POWER SUFFICIENCY
Current (I)
AC LOAD Voltage (V) VA Remarks
L1 L2 L3
MAIN BREAKER 210 45.7 40.6 At ACPDB
9597.00
Total 45.7
It = Highest line current reading x 130 % (Safety factor considering Battery charging, WACU starting current & DC loading increase)
It = 45.7 x 130 %
It = 59.41 Amps.
Recommendation/s:
Transformer loading:
Actual AC load (V x It) / Transformer KVA Rating X 100 %
% loading = 33.27 %
Note: Sufficient
NO PICTURE NO PICTURE
ECB MCB
NO PICTURE NA
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
MTS ATS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
B5 - SITE LAYOUT
RECTIFIER
RECTIFIE ACPDB
150 AT
50 mm2 + 14 mm2 THHN U.G.,
25 meters, 1 1/2 in. dia. IMC
ATS
225 A ECB
MTS 150 AT
GENERATOR 150 AT
50 mm2 + 14 mm2 THHN U.G.,
6 meters, 1 1/2 in. dia. IMC
KWHR
CL200
12 meters - 38 mm2 THHN AERIAL
TRANSFORMER 7 meters - 50 mm2 THHN 1 1/2 in. dia. IMC
37.5KVA
NEW
ACPDB
150 AT 50 mm2 + 14 mm2 THHN U.G.,
MB 25 meters, 1 1/2 in. dia. IMC
ATS 150 AT
225 A ECB
MTS 150 AT
GENERATOR 150 AT
50 mm2 + 14 mm2 THHN U.G.,
6 meters, 1 1/2 in. dia. IMC
KWHR
CL200
( Replace service cap )
12 meters - 50 mm2 THHN AERIAL
TRANSFORMER 7 meters - 50 mm2 THHN 1 1/2 in. dia. IMC
37.5KVA
V16 S.L
MALVAR-BULIHAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
7 meters
50 mm2 THHN,
TRANSFORMER
12 meters
37.5 KVA CL200 M
38 mm2 THHN AERIAL
50 mm2 + 14 mm2 THHN U.G.,
ECB L1: 45.7 6 meters, 1 1/2 in. dia. IMC
150 AT L2: 40.6
50 mm2 + 14 mm2 THHN U.G.,
25 meters, 1 1/2 in. dia. IMC
N E
ATS
225 A
G
L
50 mm2 + 14 mm2 THHN ,
3 meters, 1 1/2 in. dia. IMC
N E
MTS
150 AT
L
50 mm2 + 14 mm2 THHN U.G.,
3 meters, 1 1/2 in. dia. PVC ACPDB L1: 45.7
L2: 40.6
150AT,2P
70AT,2P
SPACE 1 2 RECTIFIER
50AT,2P 50AT,2P
RECTIFIER 3 4 SPARE
40AT,2P 20AT,2P
COMBA
SPARE 5 6
40AT,2P 40AT,2P REPEATER
PERIMETER
7 8 TOWER LIGHT
LIGHT
32AT,2P 32AT,2P
ACU 2 9 10 ACU 1
20AT,2P 20AT,2P
C.O 11 12 ROOM LIGHT
SITE SURVEY REPORT
DOCUMENT NO PAGE
V16 S.L
MALVAR-BULIHAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
Proposed SLD
7 meters
50 mm2 THHN,
N E
ATS
225 A
G
L 50 mm2 + 14 mm2 THHN ,
50 mm2 + 14 mm2 THHN ,
3 meters, 1 1/2 in. dia. IMC
3 meters, 1 1/2 in. dia. IMC
N E MB
MTS
150AT
150 AT
50 mm2 + 14 mm2 THHN , L
3 meters, 1 1/2 in. dia. PVC NEW ACPDB
150AT,2P
70AT,2P 70AT,2P
RECTIFIER #1 SUPPLY A 1 2 RECTIFIER #1 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #2 SUPPLY A 3 4 RECTIFIER #2 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #3 SUPPLY A 5 6 RECTIFIER #3 SUPPLY B
20AT,2P 20AT,2P
ACU 1 7 8 ACU 2
20AT,2P 20AT,2P
ACU 3 9 10 ACU ( FUTURE )
20AT,2P 20AT,2P
C.O. 11 12 LIGHTINGS
TOWER LIGHT 13 14 PERIMETER LIGHT
SPARE 15 16 SPARE