Professional Documents
Culture Documents
Performance Improvement of Shunt Active - TPE - 2007
Performance Improvement of Shunt Active - TPE - 2007
Performance Improvement of Shunt Active - TPE - 2007
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
248 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Fig. 2. Simplified diagram of the proposed shunt APF topology with feedback
and feedforward loops. The current sensor is placed in between the connection
points of each inverter to the power system.
II. DESCRIPTION OF APF PARALLEL TOPOLOGY where: and are the transfer functions of the inner
current controllers (equivalent generalized integrators), as they
A. Selection of the Topology will be defined in Section III; and are each
inverter’s equivalent gain; and are the switching pe-
By using two separate inverters, different topologies may be riods of each inverter. Here it is assumed that the A/D sampling
configured as it is illustrated in Fig. 3. Dependent on the place- frequency is the same as the PWM switching frequency.
ment of the harmonic current sensor, either one or both APFs Further, the equations that hold for the feedforward APF (see
can be configured in feedforward or feedback loop. also Fig. 2) can be written as
Regarding the feedforward APF topology the most common
control method is the current-controlled source. On the other
(3)
hand it is proven in literature that the feedback APF topology
provides a better transient response operating as voltage-con-
trolled source [6]. Thus, for the analysis carried out in Fig. 3 the which gives
feedforward APF is controlled as a current source and the feed-
back APF is controlled as a voltage source. (4)
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 249
TABLE I
CALCULATION OF THE LINE CURRENT I FOR EACH CASE IN FIG. 3
For the feedback APF the complexity of the hardware design, the number of analog
digital (AD) converters and possible the speed of the calcula-
tions.
(5) However, case-(b) and case-(d) require a careful design re-
garding the imposed harmonic current references. In the sim-
plest way the reference can be given as half of the measured
which gives harmonic current for each inverter, but then both inverters must
be rated at the same nominal power. For other references values,
(6) additional processing is necessary in order to correctly balance
the reference signals and as it is shown in Fig. 3.
Thus, one may describe the resultant line current as a func- Finally, the actual study selects only the topology shown in
tion of the initial harmonic current from the ASD and the ex- case-(f).
isting source voltages ( and , i.e., fundamental respective
harmonic voltages from the grid side). The analytical expression B. Description of the Selected Topology (Case-f)
of the line current determined for all six topologies in Fig. 3 The proposed topology is shown in Fig. 2. As it can be no-
is given in Table I. ticed, the APF is composed of two separate inverters, each of
As it can be noticed the line current in case-(a) does not them using independent current and voltage controllers. To min-
depend on the existing voltage harmonic distortion, and the re- imize the cost this structure may be furthermore reduced by
sultant transfer function is the direct effect of each individual connecting the inverters together on the dc-link [4]. Thus, only
transfer function of the active power filters. Case-(c) is useful one dc-link capacitor would be needed and implicitly a single
for damping the resonances between the grid and possible ac-ca- voltage controller. However, it makes the hardware design and
pacitor at the load side, because both and give the the control more complicated, as a zero sequence current cir-
effect of a damping in series with the grid impedance. However, culates between inverters [7]. In order to break the circulation
the harmonic current mitigation directly depends on the filter’s path of the zero sequence currents between inverters, a galvanic
inductances, which may create design restrictions depending on isolation is inserted by means of either isolating transformer or
the grid impedance value . For case-(b) and case-(d), the com- separate dc-capacitors. Thus, the inverters can be independently
mand law depends on the imposed reference and controlled.
for each filter, which is useful for sharing the loading between The load current sensor for harmonic detection is placed in
filters, during different operating conditions. Case-(f) achieves between the connection points of the inverters, thus achieving
better harmonic mitigation compared to case-(e) regarding the a feedback path for the first inverter (PWM inverter 1), and a
influence of the harmonic grid voltages . feedforward path for the second inverter (PWM inverter 2). This
Furthermore, for case-(b), case-(d) and case-(f), the schemes new topology may allow each inverter to perform different tasks,
use just one pair of harmonic detection sensors, which reduce depending of the imposed current references.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
250 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Thegenerationofharmonicreferencecurrentisdoneinmaster-
slave configuration, as the first inverter dictates the harmonic ref-
erence of the second. Two separate master-slave configurations
can be implemented, one is the harmonic-sharing and the other is
the load-sharing control. In the harmonic-sharing mode the first
inverter mitigates only several harmonic currents, and the second
inverter takes care of the rest of the harmonic spectrum.
It is also possible to operate the filters in load-sharing mode,
when both filters compensate the same harmonic spectrum but Fig. 4. Principle algorithm of harmonic extraction and reference current con-
with different imposed reference amplitudes. If the harmonic trol in synchronous fundamental frame.
reference is equally divided between inverters then each takes
50% of the total required power. Other ratio of harmonic refer- has already mitigated part of the harmonic spectrum. The cur-
ences in each inverter is also possible and useful for inverters rent reference for the feedforward APF contains only the har-
with different rated powers or when it is desired to control the monics left in the line currents. The second inverter is designed
distribution of the power losses, but the reference generation al- for mitigation of high order harmonics. As a result, the second
gorithm is more complicated. inverter is configured for a faster dynamic response, thus com-
A third possibility is to configure the proposed topology in a pensating the slower dynamic of the first inverter (which may
redundant-mode, which is a benefit provided by the proposed cas- react slowly and imprecisely in transient conditions especially
caded configuration. The redundant-mode is a particular case of if its switching frequency is lower).
the load-sharing mode, when the harmonic reference is not di- The entire topology has the advantage of a good harmonic
vided between inverters but set at maximum for only one inverter. mitigation in stationary conditions (due to the feedback in-
Thus, APF1 has the task of the main harmonic compensator. Since verter), but also very good response in transient conditions (due
APF2 follows APF1, when APF1 ceases its harmonic mitigation, to the faster feedforward inverter) [8]. The power losses of the
APF2 automatically can take over, if it is configured to do so. This second inverter are kept at a lower value since the high order
offers a wireless independent control feature, because there are harmonics are not so large. Another advantage of this topology,
no connectivity wires between the inverters to change informa- but not tested here, is that the feedback APF can provide an
tion about the internal variable or states of each control loop. Each active damping of existing resonances between the grid and a
APF’s control is only based on information available locally at possible installed ac-capacitor at the load side, e.g., EMI filter
the inverter terminals. However, the redundant-mode implies that or custom passive harmonic filter, although this requires an
the rated power of APF2 is sufficiently large to cover the overall increased bandwidth of the APF current controller.
harmonic mitigation, which may not be cost-effective.
In order to optimize the cost, one may use the feedback inverter III. CONTROL ALGORITHM
(PWM inverter 1) to compensate only a part of the harmonic spec- The control algorithm is developed in the synchronous funda-
trum, for instance, the low order harmonics as most of the power mental reference dq-frame. The input signals, measured in abc-
density is contained here. As the compensation is carried out in the coordinates (i.e., stationary reference frame), are transformed
feedback loop, the steady state response is expected to be much into the fundamental -rotating reference frame by means of
more tolerant to nonlinearities and parameter variation [6]. the Park transformation
Consequently, since the inverter is of high rated power a lower
switching frequency is desirable. Regarding the selection of the
switching frequency one choice is to use different switching
frequencies (i.e., APF1 low, APF2 high) in order to have re-
duced power losses but still a good overall harmonic mitigation (7)
performance. Another choice is to use the same switching fre-
quency for both, which allows implementation of interleaving where , and , , are the currents in the -frame, re-
techniques to reduce the switching frequency ripple, and conse- spective in -frame; and is the angular position of the ref-
quently EMI and the line filter. erence frame.
In this paper, the second choice was used due to some hard-
The frame rotates at fundamental angular frequency that
ware limitation (APF1 and APF2 have the same switching fre-
makes the fundamental current to appear as dc-component and
quency), but a discussion presented in Section VI analyzes the
the harmonics as ac-signals. Thus, harmonic detection becomes
potential operational efficiency improvement if APF1 switches
a matter of removing the dc-signal by means of a high-order
at a lower frequency. In the case when both power inverters
high pass filter [(HPF) in Fig. 4 with a cutoff frequency between
have the same switching frequency, by interleaving their carriers
25 Hz and 120 Hz] [9]. The HPF outputs the harmonic current
by 180 it may significantly reduce the line switching current
to be compensated by the active filter. This is a fourth order
ripple. Thus, the highest ripple amplitude is seen at a doubled
switching frequency, which is much easier to filter out. As the filter implemented in fundamental frame, which removes the
frequency of the switching current is higher it gives lower EMI fundamental current, i.e., the dc-signal
and is also damped much faster in the power lines due to their
inductive effect. (8)
The feedforward inverter (PWM inverter 2) receives the in-
formation of the harmonic content only after the first inverter where the cutoff frequency is 300 rad/s, and 0.8.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 251
(11) (15)
where and are the proportional and the integral
gains of each complex current controllers. if APF2 is set for redundant-mode 1, else 0.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
252 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Fig. 6. Bode plots of (a) open loop transfer functions H s ( ) for APF 1 (b)
open loop transfer function H s ( ) for APF 2, and (c) overall closed loop system
TABLE II
PARAMETERS USED IN CONTROL FOR BOTH INVERTERS APF1 AND APF2
transfer function as in Table I.
By replacing (14) and (15) into the initial open loop transfer
functions of each active filter in (1) and (2), one can deter-
mine the Bode plots of each system as it is given in Fig. 6. The
behavior of the open loop transfer functions , of
each active filter APF1, respectively, APF2 is dominated by the
transfer functions of the harmonic integrators re-
spectively . Therefore, the close loop Bode plot of
the overall system (APF1 together with APF2) looks as a mul-
tiple notch filter tuned for the selected frequency in -frame
[see Fig. 6(c)].
Thus, APF1 mitigates only the lower harmonic currents (fifth
and seventh) the controller having a very high selectivity (i.e.,
low value for gain) in order to determine a precise mitiga- task. This may happen in transient conditions due to the slow
tion of these harmonics. However, it is known that lower values response of the APF1 as previously presented.
of give also a slow dynamic response. Another particular case is when the APF1 is programmed to
The filter APF2 mitigates the rest of the characteristic har- reduce (but not completely) the amount of mitigated harmonics
monic currents up to 31st order. The selectivity of the equivalent due to different operating conditions, which automatically en-
harmonic integrators is set wider (i.e., higher values for the ables the second filter APF2 to take over the harmonic miti-
gains) in order to cope with the variation of the line frequency. gation without any special communication between both active
As the line frequency varies, the harmonics suffer also a small power filters. However, as initially mentioned, in this case the
frequency shift, which it is more severe as the harmonic goes power rating of the second filter should be sized for that pur-
higher. Thus, in order to provide a better harmonic tracking, it pose.
is advisable to have a wider selectivity of the higher order res-
onant controllers. As the selectivity of the controller is wider,
IV. IMPLEMENTATION
the dynamic response of the APF2 becomes faster compared to
APF1. The proposed topology and control method are tested on a
The redundant-mode feature is implemented in the APF2 laboratory setup (Fig. 7) composed of two Danfoss inverters
control by setting 1 [see Fig. 5 and (15)] which enables the VLT 5006 rated as 400 V/7.6 kVA each. The switching fre-
sixth harmonic inner current controller in . This can be quency was set to 12.6 kHz for both inverters. The control algo-
seen in Fig. 6(b) where the open loop transfer function rithm is implemented with a dSpace system DS1103, using the
is plot in two cases, with and without a harmonic integrator Matlab/Simulink Real Time Workshop toolbox [17], having the
tuned for 300 Hz. If is not tuned for 300 Hz it means control parameters set as in Table II.
that the filter APF2 cannot mitigate the same harmonics as the In practice a proper the design of the inductors depends on
first filter APF1. If is tuned for 300 Hz, it allows APF2 the mitigated harmonic current spectrum and its power level.
to mitigate also the fifth and seventh harmonics. But since its A higher power inverter requires a lower inductance in order
mitigation follows after APF1, the effect is similar as sharing to reach lower iron losses. A faster inverter (i.e., compensation
the harmonic load when the first filter APF1 does not fulfill its of higher harmonic orders) requires also a lower inductance to
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 253
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
254 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
TABLE IV
CHARACTERISTICS OF THE PROPOSED TOPOLOGY DEPENDING ON THE DESIRED COMPENSATED
SPECTRUM AND SELECTED SWITCHING FREQUENCY OF EACH INVERTER
Fig. 11. Measured steady-state response of the APF2—feedforward compen- Fig. 12. Measured steady-state response of the proposed topology. Both low
sation. The harmonic compensation reference is set for mitigation of the high order and high order harmonic currents are mitigated down to 2% THD , by
order (11th to 31st) harmonic currents. enabling APF1 and APF2 together.
A typical stationary response for the feedforward APF2 is retically be identical (see columns 2 and 4). Furthermore, it is
given in Fig. 11, where the total line current still contains a sig- proven in [6], that although some of the gains are different,
nificant quantity of harmonic distortion, but with smoother cur- the transfer functions of the feedforward and feedback loops
rent gradients. As the current spectrum indicates (see Table V are equivalent. This should give the same harmonic mitigation
column 5) the APF2 filter compensates only for the harmonic performance of the feedback compared to the feedforward re-
currents higher than 11th order. spective the proposed topology. However, it is experimentally
noticed that the proposed topology provides a better harmonic
C. Combined Compensation current mitigation, presumably due to the cascade configuration
Different tests can be performed with the proposed topology (see columns 6 respective 7 of Table V). In order to measure the
depending on the imposed compensated spectrum and the se- data presented in columns 2 and 4 of Table V, the control of each
lected switching frequency of each inverter, as it can be seen in branch APF1 or APF2 is configured as in (13) by enabling all
Table IV. In this paper only Case-1 and Case-3 are tested. five orders of the harmonic integrators, 6,12,18,24,30 .
First, both feedback and the feedforward loops are connected The second test is with the proposed topology set as in Case-3
together and set as in Case-1, Table IV. The result, seen in the Table IV, but in a particular case as redundant-mode, which is
line current waveform, represents the cumulative effect of both done by setting the parameter 1 in (15) and Fig. 5. The
loops. Thus, both low order and high order harmonics are com- steady state harmonic mitigation performance can be seen in
pensated, as shown in Fig. 12. Table V compares the harmonic Table V column 7, which is the best compared to the other pre-
current spectrum for each of the measured cases. The proposed sented cases. Fig. 13 shows the dynamic response of the entire
topology brings the THD from the initial value of 27%, without APF for a load step of 5 kW due to the ASD. Active filter APF1
any filtering, down to less than 2% with both APF filters active. responds slower because of the lower gain of its equiva-
The control method uses harmonic integrators, which ideally lent harmonic integrator. Active filter APF2 responds faster and
present infinite amplification at the selected harmonic. There- takes over the compensation of the fifth and seventh harmonics
fore, the mitigation performance of each branch should theo- during the transient. This is possible due the enabled redun-
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 255
TABLE V
COMPARISON OF THE APF’S HARMONIC MITIGATION PERFORMANCE FOR EACH MEASURED
CASE: FEEDBACK, FEEDFORWARD AND THE PROPOSED PARALLEL TOPOLOGY
Fig. 13. Dynamic response of the proposed topology in redundant-mode, for a Fig. 14. Dynamic response of the proposed topology in redundant-mode, when
load step of 5 kW created by the ASD. APF1 responds slower than APF2 due the APF1 is powered on while APF2 was compensating the overall harmonic
to different parameters set for the current controller. current spectrum. Once APF1 becomes active APF2 keeps its main task of com-
pensating only the higher harmonic orders.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
256 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
TABLE VI
COMPARISON OF A SINGLE UNIT INVERTER AND THE PROPOSED DUAL PARALLEL
TOPOLOGY OPERATING EITHER IN HARMONIC-SHARING OR LOAD-SHARING MODE
V. DISCUSSION For the given case the measured THD is 27%, while the fifth
As the active filtering device proposed here is composed from and seventh gives a THD 26% for APF1 and the higher
two inverters, one may argue if this is economically feasible. It harmonic currents 11th up to 31st give a THD 6% for
is expected that two inverters are more expensive than a single APF2
one, as each inverter has to contain its own gate-drives, insulated THD
gate bipolar transistor (IGBT) switches, snubbers, logic-control
THD (17)
and protection circuits.
The costs of the gate-drives, and the control and protection As it can be seen, the second inverter is of a smaller power, i.e.,
circuits are fairly lower compared to the power switches. Thus, 10%–50% of APF1, which in turn means a relatively lower cost.
they can be neglected, since nowadays there is a large diversity An interesting discussion is also the potential operational ef-
of cost-effective integrated modules on the market. ficiency improvement between the harmonic-sharing and load-
Therefore, the most expensive components are considered the sharing modes. In harmonic-sharing mode APF1 may switch at
power switches and the passive components: boost inductor lower frequency, sufficiently to handle the low order harmonics,
and dc-capacitor , which are all sized based on the designed and APF2 switches at higher frequency to handle the higher
rated power of the inverters. order harmonics. In load-sharing mode APF1 and APF2 switch
An estimation of the designed rated power of the inverter is at high frequency and each may be set to take care half of the
the inverter kVA rating, calculated based on the inverter root- harmonic current. An estimate of the efficiency is determined
mean-square (RMS) output current. The ampere requirement of here based on the estimation of the switching losses in IGBTs.
the power switches is determined by the peak current and not the The IGBT’s conduction losses and the losses in the passive com-
RMS value, thus large IGBTs may still be required depending ponents are not evaluated.
on the load current behavior. However, as the RMS value of the Evaluation of the switching losses is done in the same way as
current determines the inverter power losses and consequently in [18], assuming that the inverter has a linear switching loss de-
the size, volume and costs of the active and passive components, pendency with the amplitude of the current. The average value
a simplified assumption is considered here, that the cost of the of the switching power losses over the fundamental pe-
inverter is mainly determined by its kVA rating. riod is defined in (18). Further, (19) is derived assuming that
For a single unit inverter the designed rated power of the in- the energy losses due to commutation are proportional to
verter is turn-on and turn-off durations and the absolute value of
the output filter current . The filter current may be expressed
THD
in a similar way as in (16) depending on the ASD current and
THD (16) its THD , which is constant for a given case. The power losses
can be related to the switching frequency and the inverter cur-
where and are the power of the APF respective the rent THD as in
ASD; and are the RMS current of the APF
respective the fundamental current of the ASD; and
is the total harmonic current distortion from the ASD.
For the proposed topology, because the harmonic power is di- (18)
vided between two inverters, the RMS current in each inverter
is lower than as for a single unit inverter. Thus, the total rated
power of each inverter is reduced. The second inverter APF2
compensates only the higher harmonics, which have a lower
spectral power compared to the fifth and seventh, in ASD’s ap- (19)
plications, therefore, the rated power of the second inverter is
lower.
Table VI shows the theoretical and the measured THD from THD (20)
nonlinear load. In the actual case the measured THD has a
lower content of higher harmonics due to the 3% front inductor where is the dc-voltage, and are the turn-on re-
in series with the ASD. spective turn-off intervals, is the switching frequency,
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 257
Fig. 15. Estimated efficiency limit based on the switching frequency and the Fig. 16. Steady-state response of the APF filters’ currents and their duty-cycles.
load current THD .
is output inverter current, which can be expressed as a function overall smaller power, even though the efficiency may not be
of the load current and filter THD , is a constant very high. The efficiency of the harmonic-sharing mode is
including all other constant parameters, and is the abso- attractive only if the switching frequency of the APF1 inverter
lute value function. (mitigating the lower order harmonics) is at maximum two
Assuming that in the harmonic-sharing mode the inverter times smaller than the switching frequency of the APF2 inverter
switches at a lower frequency, the switching losses of APF1 (mitigating the higher order harmonics).
inverter are reduced by a factor of As it was previously mentioned, another advantage of the
topology is that, having two separately controlled inverters, they
THD can be interleaved by 180 , to reduce the line switching current
THD (21) ripple.
Fig. 16 shows the filter currents and along with their
Switching losses in harmonic-sharing mode are duty-cycles. It can be noticed that, even the output currents are
different, the duty-cycles look similar. This is because the in-
THD THD verter voltage must be comparable to the line voltage in order
(22) to make the current flowing through the line inductors. Thus,
the duty-cycles contain a fundamental component that makes
Switching losses in load-sharing mode are equally distributed their waveforms to resemble. This property is used to reduce
between inverter the switching ripple of the line current if one uses two carriers
THD (23) shifted by 180 . A simplified illustration of the interleaving is
provided in Fig. 17 for one phase only. The amplitude of the
The efficiency improvement of the harmonic-sharing compared current ripple in each inverter depends on the used inductors.
to load-sharing mode is estimated as Furthermore, even though the carriers are interleaved by
THD THD 180 , the duty-cycles are ac-signals, therefore determining
different pulse width lengths in each inverter. Thus a complete
THD cancellation of the current ripple at the switching frequency
(24) is not possible. However, the interleaving helps in minimizing
Fig. 15 gives a graphical interpretation of (24), as a function of the total line current ripple. The switching frequency is only
the switching frequency factor . partially canceled, as it can be seen in Fig. 18, which reduces
Thus, assuming a reduction by half of the switching fre- the requirement of a stronger line filter against EMIs. A smaller
quency, i.e., 0.5, the efficiency improvement of the EMI filter is assumed to be inexpensive, as it requires smaller
harmonic-sharing is line connected capacitors. Furthermore, smaller capacitors
mean an increase of the system stability, because possible
for theoretical
power system resonances between the capacitors and source
ASD model for measured data (25) impedances are shifted to higher frequencies. The resonances
may be easily damped and may not interfere with the control.
One may determine the boundary limit of the switching fre- If the rated power of APF2 is of a small value, as it is cal-
quency where the efficiency of the harmonic-sharing is lower culated in (17), then the load-sharing feature cannot be used.
compared to the load-sharing. Considering also the data in Therefore, one may need to assign a higher rated power for the
Table VI, it seems that in load-sharing the inverters have an second inverter (APF2), in order to operate in load-sharing. This
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
258 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
VI. CONCLUSION
This paper describes a new topology for dual operation of ac-
tive power filters. The novelty consists in a parallel connection
of two active filters, one working in feedforward current loop
and the other in feedback current loop, both sharing the same
load current sensor. The proposed topology is theoretically an-
alyzed and then practically tested on a laboratory platform.
The most significant features of the proposed solution are as
follows.
— It improves the stationary performance compared to an
APF based on a single inverter.
— It provides an improved dynamic response in frequency-
sharing operation due to the fact that one filter is pro-
grammed for fast compensation, while the other is effec-
tive in stationary operation.
— Load distribution with or without redundancy is possible
in load-sharing operation.
— Wireless operation of the two filters is an intrinsic property
of this topology in all operating situations.
— Current ripple reduction is possible and was confirmed in
interleaving operation.
— The overall achieved THD performance is below 2% from
uncompensated THD value of 27%.
The proposed solution is targeted for medium power Ad-
Fig. 17. Simplified description of the current ripple based on the on-off con- justable Speed Drives applications where the harmonic pollu-
duction instants with the carriers interleaved by 180 . tion is a significant issue.
REFERENCES
[1] IEEE Recommended Practice and Requirement for Harmonic Control
in Electrical Power Systems, IEEE Std. 519-1992, 1993.
[2] S. Hansen, P. Nielsen, P. Thoegersen, and F. Blaabjerg, “Line side har-
monic reduction techniques of pwm adjustable speed drives—a cost-
benefit analysis,” in Proc. PCIM’01, 2001, pp. 39–46.
[3] W. M. Grady, M. J. Samotyj, and A. H. Noyola, “Survey of active
power line conditioning methodologies,” IEEE Trans. Power Delivery,
vol. 5, no. 3, pp. 1536–1542, Aug. 1990.
[4] H. Akagi and K. Nabae, “Control strategy of active power filters using
multiple voltage source PWM converters,” IEEE Trans. Ind. Appl., vol.
lA-22, no. 3, pp. 460–466, May/Jun. 1985.
[5] P. Mattavelli, “A closed-loop selective harmonic compensation for ac-
tive filters,” IEEE Trans. Ind. Appl., vol. 37, no. 1, pp. 81–89, Jan./Feb.
2001.
[6] S. Khositkasame and S. Sangwongwanich, “Design of harmonic cur-
rent detector and stability analysis of a hybrid parallel active filter,” in
Proc. Power Conversion’97, 1997, vol. 1, pp. 181–186.
[7] L. Asiminoaei, E. Aeloiza, J. H. Kim, P. Enjeti, F. Blaabjerg, L. T.
Moran, and S. K. Sul, “An interleaved active power filter with reduced
size of passive components,” in Proc. APEC’06, 2006, vol. 1, pp.
969–976.
Fig. 18. Harmonic spectrum of the filters’ currents and total line current. Spec- [8] S. Kim and P. Enjeti, “A new hybrid active power filter (APF)
trum shows the reduction of the switching frequency f in the source current topology,” in Proc. APEC’01, 2001, vol. 2, pp. 835–841.
I due to 180 interleaved carriers. [9] V. Soares, P. Verdelho, and G. Marques, “Active power filter con-
trol circuit based on the instantaneous active and reactive current id-iq
method,” in Proc. PESC’97, 1997, vol. 2, pp. 1096–1101.
[10] N. Mendalek, K. Al-Haddad, F. Fnaiech, and L. A. Dessaint, “Sliding
mode control of 3-phase 3-wire shunt active filter in the dq frame,” in
means a higher cost for the second inverter, but the advantage Proc. Electron. Comp. Eng. Conf., 2001, vol. 2, pp. 765–769.
is the achievement of redundancy and ride-through functions [11] C. Lascu, L. Asiminoaei, I. Boldea, and F. Blaabjerg, “High perfor-
when one inverters fails. The ratio of the inverter’s size becomes mance current controller for selective harmonic compensation in active
power filters,” in Proc. OPTIM’06, 2006, [CD ROM].
a matter of practical design. For instance if APF2 is only used [12] H. Akagi, “Control strategy and site selection of a shunt active filter
for mitigation of transient conditions due to slower APF1 re- for damping of harmonic propagation in power distribution systems,”
sponse, then its rated power may be selected in the range of IEEE Trans. Power De1ivery, vol. 12, no. 1, pp. 354–362, Feb. 1997.
25%–50% of APF1 power. If APF2 is going to be permanently [13] R. I. Bojoi, G. Griva, V. Bostan, M. Guerriero, F. Farina, and F. Pro-
fumo, “Current control strategy for power conditioners using sinusoidal
used for load-sharing, then its rated power would be comparable signal integrators in synchronous reference frame,” IEEE Trans. Power
to APF1. Electron., vol. 20, no. 6, pp. 1402–1412, Nov. 2005.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 259
[14] J. Allmeling, “A control structure for fast harmonics compensation in Frede Blaabjerg (S’86–M’88–SM’97–F’03) was
active filters,” IEEE Trans. Power Electron., vol. 19, no. 2, pp. 508–514, born in Erslev, Denmark, on May 6, 1963. He
Mar. 2004. received the M.Sc.EE. and Ph.D. degrees from
[15] M. J. Newman, D. N. Zmood, and D. G. Holmes, “Stationary frame Aalborg University, Aalborg, Denmark, in 1987 and
harmonic reference generation for active filter systems,” IEEE Trans. 1995, respectively.
Ind. Appl., vol. 38, no. 6, pp. 1591–1599, Nov./Dec. 2002. He was with ABB-Scandia, Randers, Denmark,
[16] R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh, “Proportional- from 1987 to 1988. He became an Assistant Pro-
resonant controllers and filters for grid-connected voltage-source con- fessor in 1992 at Aalborg University, in 1996 an
verters,” Proc. Inst. Elect. Eng., vol. 153, no. 5, pp. 750–762, 2006. Associate Professor, and in 1998 a Full Professor
[17] Matlab/Simulink, “Software installation and management guide,” in in power electronics and drives. In 2000, he was a
Proc. Real-Time Workshop dSPACE DS1103 Hardware, 2004, [CD Visiting Professor with the University of Padova,
ROM]. Padova, Italy, as well as a part-time Programme Research Leader in wind
[18] A. M. Hava, R. J. Kerkman, and T. A. Lipo, “A high performance gen- turbines at the Research Center Risoe. In 2002, he was a Visiting Professor
eralized discontinuous PWM algorithm,” IEEE Trans. Ind. Appl., vol. at Curtin University of Technology, Perth, Australia. He is involved in more
34, no. 5, pp. 1059–1071, Sep./Oct. 1998. than ten research projects within the industry. Among them is the Danfoss
Professor Programme in Power Electronics and Drives. He is the author or
coauthor of more than 350 publications in his research fields including Control
in Power Electronics (New York: Academic, 2002). He is an Associate Editor
for the Journal of Power Electronics and Elteknik. He has been very involved in
Danish Research policy in the last ten years. His research interests are in power
electronics, static power converters, ac drives, switched reluctance drives,
modeling, characterization of power semiconductor devices and simulation,
wind turbines, and green power inverters.
Dr. Blaabjerg received the 1995 Angelos Award for his contribution in
modulation technique and control of electric drives, the Annual Teacher Prize
from Aalborg University, in 1995, the Outstanding Young Power Electronics
Engineer Award from the IEEE Power Electronics Society in 1998, five IEEE
Lucian Asiminoaei (S’03–M’06) was born in Prize paper awards during the last five years, the C. Y. O’Connor fellow-
Galati, Romania, on April 3, 1973. He received the ship from Perth, Australia in 2002, the Statoil-Prize for his contributions in
B.Sc. and M.Sc. degrees in electrical engineering power electronics in 2003, and the Grundfos-prize for his contributions in
from “Dunarea de Jos” University of Galati, in 1996 power electronics and drives in 2004. He is an Associate Editor of the IEEE
and 1997, respectively, and is currently pursuing the TRANSACTIONS ON INDUSTRY APPLICATIONS and the IEEE TRANSACTIONS ON
Ph.D. degree at the Institute of Energy Technology, POWER ELECTRONICS. He is a member of the Danish Academy of Technical
Department of Power Electronics and Drives, Aal- Science, the European Power Electronics and Drives Association, and the
borg University, Aalborg, Denmark. IEEE Industry Applications Society Industrial Drives Committee. He is also a
From 1996 to 1999, he was with Iron & Steelworks member of the Industry Power Converter Committee and the Power Electronics
Sidex S.A., Galati, as a Maintenance Engineer and in Devices and Components Committee, IEEE Industry Application Society.
1999 moved to the IT Department, IspatSidex LNM
Group, Galati, as a Hardware Engineer. In February 2003, he joined the Institute
of Energy Technology, Department of Power Electronics and Drives, Aalborg
University, and is involved in projects sponsored by Danfoss Drives A/S, Den- Ion Boldea (M’77–SM’81–F’96) received the B.S.
mark and Power Lynx A/S, Denmark. His areas of interests include harmonic and Ph.D. degrees in electrical engineering from the
mitigation, harmonic measurement, and design of active and hybrid filters. University Politehnica, Timisoara, Romania, in 1967
and 1973, respectively.
He is currently a Full Professor at the University
Politehnica Timisoara. He has worked and published
Cristian Lascu received the M.S. and Ph.D. de- extensively on linear and rotary electric machines
grees in electrical engineering from the University and their power electronics control, with and without
Politehnica Timisoara, Timisoara, Romania, in 1995 motion sensors. He co-authored Induction Machine
and 2002, respectively. Handbook (Orlando, FL: CRC, 2001), Linear Motion
In 1995, he joined the Department of Electrical Electromagnetic Devices (London, U.K.: Taylor &
Engineering, University Politehnica Timisoara where Francis, 2001), Electric Drives (Boca Raton, FL: CRC, 2006), and The Electric
his research was focused on power electronics and Generators Handbook (Boca Raton, FL: CRC, 2006). He spent about five years
high performance electrical drives. He was a Visiting as a Visiting Scholar in the U.S. and U.K., and presented keynote addresses,
Researcher at the Institute of Energy Technology, intensive courses, and does consultant work in the U.S., Europe, and Asia. He is
Aalborg University, Aalborg East, Denmark, in 1997 Associate Editor of the Electric Power Components and Systems Journal, and
and 2005, and with the Department of Electrical Director and Founder of the Internet-only, Journal of Electrical Engineering.
Engineering, University of Nevada, Reno, from 1999 to 2000. From 2002 to Dr. Boldea is an active member of the Industrial Drives and Electric Machines
2004, he was with SIEI S.p.A., Italy, working on advanced power electronics Committee, IEEE Industry Applications Society, and Co-chairman of the IEEE
and drives for electrical vehicles under a European Marie Curie Fellowship. IAS Technically Sponsored OPTIM 96, 98, 00, 02, 04, and 06 International
Dr. Lascu received the IEEE IAS Prize Paper Award in 1998. Conferences.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.