ANSI/TIA-942-A: Table 10: Tiering Reference Guide (Telecommunications) Tier 1 (T)
ANSI/TIA-942-A: Table 10: Tiering Reference Guide (Telecommunications) Tier 1 (T)
TIER 1 (T1)
TELECOMMUNICATIONS
General
Cabling, racks, cabinets, & pathways compliant with relevant yes
TIA specifications
Patch panel and patch cable documentation compliant with not required
ANSI/TIA-606-B.
71
ANSI/TIA-942-A
Table 11: Tiering reference guide (architectural)
TIER 1 (A1)
ARCHITECTURAL
Site selection
Proximity to flood hazard area as mapped on a federal Flood
Hazard Boundary or Flood Insurance Rate Map not required
Parking
Separate visitor and employee parking areas not required
Building construction
Type of construction (IBC 2006) no restriction
Fire resistive requirements
Exterior bearing walls Code allowable
Interior bearing walls Code allowable
Exterior nonbearing walls Code allowable
Structural frame Code allowable
Interior non-computer room partition walls Code allowable
Interior computer room partition walls Code allowable
Shaft enclosures Code allowable
Floors and floor-ceilings Code allowable
Roofs and roof-ceilings Code allowable
Meet requirements of NFPA 75 not required
72
TIER 1 (A1)
Miscellaneous Building components
Vapor barriers for walls and ceiling of computer room not required
Roofing
Class no restrictions
Type no restrictions
Entry Lobby
Physically separate from other areas of data center not required
Fire separation from other areas of data center Minimum Code requirements
Security office
Physically separate from other areas of data center not required
Fire separation from other areas of data center Minimum Code requirements
Fire separation from computer room and support areas Minimum Code requirements
Fire separation from computer room and other areas of data Minimum Code requirements
center
Required Exit Corridors
Fire separation from computer room and support areas Minimum Code requirements
74
TIER 1 (A1)
Shipping and receiving area
Shipping and receiving area physically separate from other No shipping and receiving area
areas of data center provided
Minimum Code requirements if
Fire separation from other areas of data center shipping and receiving area present
75
ANSI/TIA-942-A
TIER 1 (A1)
Security Access Control/Monitoring at:
Generators industrial grade lock
UPS, Telephone & MEP Rooms industrial grade lock
Fiber Vaults industrial grade lock
Emergency Exit Doors industrial grade lock
CCTV Monitoring
Building perimeter and parking not required
Generators not required
Access Controlled Doors not required
Computer Room Floors not required
UPS, Telephone & MEP Rooms not required
CCTV
CCTV Recording of all activity on all cameras not required
Recording rate (frames per second) no requirement
76
TIER 1 (A1)
Structural
Facility design to International Building Code (IBC) Seismic Use SDC requirements for building
Design Category (SDC) requirements location
77
ANSI/TIA-942-A
Table 12: Tiering reference guide (electrical)
TIER 1 (E1)
ELECTRICAL
General
System allows concurrent maintenance Not required
Computer & Telecommunications Equipment Power Cords Single Cord Feed with 100%
capacity
Utility
Service Shared
78
TIER 1 (E1)
Uninterruptible Power Supply System
Redundancy N
Output No requirement
79
ANSI/TIA-942-A
TIER 1 (E1)
Grounding
Based on risk analysis as per
Lightning protection system NFPA 780 and insurance requirements.
Battery Room
Separate from UPS/Switchgear Equipment Rooms Not required
Individual Battery Strings Isolated from Each Other Not required
Shatterproof Viewing Glass in Battery Room Door Not required
80
TIER 1 (E1)
Standby Generating System
Sized for UPS System only
Generator Sizing without redundancy
Equipment Maintenance
Operation and Maintenance Staff Offsite. On call.
81
ANSI/TIA-942-A
Table 13: Tiering reference guide (mechanical)
TIER 1 (M1)
MECHANICAL
General
Redundancy for mechanical equipment (e.g. air conditioning
units, coolers, pumps, cooling towers, condensers)
Not required
Heat Rejection
Piping System Single path condenser water
system
82
TIER 1 (M1)
Chilled Water System
Humidity Control for Computer Room Not required
Fire Suppression
Fire detection system yes
Fire sprinkler system When required
Gaseous suppression system No requirement above AHJ
Early Warning Smoke Detection System No requirement above AHJ
Water Leak Detection System No requirement above AHJ
83
ANSI/TIA-942-A
10: Tiering reference guide (telecommunications)
TIER 2 (T2) TIER 3 (T3) TIER 4 (T4)
71
not within the 50-year flood hazard area Not within 100-year flood hazard area and Greater than 91 m (300 ft) from 100-
greater than 91 m (300 ft) from 50-year flood year flood hazard area
hazard area
not required Greater than 91 m (300 ft) Greater than 0.8 km (1/2 mile)
not required Greater than 91 m (300 ft) Greater than 0.8 km (1/2 mile)
not required Greater than 1.6 km (1 mile) and less Greater than 8 km / 5 miles and less
than 48 km (30 miles) than 48 km (30 miles)
not required yes (physically separated with yes (physically separated by fence or
separate entries) wall with separate entries)
not required yes (physically separated with yes (physically separated by fence or
separate entries) wall with separate entries)
9.1 m (30 ft) minimum separation with 18.3 m (60 ft) minimum separation with
not required physical barriers to prevent physical barriers to prevent
vehicles from driving closer vehicles from driving closer
Allowed only if occupancies are non- Allowed if all tenants are data centers or Allowed if all tenants are data centers or
hazardous telecommunications telecommunications
companies companies
Minimum Code requirements (not less than Minimum Code requirements (not less than
Minimum Code requirements 3/4 hour at computer room) 1 1/2 hour at computer room)
Minimum Code requirements and not Minimum Code requirements (not less than 1 Minimum Code requirements (not less than
less than 1 m (3 ft) wide and m (3 ft) wide into computer, electrical, & 1.2 m (4 ft) wide into computer, electrical, &
2.13 m (7 ft) high mechanical rooms) and not less than 2.29 m mechanical rooms) and not less than 2.49
(7’-6” ) high m (8 ft) high
Allowed with minimum Code Interior windows allowed with Interior windows allows with
required fire rating minimum 1-hour fire rating, no minimum 2-hour fire rating, no
exterior windows allowed exterior windows allowed
Minimum Code requirements Minimum Code requirements (not less Minimum Code requirements (not less
than 1 hour) than 2 hour)
not required yes yes (physically separated from other
areas of the data center)
not required yes yes
73
yes Yes, with 16 mm (5/8 in) plywood lined Yes, with 16 mm (5/8 in) plywood lined
walls and solid core door walls and solid core door
If immediately adjacent, provided with Not immediately adjacent and provided with
no requirement leak prevention barrier leak prevention
barrier
Minimum Code requirements Minimum Code requirements (not less Minimum Code requirements (not less
than 1 hour) than 2 hour)
no requirement Minimum Code requirements (not less Minimum Code requirements (not less
than 1 m (3 ft) clear) than 1.2 m (4 ft) clear)
no requirement Immediately adjacent Immediately adjacent
Minimum Code requirements Minimum Code requirements (not less Minimum Code requirements (not less
than 1 hour) than 2 hour)
Minimum Code requirements Minimum Code requirements (not less Minimum Code requirements (not less
than 1 hour) than 2 hour)
Minimum Code requirements Minimum Code requirements and not less Minimum Code requirements and not
than 1.2 m (4 ft) clear less than 1.5 m (5 ft) clear
74
ANSI/TIA-942-A
TIER 2 (A2) TIER 3 (A3) TIER 4 (A4)
not required yes (minimum 19 mm (3/4 in) yes (steel bollards or similar
plywood wainscot) protection)
1 per 2500 m2 ( 25,000 ft2) of 1 per 2500 m2 (25,000 ft2) of 1 per 2500 m2 (25,000 ft2) of
Computer room Computer room (2 minimum) Computer room (2 minimum)
If within Data Center building, provided with Separate building or exterior weatherproof
no requirement minimum 2 hour fire separation from all other enclosures with Code required building
areas separation
no requirement 9 m (30 ft) or greater separation 19 m (60 ft) or greater separation
Building + Battery (4 hour min) Building + Battery (8 hour min) Building + Battery (24 hour min)
Building + Battery (4 hour min) Building + Battery (8 hour min) Building + Battery (24 hour min)
Use SDC requirements for building location Use SDC requirements for building Use appropriate SDC requirements for the
location site with SDC-C being the minimum
no requirement with Operation Status after 10% in 50 year with Operation Status after 5% in 100 year
event event
I=1.5 I=1.5 I=1.5
Concrete Shearwall / Steel Braced Concrete Shearwall / Steel Braced Frame Concrete Shearwall / Steel Braced
Frame Frame
passive dampers for IBC Seismic Design passive dampers/base isolation for IBC
Not required Category D or higher Seismic Design Category D or higher
CIP Mild Concrete Steel Deck & Fill Steel Deck & Fill
77
Utility, generator, and UPS system From utility down to but not including Throughout Distribution System
power distribution unit
Multiple single points of failure Single point of failure from last distribution No single points of failure for distribution
throughout the distribution system panel to critical and essential load only systems serving electrical equipment or
essential
load
Up-to-date short circuit study, coordination Up-to-date short circuit study, coordination Up-to-date short circuit study, coordination
study, and study, study,
arc flash analysis arc flash analysis, and load flow study arc flash analysis, and load flow study
Single Cord Feed with 100% Redundant Cord Feed with 100% Redundant Cord Feed with 100% capacity
capacity capacity on remaining cord or cords on remaining cord or
cords
2N Redundant Feed
Single Feed N+1 Redundant Feed from different utility substations or
generator plant
Switchboard with stationary circuit Switchboard with draw out circuit Switchgear with draw out circuit
breakers breakers breakers
78
ANSI/TIA-942-A
TIER 2 (E2) TIER 3 (E3) TIER 4 (E4)
N N+1 2N
Distributed Redundant Modules or Block Distributed Redundant Modules or
Single or Parallel Modules Redundant System Block Redundant System
Yes with non dedicated feeder to Yes, with dedicated feeder to Yes, with dedicated feeder to
automatic bypass automatic bypass automatic bypass
Non dedicated maintenance bypass feeder Dedicated maintenance bypass feeder Dedicated maintenance bypass feeder
to UPS output switchboard serving UPS output switchboard serving UPS output switchboard
Panel board incorporating standard thermal Switchboard incorporating removable circuit Switchboard incorporating removable
magnetic trip breakers breaker with adjustable long time and circuit breaker with adjustable long time,
instantaneous trip function short time and instantaneous functions with
provision to turn off instantaneous
function
Dedicated String for each module Dedicated String for each module Dedicated String for each module
10 Year valve regulated lead acid or 15 Year valve regulated lead acid or 20 Year lead acid flooded type or
flooded type or flywheel flooded type or flywheel flywheel
7 minutes 10 minutes 15 minutes
Standard high efficiency K-Rated or harmonic cancelling, high K-Rated or harmonic cancelling, low
efficiency Inrush high efficiency
If required by AHJ, push to activate with If required by AHJ, push to activate with If required by AHJ, push to activate with
cover guard and cover guard and warning label cover guard and
warning label warning label
Not required Yes Yes
Not required Yes Yes
Not required As allowed by local codes As allowed by local codes
Utility UPS Utility, Main Transformer, UPS, Generator, Utility, Main Transformer, UPS, Generator,
Generator Feeder Circuit Feeder Circuit Breakers, Automatic Static
Breakers, Automatic Static Transfer Switch, Transfer Switch, PDU, Automatic Transfer
PDU, Automatic Transfer Switches Switches, Surge
Protection Device, Critical Load Branch
Circuits
Control Room Console, Pager, Email, and/or Control Room Console,
text message Pager, Email, and/or
Control Room Console
text message to multiple facility personnel
Sized for UPS & mechanical system Sized for total building load N+1 Sized for total building load with 2N
without redundancy distributed redundancy distributed redundancy
Yes No No
Provision for Portable Provision for Portable Permanent sized for single largest
equipment
Generator Generator Generator
UPS UPS
Not required Automatic upon failure of utility Automatic upon failure of utility
Not required UPS and Generator Systems UPS and Generator Systems,
Generator controls, ASTS
Contact Resistance test of all circuit breakers Primary Injection and Contact Resistance
in critical and essential paths, 225 A and test of all circuit
Not required
higher breakers in critical and essential paths, 225
A and higher
Component level Component level and System Component level, system level, and
level integrated system including
total outage testing
Onsite Day Shift only. On-call at other Onsite 24 hrs M-F, on-call on Onsite 24/7
times weekends
Generator maintenance Generator and UPS maintenance Comprehensive preventative
maintenance program
Limited training by manufacturer Comprehensive training program for normal
operation of equipment and manual
Comprehensive training program for
operation of equipment during emergency
normal operation of equipment
operation
81
N+1 redundancy for mechanical equipment. N+1 redundancy for mechanical equipment. N+1 redundancy for mechanical equipment.
Loss of electrical power can cause loss of Temporary loss of electrical power will not Extended loss of electrical power will not
cooling cause loss of cooling, but may cause cause loss of cooling outside operational
temperature to elevate within range of critical equipment
operational range of critical equipment
One redundant AC Unit per critical area Qty. of AC Units sufficient to maintain critical Qty. of AC Units sufficient to maintain
area during loss of one source of electrical critical area during loss of one source of
power electrical power
Humidification provided Humidification provided Humidification provided
Single path of electrical power to AC Multiple paths of electrical power to AC Multiple paths of electrical power to AC
equipment equipment. Connected in equipment. Connected in
checkerboard fashion for cooling redundancy checkerboard fashion for cooling
redundancy
Single path condenser water Headered parallel piped condenser water Dual path condenser water system
system system
Single path chilled water system Dual path ladder loop chilled water Dual path chilled water system
system with isolation valves
Single path condenser water Headered parallel piped condenser water Dual path condenser water system
system system
82
ANSI/TIA-942-A
TIER 2 (M2) TIER 3 (M3) TIER 4 (M4)
Single path of electrical power to Multiple paths of electrical power to Multiple paths of electrical power
AC equipment AC equipment to AC equipment
Single path of electrical power to AC Multiple paths of electrical power to AC Multiple paths of electrical power to AC
equipment equipment equipment
Humidification provided Humidification provided Humidification provided
Control system failure will not interrupt Control system failure will not Control system failure will not interrupt
cooling to critical areas interrupt cooling to critical areas cooling to critical areas
Redundant, UPS electrical power to Redundant, UPS electrical power to BMS Redundant, UPS electrical power to
BMS Control Control BMS Control
Dual sources of water, or one Dual sources of water, or one source Dual sources of water, or one
source + on-site storage + on-site storage source + on-site storage
Single point of connection Two points of connection Two points of connection