Setup
CT Type: 5A Frequency Type: 60Hz
Phase Rotation: ABC Expanded I/O: Disabled
Nominal Voltage: 120.0 (V) Nominal Current: 5.00 (A)
Delta-Y Transform: Disable VT Configuration: Line to Line
50DT Split Phase
59/27 Magnitude Select: DFT Differential: Disable
V.T. Phase Ratio: 1.0 (:1) V.T. Neutral Ratio: 1.0 (:1)
V.T. VX Ratio: 1.0 (:1) C.T. Phase Ratio: 10 (:1)
C.T. Neutral Ratio: 10 (:1)
I/O Settings
Latched Outputs: Pulsed Outputs:
Active Inputs (Open): Active Inputs (Close): 1, 2, 3, 4, 5, 6
Sealin Time
Output 1: 30 (Cycles) Output 2: 30 (Cycles)
Output 3: 30 (Cycles) Output 4: 30 (Cycles)
Output 5: 30 (Cycles) Output 6: 30 (Cycles)
Output 7: 30 (Cycles) Output 8: 30 (Cycles)
12/29/2018 Page 1 of 5
Dead Voltage Limit: 40 (V) Time Delay: 30 (Cycles)
Dead Input Enable: Dead V1 Hot VX: Enabled
Hot V1 Dead VX: Enabled Dead V1 Dead VX: Enabled
12/29/2018 Page 2 of 5
50/27: Inadvertent Energizing
50/27 (Disabled)
12/29/2018 Page 3 of 5
64S: 100% Stator Ground Protection by Low Frequency Injection
64S (Disabled)
81: Overfrequency/Underfrequency
81 #1
Blocking Inputs: FL Outputs: 7
Pickup: 57.00 (Hz) Time Delay: 30 (Cycles)
81 #2 (Disabled)
81 #3 (Disabled)
81 #4 (Disabled)
12/29/2018 Page 4 of 5
TC: Trip Circuit Monitoring
TC (Disabled)
IPS
IPSlogic #1
Blocking Inputs: Outputs: 4
Initiating Inputs: 1 Initiating Outputs:
Initiating Function
Pickup:
Initiating Function
Timeout:
Initiating Inputs Gate: OR Initiating Outputs Gate: OR
Initiating Outputs &
Initiating Function Gate: OR Function Control Gate: OR
Initiating Gateway: OR Initiate via Comm: Disabled
Blocking Inputs Gate: OR Block via Comm: Disabled
Time Delay: 30 (Cycles) Reset Delay: 0 (Cycles)
Profile: Not Activated
IPSlogic #2 (Disabled)
IPSlogic #3 (Disabled)
IPSlogic #4 (Disabled)
IPSlogic #5 (Disabled)
IPSlogic #6 (Disabled)
Function Trip:
Function Dropout: