Professional Documents
Culture Documents
Eccentric Reducers: Pumps Pipe Fittings
Eccentric Reducers: Pumps Pipe Fittings
Eccentric Reducers: Pumps Pipe Fittings
Eccentric reducers should be used near the pump, with the flat side up to keep the top of line Flanges, Centrifugal Pumps,
level. Nozzle, Reciprocating Pumps,
Centerline, Discharge Line, Pipe
From: Natural Gas Processing, 2014
Size, Suction Line, Suction Nozzle,
Suction Pipe
• To enable good access to valve handwheels and ease of NOTE: Always use the H dimension of the large end when determining
supporting, the discharge line should be turned flat after the the fitting length of any reducing fitting.
reducer, and the line angled away from the nozzle to enable the
Figure 3.48 represents the step-by-step procedures used to draw a
line to be supported from grade.
16″×14″ concentric reducer. Figure 3.49 shows the step-by-step
• Avoid supporting large lines from pipe-rack structures if possible, procedures that a 10″×8″ eccentric reducer, flat on bottom, is drawn
this enables minimum-size beam sections to be used and better with.
access for pump removal and maintenance.
Reducers/swage
Reducers are used to reduce or expand the line size. There are two
types of reducers: concentric and eccentric (Fig. 14.26).
Figure 3.48. 16″ × 14″ Concentric reducer. Manual step-by-step drafting procedures.
Energy Conservation
There are choices that can be made in the installation and pump
selection that can conserve energy. The selection of the most efficient
pumps and motors capable of doing the job is one area. Piping is
another area. Pipe sizing is normally a compromise between first cost
and operating costs but another area that is often overlooked is the
optimal recovery of the kinetic energy in the pump discharge. Many
times the discharge size of a pump is specified small, to allow the use
of lower cost valves at the discharge and then expanded up by means
of eccentric reducers.
The use of concentric reducers should be considered since they are
much more effective at converting the velocity pressure to static
pressure. The use of a conical 7° diffuser would result in a recovery of
approximately 90%14 whereas an eccentric reducer could have a
estimated best case recovery of 55%. If the velocity head at the
Download full-size image discharge flange is 3 m (10 ft.), then 2.7 m or 9 ft. would be recovered
Fig. 14.29. Eccentric reducer upstream of the pumps.
by the conical diffuser as opposed to the 1.65 m or 5.5 ft. recovery of
the eccentric reducer. This is a difference of 1.05 m or 3.5 ft. Some of
Elbows, like other fittings, can have butt weld, socket weld, or thread the unrecovered kinetic energy would be recovered later in the pipe,
connections. Applicable pressure ratings, dimensional standards, and just as in a sudden expansion. Taking this recovery as being 50%, we
material standards are as per the ASME B16.9 standard. This are now showing 1.75 ft. unrecovered, or an equivalent power loss of
standard covers all the wrought fittings with butt weld connections. almost 2%. Fig. 1.14 shows the result of a study by the U S
Socket and thread end elbows are covered by the ASME B16.11 Department of Energy, namely 240 billion kwh/yr potential savings in
standard. pump installations due to improvement in motor efficiency, electrical
Swages are functionally the same as reducers, which are used in distribution correction, motor drive/mechanical system matching e.g.
small sizes of screwed and socket connections (Fig. 14.30). The short adjustable speed drives, and process automation. While electrical
length of a reducer probably does not allow enough space to have a distribution may or may not be controllable by the user, the other
thread or socket on both ends. Swages are longer than reducers. three more significant factors of high efficiency motors, system
Swages, like reducers, are in both eccentric and concentric types. matching and process optimization are.
Swages can have three types endings—socket, thread, and beveled
end on both sides (Fig. 14.31). Swages are also called swage nipples.
Pumps
Seán Moran, in Process Plant Layout (Second Edition), 2017
31.10 Piping
Download full-size image
The design of pump suction piping is particularly important. It
Fig. 14.31. Forged and threaded swage connections.
should be arranged so as to minimize head loss (i.e., be as short and
straight as possible, with minimum valves and obstructions to flow).
View chapter Purchase book
When vessels are elevated, suction lines are preferably routed
overhead with top suction connections to pumps.
Any reduction in horizontal suction line size required at the pump
flange should be made with eccentric reducers with the bottom
Gas Gathering Systems
straight for pumps taking suction from below; and the top straight
David A. Simpson P.E., in Practical Onshore Gas Field Engineering, for pumps fed from above.
2017 All overhead pump suction lines should be arranged to drain from
6.3.5.2 Pigging equipment the equipment toward the pump without inverted pockets. Any
As we discussed in the last chapter, the only way to manage the risk changes in the direction of suction lines should be at least 600 mm
of internal corrosion in steel pipes is by removing any standing water. from the pumps to avoid unbalanced incoming flow.
It should have been clear in the last section that drip traps are only Any increase in size in non-vertical discharge lines should be
effective at removing the liquid that happens to arrive at the trap. achieved using eccentric reducers, arranged with bottom straight for
Liquid that accumulates away from drip traps is a serious corrosion delivery above pump, and top straight for delivery below. Discharge
risk and will often have detrimental impacts on your ability to control lines with flowmeters should preferably run vertically from the top of
operating pressure at well-sites. Finally, accumulated liquid can the pump to just above headroom height and then horizontally to the
become mobile for reasons and at times not of our choosing, and the piperack (but see Section 36.5). Positioning of flowmeters has to take
resulting slugs can do real harm. account of flow disturbance and the required number of pipeline
It is critical that we manage liquid accumulations as part of an diameters upstream and downstream from the meter of any
ongoing, carefully considered plan. The only way to manage these obstruction to flow.
liquid accumulations is to run a device through the line to displace Provision should be made to isolate the pump from the feed vessel
the liquid toward some piece of equipment that can capture it. This when it leaks or otherwise malfunctions so that it can be replaced
device is called a “pig.” There are many apocryphal stories about without draining the vessel. Isolation should be provided on the
where the name came from. It has been proposed that it is an discharge side in such a way that also allows safe access to any
acronym, and it has been proposed that the name comes from the nonreturn valves and instrumentation.
squealing sound it makes as it travels down the pipe. The acronyms
are sometimes humorous (such as “pipeline inspection gadget”), but View chapter Purchase book
incorrect. The persistent story is that early pigs were made of straw
wrapped in wire and the sound was distinctive. The sound of a pig
traveling down a pipe is rarely distinguishable from the background
flow sounds and when it is noticeable it doesn’t sound much like a Food Safety Management
“squeal.” The actual genesis of the name is that early pigs were
round, fat, and the end tapered toward something that looks slightly A.N Murray, in Encyclopedia of Food Safety, 2014
like a pig’s snout. That was the limit of thought that went into
Design of Product Contact Surfaces
naming this ubiquitous device.
Design of product contact surfaces needs to take the following into
Pigs are used for many specific tasks. Pigs to remove liquid are fairly account: surface texture, cleaning and inspection, disinfection,
simple and increasingly the industry is using “Turbo Pigs” (“Turbo pasteurization and sterilization, microbial ingress, draining, dead
Pig” is a registered trademark of Girard Industries) which are spaces, joints, coatings, internal angles, corners and grooves, seals,
reusable resilient plastic with a central core and a number of cups or gaskets, o-rings and joint rings, fasteners, process flow disruption
wipers. See the pigs toward the right-hand side and the small pig in caused by intrusions, shafts and bearings, sensor and sensor
front on the left-hand side of Fig. 6.13, but many people still prefer connections, other connections, and openings and covers.
the traditional “bullet” or porcine shape. If you need to clean the pipe
Surface texture: Cracks, pits, and folds are to be avoided and the
walls of solids accumulations, the pigs with brushes are available in
surfaces should be smooth.
both the Turbo style and the traditional porcine shape.
Cleaning and inspection: All equipment must be cleanable either in
or out of place and where possible the surfaces should be capable
of inspection after cleaning.
Disinfection, pasteurization, and sterilization: It should be possible
after cleaning to disinfect, pasteurize, or sterilize product contact
surfaces either in place or after disassembly.
Microbial ingress: Where necessary, equipment should be
designed to prevent ingress of microorganisms.
Draining: Pipelines and equipment should be completely
drainable. This generally requires the use of eccentric reducers in
horizontal pipe runs. It also necessitates that certain positive
Download full-size image
displacement pumps be mounted with their inlets and outlets in
Figure 6.13. Range of pigs.
the vertical.
Courtesy of Girard Industries (www.girardindustries.com).
The launcher and receiver in Fig. 6.14 represent nearly 30 years of my Sensor and sensor connections: They should be installed in such a
evolution in designing pigging equipment. When I look at the way that there are no dead spaces or crevices.
equipment that I did on my first project I dearly want to “fix” it, but it Other connections: All permanent and nonpermanent pipework
works and I’m not going to apologize for designing this equipment connections to equipment should be designed to prevent ingress
based on designs in common use in the industry. As usual the of contamination.
“designs in common use” are the result of compromises between Openings and covers: Hinges that allow crevices for soil to
fabrication complexity, cost, and operability (with limited input from accumulate should be avoided.
the operators), and are not as good as they could be. I’ve built upward
of 20 launcher/receiver pairs to the exact design represented by Fig. View chapter Purchase book
6.14 and it has been several years since I was last tempted to tweak it.
Reciprocating pumps
Maurice Stewart, in Surface Production Operations, 2019
Vents/drains. I put the barrel vent very close to the barrel-isolation An appendage dampener and cone strainer are installed in the
valve. This location was selected in response to several leaking barrel- suction line. An inline bladder/desurger and FSV are installed in the
isolation valves one after the other. When the barrel-isolation valve discharge line. The FSV protects against leakage from discharge when
has a small leak, the launcher is still usable, but when you seal the the pump is not running. It is preferable that this be a piston FSV to
throat with the pig the leaking gas will spit it out of the throat before keep it from chattering due to pressure pulsations. Nevertheless,
you have the closure shut, then opening the kicker valve will just swing FSVs are used successfully in some installations that follow the
bypass the pig. One inventive operator cut the handle off of a shovel design practices for minimizing pulsations. Drain valves are provided
and braced the handle between the pig and the closure, this allowed so that the pump can be maintained easily, and an oil PSL is provided
the pig to launch, but the stick had penetrated the pig and became to shut-in the motor.
the pig’s “tail” on the cleaning run. When it arrived, the tail prevented
API RP 14C requires a PSH be installed on the discharge so that the
the receiver barrel-isolation valve from closing and the line had to be
pump will shutdown before the discharge PSV opens. It also requires
blown down to remove the pig.
that a PSL sensor on the discharge be installed to shutdown the
There is also a vent on the spool between the “flange for extension pump in case of a large leak in the discharge piping. These two
spool” and the closure. That never gets used on the launcher. On the functions are carried out by one device.
receiver it is used to shift the pig out of the throat for retrieval (using
the other vent will stall the pig in the throat and it may not be View chapter Purchase book
possible to extract it without opening the barrel-isolation valve with
the closure open, a practice that should be discouraged).
I put a drain on both launchers and receivers. On receivers the drain
is piped to some disposal container that can hold the liquid from the Precooling and Surface Cooling of Mass
pig run. On launchers I generally build a small containment area to
Concrete
drain condensation. Some operators leave this drain open between
pig runs which adds to the surface corrosion inside the barrel and Zhu Bofang, in Thermal Stresses and Temperature Control of Mass
throat, but only minimally and has not been a problem. Concrete, 2014
Sweeps. Long pigs can have difficulty traversing a “long radius 45-
18.5 Cooling by Spraying Fog or Flowing Water over Top
degree elbow” which is the proper designation of the most common
of the Concrete Block
fitting used in gathering piping. By “long radius” ASME B16.7:
18.5.1 Spraying Fog over Top of the Concrete Block
Factory-Made Wrought Buttwelding Fittings means that the radius of
When pouring concrete in summer, it is better to form a foggy
the bend at the centerline of the pipe is 3 times the outside diameter
insulating layer over the top of the concrete block by spraying fog.
of the pipe. For launchers and receivers it is better to use a “hot
This could reduce the direct sunlight so as to lower the surface
bend” which is a length of pipe that has been heated and bent to a
temperature of the concrete block.
specific bend radius. The most common bend radius specified for
There are arc sprayer, straight tube sprayer, T-shaped sprayer, and
launchers and receivers is 6D, but I have seen 9D specified, the
axial flow fan sprayer. The former two can be used in large concrete
bigger the radius, the longer the pig that will traverse it. When smart
block, and the latter two are suitable for small concrete blocks. The
pigs first came into the industry it was common for smart pigs to
performances of these four kinds of sprayers are shown in Table 18.2.
require 42D bend radius, but that excluded virtually all pipelines from
using these tools. The technology has evolved and now most can pass
Table 18.2. Comparison of Performance of Four Kinds of Sprayers
a long-radius fitting, and all can pass a 6D sweep. When specifying
the fabrication of hot bends (also called “induction bends” or Spraying
Equipment Arc Sprayer Tube Sprayer T-Shaped Sprayer Axial Flow Fan Sprayer
“sweeps”), it is important to specify a minimum tangent length. The
Direct use of Pressure water, Pressure water, Pressure water, wind Water, electricity
bend starts with a length of pipe (e.g., a 12 in (300 DN) pipe would energy wind wind
have 60 in (152.4 mm) included a 6D 45-degree bend, the fabricator Performances The fog is dense The fogging The fogging range is The fogging range is
of spray and the effect of range is large, small, and the effect of small, and the effect of
will start with a pipe a bit longer if you don’t specify a tangent), no
fogging is good, while the effect fogging is common. fogging is common.
matter how careful the fabricator is there will be some amount of the fogging range of fogging is More sprayers should More sprayers should
is large common be placed in one block be placed in one block
ovality in the bent pipe, welding this out-of-round pipe to straight
Covering 5–20 10–20 4–7 6–15
pipe can be very difficult and will frequently cause the weld to fail range (m)
inspection. Adding pipe to the bend solves this. I always specify a Cooling effect 3–11 3–6 3–5 3–6
(°C)
minimum of 18 in (457 mm) tangents. It is common to get one
tangent, i.e., 15 in (381 mm) and the other 21 in (533 mm), but both
will be round pipe. In order to improve the effect of spraying, a fog-spray device was
successfully developed and used in the Three Gorges stage II Project.
View chapter Purchase book Pressure swirl atomizer atomizes the water into fine droplets, which
were then blown onto the surface of the concrete uniformly and
formed a fog layer. On one side, the fog droplets would evaporate by
absorbing heat; on the other side, the fog layer could reduce the
direct sunlight, thereby reducing temperature of the pouring surface.
Utilities II
Its working process is as follows.
Seán Moran, in Process Plant Layout (Second Edition), 2017 The pressure water gets into the combined atomizing nozzle through
the control valve, the pressure gauge and the filter, and then formed
15.9 Piping2
15.9.1 Main Steam Lines into micro droplets, of which the diameter ranges from 40 to
Steam lines should ideally be arranged to fall in the direction of flow, 100 μm. The control valve can adjust the water pressure within 0.3–
at not less than 100 mm per 10 m of pipe (1:100). This slope will 0.6 MPa, in order to control the atomizing. Oblique flow high-
ensure that gravity (and the flow of steam), will assist in moving the pressure blower generates high-pressure conveying flow, which
condensate towards drain points so that the condensate may be sends the droplets into the distance. The swinging system, consisting
safely and effectively removed (see Fig. 15.4). Any steam lines rising of a low-speed motor, worm gear reducer, eccentric wheel, swing
in the direction of flow should slope at not less than 250 mm per link, and a bracket, drives the fan to reciprocating swing of 3–4
10 m of pipe (1:40). times/minute within 0–90°. The elevation angle bracket installed
under the fan, according to the environmental condition, can
upgrade the fan within 0–20°.
The fog-spray device comprises atomizing system, conveying flow
system, and swinging system and the base, etc. The base is equipped
with a solid caster and can be pushed on the surface and change the
spray direction. The base bench was welded by angle steel, with steel
plate covered to the external, and can be removed for inspection and
maintenance of the swing system in the base box.
The effect of the fog-spray device used in the Three Gorges Project is
Download full-size image
as follows. (1) The temperature of the concrete is lower than the
Figure 15.4. Typical steam main installation.
Recommended publications
• Because the liquid velocity in the surge is higher than normal, the
dissipation of kinetic energy is higher than would normally be
expected
• Water is dense and incompressible, so it has high momentum,
and the “cushioning” effect experienced when gases encounter
obstructions is absent
• The energy in the water is dissipated against the obstructions in
the piping system such as valves and fittings.
Indications of water hammer include banging noises and pipe
movement. In severe cases, water hammer may fracture pipeline
equipment with almost explosive effect, with consequent loss of live
steam at the fracture, leading to an extremely hazardous situation.
Good engineering design, installation, and maintenance will avoid
water hammer. Avoidance by design is far better practice than
attempting to contain it by choice of materials and pressure ratings
of equipment. Commonly, sources of water hammer occur at the low
points in the pipework (see Fig. 15.10).
Branch line connections taken from the top of the main carry the
driest steam (Fig. 15.27). If connections are taken from the side, or
even worse from the bottom (as in Fig. 15.13A), they can accept the
condensate and debris from the steam main. The result is very wet
and dirty steam reaching the equipment, which will affect
performance in both the short and long term.
Steam flows from the inlet “A” through the perforated screen “B” to
the outlet “C.” While steam and water will pass readily through the
screen, dirt cannot. The cap “D” can be removed, allowing the screen
to be withdrawn and cleaned at regular intervals. A blowdown valve
can also be fitted to cap “D” to facilitate regular cleaning.
Strainers can, however, be a source of wet steam, as previously
mentioned. To avoid this situation, strainers should always be
installed in steam lines with their baskets to the side.
15.9.4.2 Steam Traps
Steam traps are the most effective and efficient method of draining
condensate from a steam distribution system. The steam traps
selected must suit the system in terms of pressure rating, capacity,
and suitability.
Pressure rating is easily dealt with; the maximum possible working
pressure at the steam trap will either be known or should be
established.
The capacity (quantity of condensate to be discharged) can be divided
into two categories; warmup load and running load. For warmup
load, in the first instance the pipework needs to be brought up to
operating temperature. The condensate load form this activity can be
determined by calculation, knowing the initial temperature, mass and
specific heat capacity of the pipework and fittings.
The initial pressure in the main will be little more than atmospheric
when the warmup process begins. However, the condensate loads
will still generally be well within the capacity of a DN15 “low capacity”
steam trap. Only in rare applications at very high pressures (above
70 barg) combined with large pipe sizes, will greater trap capacity be
needed.
For running load, once the steam main is up to operating
temperature, the rate of condensate production is mainly a function
of the pipe size and the quality and thickness of the insulation.
Steam trap types used to drain condensate from mains are shown in
Fig. 15.17. The thermostatic trap is included because it is ideal where
there is no choice but to discharge condensate into a flooded return
pipe.
Figure 15.18. A steam main trap set discharging condensate into a common return line.
With steam mains drainage, provided drain pockets are installed, the
drain line between the pocket and the steam trap may be horizontal.
If the drain pocket is not as deep as the recommendation, then the
steam trap should be fitted an equivalent distance below it (see Fig.
15.21).
Figure 15.22. Trap discharge lines pass condensate, flash and noncondensable gases.
These lines should fall in the direction of flow to maintain free flow of
condensate. On shorter lines, the fall should be discernible by sight.
On longer lines, the fall should be about 1:70, i.e., 100 mm every
7 m.
Discharging traps into flooded return lines is not recommended,
especially with blast action traps (thermodynamic or inverted bucket
types), which remove condensate at saturation temperature.
Good examples of flooded condensate mains are pumped return
lines and rising condensate lines. They often follow the same route as
steam lines, and it is tempting to simply connect mains drainage
steam trap discharge lines into them. However, the high volume of
flash steam released into long flooded lines will violently push the
water along the pipe, causing water hammer, noise and, in time,
mechanical failure of the pipe.
Where condensate from more than one trap flows to the same
collecting point such as a vented receiver, it is usual to run a
common line into which individual trap discharge lines are
connected. Provided the layouts as featured in Figs. 15.23–15.25 and
15.27 are observed, and the pipework is adequately sized, this is not a
problem.
Figure 15.25. Balanced pressure thermostatic trap with cooling leg into a flooded line.
Figure 15.26. Discharge from steam traps on temperature controlled equipment into flooded lines.
About ScienceDirect Remote access Shopping cart Advertise Contact and support Terms and conditions Privacy policy
We use cookies to help provide and enhance our service and tailor content and ads. By continuing you agree to the use of cookies.
Copyright © 2021 Elsevier B.V. or its licensors or contributors. ScienceDirect ® is a registered trademark of Elsevier B.V.