1 Tag No.

I Quantity FT-8145-F 1 (One)


2 Service LP Fuel Gas Supply to Hot Oil Heater A
..J 3 P&ID No. SNO-R-Pl-105
w
ct
a: 4 Line No. I
Line Schedule 2"-FG-0013-1B SCH80
) z
w 5
6
NACE Requirement
Harzardous Area Classification I Protection Method
Yes
Zone-2, Gr.llB. T3 Exi
7 Ingress Protection I Tropicalization IP65 Yes
8
9 Fluid I Status Fuel Gas Gas
10 Flow (Max. / Nor./ Min.) MMScfd 2.168 1.843 0.434
I I
U)
wZ
uO
5E
11 Pressure (Max. / Nor./ Min.)
12 Temperature (Max./ Nor./ Min.)
psig
T
102
91
II 102
91
I
I
102
91
a: 0
wz
U) 0
13 Design Pressure psig 150
u 14 Design Temperature l 200
15
16 Type Foundation Fieldbus
17 Mounting 2· pipe mounting with bracket
18 Element Type Diaphragm
19 Element Material 31655
20 Connection Size (High & Low) 1/2" NPT
21 Body Material 31655
a: 22 Wetted 0-Rings Material 316LSS
w
23 Bolt and Nuts Material 31655
::i,:
U)
24 Housing Material I Paint Cast Aluminum Alloy High anti-corrosion coating
ct 25 Output Signal Foundation Fieldbus
.... 26 Power Supply 24VDC Loop power
27 Accuracy I Repeatability +-0.1 % of span +-0.25% of span
28 Temperature effect +-0.1% of span I 50 Deg F variation
29 Adjustable Range (Instrument Range) 4 400 in-H20@ 60DegF
30 Set Range (Calibration Range) 0 - 100 in-H20@ 60DegF
31 Electric Connection 1/2" NPT
32
33 Diaphragm Type I Diaphragm Material NIA NIA
::i,:
34 Fill Fluid NIA
ct ..J
a: ct 35 Capillary Material !Capillary Length N/A NIA
:cw 36 Armor Material NIA
0. U)
37 Allowable Over Temperature
)�
NIA
38
39 Integral Meter IScale (Note 3) LCD 0 - 3 MMscfd
40 Mounting Bracket !Type Yes Flat type
41 Valve Manifold Type IMaterial Integral 5-Way Manifold 31655
42 Cable Gland Yes
U)
w
43 Calibration Certificate Yes
U)
U)
44 Calibration Report Yes
w 45 Material Certificate Yes
u
u 46 Hydrosatic Testing Yes
ct
47 Material Tagging Plate 31655
48 Surge protector Yes
49
w 50 Manufacturer Yokogawa
51 Model EJA11 OE-FMS5G-91CDJIKS26/D1/X2/A/M01/T12/HC
U)
ct
52 Requisition Number
53 Purchase Order Number
54
Notes:
1. Vendor shall refer to the Standard specification for engineering and design of instrumentation systems. SNO-I-ES-001.
2. FISCO Certification is required for FF Transmitter.
3. Square Root scale shall be indicated. Square Root will be by transmitter

'
\
INSTRUMENT DATA SHEET FOR
FLOW TRANSMITTER
I PERTAMINA

-
GE
MtOC:OCP<f!IIOt

I (DP TYPE) .:2,


fHll"' "lt,,IM._A,, -•v-o

•-O--m�
1 15-Feb-2020 VAR Approved for Construction
..... ..,...... T,-tA.-•..... -su ...o C<H•t'llOf'l!ITIV ...
,.

0 16-Apr-2014 HJH Approved for Construction Sheet 115 of 118


REV. DATE BY DESCRIPTION Doc. No. : SN0-1-05-009 IREV.: 1

You might also like