Professional Documents
Culture Documents
Energy Saving Potential of Thermoelectric Radiant Cooling Panels With A Dedicated Outdoor Air
Energy Saving Potential of Thermoelectric Radiant Cooling Panels With A Dedicated Outdoor Air
Energy Saving Potential of Thermoelectric Radiant Cooling Panels With A Dedicated Outdoor Air
PII: S0378-7788(18)30234-2
DOI: 10.1016/j.enbuild.2018.03.062
Reference: ENB 8448
Please cite this article as: Hansol Lim , Jae-Weon Jeong , Energy saving potential of thermoelec-
tric radiant cooling panels with a dedicated outdoor air system, Energy & Buildings (2018), doi:
10.1016/j.enbuild.2018.03.062
This is a PDF file of an unedited manuscript that has been accepted for publication. As a service
to our customers we are providing this early version of the manuscript. The manuscript will undergo
copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please
note that during the production process errors may be discovered which could affect the content, and
all legal disclaimers that apply to the journal pertain.
ACCEPTED MANUSCRIPT
Highlights
VAV system and DOAS with CRCP were compared with DOAS with TEM-RCP.
T
DOAS with TEM-RCP showed 40.7% reduction in the annual energy compared
IP
with VAV system
CR
TEM-RCP consumed 1.0% more annual energy than that using the CRCP in
DOAS.
US
AN
M
ED
PT
CE
AC
1
ACCEPTED MANUSCRIPT
T
Department of Architectural Engineering, College of Engineering, Hanyang University,
IP
222 Wangsimni-Ro, Seongdong-Gu, Seoul 04763, Republic of Korea
CR
Abstract
US
AN
The objective of this study is to investigate the energy saving potential of a dedicated outdoor
air system (DOAS) with a thermoelectric module radiant cooling panel (TEM-RCP) by
M
comparing it with those of both a conventional variable air volume (VAV) system and a
DOAS with hydraulic ceiling radiant cooling panels (CRCP) via a detailed energy simulation.
ED
The theoretical and empirical models for each component were used to estimate the energy
performance of a VAV system and a DOAS with CRCP. Additionally, the TEM-RCP was
PT
analyzed by using the developed simulation models based on the semi-black box model.
CE
Hourly simulations were conducted to measure the annual energy performance. The results
indicated that the DOAS with a TEM-RCP consumed 40.7% less operating energy annually
AC
when compared with that of the conventional VAV system while the proposed system
exhibited only 1.0% more annual energy consumption when compared with the DOAS with
2
ACCEPTED MANUSCRIPT
hydraulic CRCP given the relatively low dimensionless figure of merit (ZT) of the TEMs (i.e.,
0.73) that is used in the TEM-RCP. However, the average coefficient of performance (COP)
of the TEM-RCP for cooling was 8.3, which is significantly higher than that of the
conventional CRCP (4.6) during the operation period. This is because the TEM-RCP uses a
cooling tower for heat removal, and its cooling water temperature is sufficiently low without
requiring additional cooling of the TEM except during summer. Therefore, TEM maintains
T
radiant panel temperature with low electric energy consumption. The study also indicated that
IP
if the ZT value of TEMs exceeded 0.75, then the proposed system exhibited lower annual
CR
energy consumption when compared to that of the DOAS with CRCP.
US
Keywords: Thermoelectric module; Radiant cooling panel; Non-vapor compression system;
AN
Dedicated outdoor air system; Variable air volume system
M
Nomenclature
ED
fp
CE
h Enthalpy [kJ/kg]
AC
3
ACCEPTED MANUSCRIPT
P Pressure [Pa]
T
R Electrical resistance of the lumped TEM [Ω]
IP
RH Relative humidity [%]
CR
S Seebeck coefficient of the lumped TEM [V/K]
Spd
T
Rotation speed [rpm]
Temperature [°C] US
AN
V Voltage [V]
Greek Symbols
∆ Difference [-]
𝜀
AC
Effectiveness [-]
𝜂 Efficiency [-]
4
ACCEPTED MANUSCRIPT
Subscripts
a Air
c Cold
T
cc Cooling coil
IP
cond Condenser
CR
CT Cooling tower
CWR
dp
Cooling water return
Dew point
US
AN
EA Exhaust air
EW Enthalpy wheel
M
h Hot
ED
hs Heat sink
in Inlet
PT
max maximum
CE
MA Mixing air
AC
OA Outdoor air
out Outlet
p Point
RA Return air
rem Remain
5
ACCEPTED MANUSCRIPT
SA Supply air
sat Saturation
SW Sensible wheel
tot Total
w Water
T
wb Wet-bulb temperature
IP
WB Water block
CR
Abbreviations
CAPFT US
Cooling capacity factor
AN
COP Coefficient of performance
1. Introduction
Over the last decade, a dedicated outdoor air system (DOAS) with a parallel sensible cooling
6
ACCEPTED MANUSCRIPT
system is attracting increasing attention due to its explicit benefits in securing good indoor air
quality with significant energy saving potentials [1,2] by decoupling sensible and latent
cooling functions. Ceiling radiant cooling panels (CRCP) were successfully used in several
alternative for conventional hydraulic radiant cooling panels [5–8]. The TEM is an element
T
that consists of n- and p-type semi-conductor thermocouples. Its operation is based on the
IP
thermoelectric effect, which converts electrical energy into thermal energy. Heat absorption
CR
and rejection occur at the cold and hot sides of TEM and create a temperature difference [9].
US
categorized into emerging non-vapor compression systems available as a heat pump [10]. The
AN
TEM exhibits advantages including the absence of refrigerants, chemical reactions, and
moving parts. It also includes advantages such as compact size, long life span of reliable
M
Shen et al. [5] indicated the feasibility of a TEM radiant panel-integrated air-conditioning
ED
system by using a theoretical simulation although their study only focused on the estimation
PT
of the cooling performance of their TEM radiant panels without thoroughly considering the
heat rejection method at the hot-side of TEMs. Liu et al. [6] proposed a photovoltaic-assisted
CE
TEM radiant cooling panel with a displacement ventilation system. In the proposed system,
the dehumidified ventilation air was supplied to the conditioned zone via the displacement
AC
ventilation system, and air-cooled TEM radiant cooling panels accommodated the sensible
cooling loads of the zone. The electric power required for operating TEM panels was
supplied by the photovoltaic (PV) system. The cooling capacity and coefficient of
performance (COP) of the TEM radiant cooling panels were 60 W/m2 and 0.9, respectively.
Meanwhile, theoretical models for the TEM radiant panel were suggested in extant studies
7
ACCEPTED MANUSCRIPT
[7,8] and were applied to the optimized panel design by optimizing design parameters such as
the arrangement of TEMs, suitable number of TEMs, and thickness of the panel and
insulation. Although extant studies suggest the use of a TEM radiant cooling panel (TEM-
RCP), limited studies examined the energy performance of TEM-RCP combined with an
independent ventilation system such as DOAS. Additionally, previous studies did not
consider the use of a water-cooled TEM-RCP that exhibits energy performance and
T
characteristics different from that of existing air-cooled TEM-RCP and conventional
IP
hydraulic CRCP.
CR
In this study, the energy saving potential of TEM-RCP combined with DOAS was evaluated
with respect to the reference case system, namely CRCP with DOAS by using detailed energy
US
simulations. Furthermore, a variable air volume (VAV) system was simulated as a case for
AN
conventional heating, ventilation, and air conditioning (HVAC) system for comparison
purposes. Existing empirical and analytical models for each system component were applied
M
via a series of energy simulations to evaluate the annual energy consumption and the
2. System overview
In the VAV system (Fig. 1), supply air flow rate is determined based on the cooling load in
the conditioned zone. Minimum required ventilation air is mixed with return air to reduce the
AC
energy consumption in the air conditioning coils. Based on the sensible and latent loads, the
operation mode is determined as cooling and heating modes. The supply air is cooled and
dehumidified by the cooling coil in the cooling mode and heated by the heating coil in the
heating mode to meet the supply air temperature set point condition. The air side economizer
control is commonly used in the intermediate season operation [2] to minimize energy
8
ACCEPTED MANUSCRIPT
consumption. The supply air set point condition included 13 °C dry bulb temperature and 80%
relative humidity in the cooling mode (i.e., the sensible load is positive) and 20 °C in the
T
IP
CR
US
AN
Figure 1. Schematic of a conventional VAV system
M
The DOAS considered in the study consists of an enthalpy wheel, a sensible wheel, and a
cooling coil [2] (Fig. 2). The DOAS accommodates all the latent loads of the conditioned
PT
zone by supplying dehumidified minimum required ventilation air. A portion of the room
sensible load is also accommodated by the DOAS based on the supply air temperature.
CE
The operation mode of the DOAS as shown in Figure 3 was also suggested by extant studies
AC
[2]. In Region 1, the enthalpy wheel initially cools and dehumidifies the introduced outdoor
air by exchanging heat and moisture between outdoor air and exhaust air without mixing. The
cooling coil additionally dehumidifies the supply air to meet the dew point temperature
setpoint of the supply air. The sensible wheel reheats the supply air by reclaiming sensible
heat from the exhaust air when the supply air temperature is excessively low and causes a
cold draft. In Region 2, when the outdoor air enthalpy is lower than that of the room air while
9
ACCEPTED MANUSCRIPT
the humidity ratio of outdoor air exceeds the target humidity ratio for the supply air, the
cooling coil dehumidifies outdoor air without operating the enthalpy wheel. The sensible
wheel reheats the supply air if necessary. In Region 3, when the humidity ratio of outdoor air
is lower than the target humidity ratio for the supply air, the enthalpy wheel is activated to
humidify the supply air to meet the target humidity ratio by reclaiming moisture from the
exhaust air stream. The supply air temperature setpoint is satisfied by the cooling coil. In
T
Region 4, the introduced outdoor air is preheated and humidified by the enthalpy wheel by
IP
reclaiming sensible heat and moisture from the exhaust air. The supply air temperature
CR
setpoint is satisfied by activating the sensible wheel. The temperature setpoint of the supply
air were 13 °C in the cooling mode and neutral temperature (e.g., 20 °C) in the non-cooling
US
mode [15]. Additionally, the setpoint of humidity ratio for the supply air was varied based on
AN
the latent loads to remove latent loads in the cooling mode [2].
The remaining space sensible load that was not satisfied by the DOAS should be
M
10
ACCEPTED MANUSCRIPT
T
IP
CR
US
AN
M
ED
Figure 2 shows the schematic of DOAS with a conventional CRCP combined system. The
air-cooled chiller supplies chilled water to the DOAS cooling coil and CRCP. The
AC
independent chiller for DOAS cooling coil and CRCP can be considered, however we
selected a single chiller application considering the initial cost and the system complexity.
Therefore, a two-way valve installed at the outlet of cooling coil adjusts the chilled water
flow rate based on the cooling coil load. In extant studies [16,17], the panel surface
temperature is generally 1 °C higher than that of the chilled water supply. Therefore, the
11
ACCEPTED MANUSCRIPT
valve to satisfy the chilled water temperature set point (i.e., 15 °C) entering the CRCP and
accommodating the remaining sensible load of the conditioned zone. Additionally, the panel
surface temperature is maintained as at least 1 °C higher than the dew point temperature of
T
2.4. Thermoelectric module radiant cooling panel
IP
The water-cooled TEM-RCP considered in this study is shown in Figure 4(a). It consists of an
CR
aluminum panel, TEMs, insulation, and water blocks. The water block (Fig. 4(b)) is a hollow
metal block with inside channels for circulating cooling water. The cold side of each TEM is
US
attached on the aluminum panel, and the water block is bonded on the hot side of each TEM
AN
to remove the released heat. It is necessary to insulate the top side of the TEM-RCP to
prevent the undesirable heat transfer to the plenum air. As shown in Figure 4(c), the cooling
M
tower is used to supply cooling water to the water blocks, and the two-way valve is installed
to modulate the cooling water flow rate entering the water blocks to maintain the hot side
ED
temperature set point of the TEMs. The hot side temperature set point of TEM is determined
PT
based on the temperature of cooling water supply, and it is discussed in section 5.1.
CE
AC
12
ACCEPTED MANUSCRIPT
T
IP
CR
US
AN
M
3. Simulation overview
PT
The model space conditioned by each system was a 100 m2 office space with 3-m ceiling
height. Two 10 m2 windows were located on the south and west exterior walls, and thus the
AC
window-to-wall ratio was 0.17. The sensible and latent heat generation rates of an occupant
were set as 75 W/person and 45 W/person, respectively, based on the ASHRAE Standard 90.1
[15]. The heat generation from the equipment (PC with a monitor) and light were 140
W/person and 13 W/m2, respectively, and the typical occupancy and system schedules
recommended by ASHRAE Standard 90.1 [15] for an office building were used to calculate
13
ACCEPTED MANUSCRIPT
the thermal loads by using the TRNSYS 17 program. The U-values of the roof, ceiling, wall
and windows were selected based on the local building code [14]. The room set point
conditions [14] were 25 °C dry bulb temperature and 50% relative humidity for cooling and
20 °C for heating. The calculated peak sensible load of the model space was 4.15 kW. The
T
Table 1. Physical conditions of the model space
IP
Location Seoul, South Korea
Weather data IWEC2 [18]
CR
Building type Open plan office
Geometry 10 m (W) × 10 m (L) × 3 m (H)
Roof, Ceiling 0.297 W/m2∙K
U-values [14] Wall
Windows
US
0.257 W/m2∙K
1.4 W/m2∙K
AN
Two 10 m2 windows (South and west)
Windows
Window-to-wall ratio: 0.17
140 W/person
Equipment
(Based on a PC with a monitor)
M
Temperature 25 °C
Cooling
Relative humidity 50%
Room set point
Temperature 20 °C
Heating
PT
Relative humidity -
CE
In the VAV system, the supply air flow rate is determined based on the sensible and latent
AC
load by using Equation (1). The return air flow rate is defined by Equation (2) based on the
supply air flow rate and the minimum required outdoor air ventilation rate as recommended
by the ASHRAE Standard 62.1 [19]. The outdoor airflow rate required per person was 2.5
L/s ∙ person, and the outdoor airflow rate required per unit area was 0.3 L/s ∙ m2 based on the
guidelines for office space. The zone population was assumed as 5, and the zone air
14
ACCEPTED MANUSCRIPT
distribution effectiveness was 1.0 for the ceiling supply of cool, warm air, and floor return.
Thus, the minimum required outdoor air ventilation rate was 0.0396 kg/s (≈ 110 m3/h), and
the maximum supply air flow rate was 0.245 kg/s in the VAV system. The dry bulb
temperature or humidity ratio of the mixed air is determined by using Equations (3) and (4) as
follows:
T
(𝑄̇ 𝑠𝑒𝑛 +𝑄̇ 𝑙𝑎𝑡 )
𝑚̇ 𝑆𝐴 =
IP
(1)
(𝑅𝐴,𝑃7 −𝑆𝐴,𝑃6 )
𝑚̇ 𝑅𝐴 = 𝑚̇ 𝑆𝐴 − 𝑚̇ 𝑂𝐴
CR
(2)
𝜔𝑀𝐴,𝑃2 =
𝑚̇ 𝑂𝐴 𝜔𝑂𝐴,𝑃1 +𝑚̇ 𝑅𝐴 𝜔𝑅𝐴,𝑃7
𝑚̇ 𝑆𝐴
US (4)
AN
In the cooling mode, the cooling coil load is determined by Equation (5). The cooling coil
M
meet the target temperature and humidity ratio of the supply air. If it is necessary to reheat the
supply air to avoid the overcooling of the zone, then the supply air is reheated up to the
ED
neutral temperature and the reheating coil load is calculated by using Equation (6). In the
PT
heating mode, the minimum required outdoor air ventilation is supplied into the conditioned
zone at the neutral temperature of 20 °C. The heating coil loads is described in Equation (7)
CE
as follows:
AC
15
ACCEPTED MANUSCRIPT
Based on Equations (1) to (7), the peak loads of the cooling coil, reheating coil, and heating
coil were 5.80 kW, 0.97 kW, and 2.64 kW, respectively. Therefore, the sizes of the coils were
T
Empirical models predicting sensible and latent effectiveness of an enthalpy wheel were
IP
found in the open literature [1,20]. In the DOAS operation, when the outdoor air condition is
CR
in Region 1 (Fig. 3) on a psychrometric chart, the enthalpy wheel should be rotated at full
speed (e.g., 18–20 rpm) [2] to obtain maximum sensible and latent effectiveness values
US
(𝜀𝑠𝑒𝑛,𝑚𝑎𝑥 and 𝜀𝑙𝑎𝑡,𝑚𝑎𝑥 ) as described in Equations (8) and (9) while the upper limits of
AN
sensible and latent effectiveness were assumed as 80% to prevent impractical results. The
On the other hand, in Region 2 (Fig. 3), it is necessary to deactivate the enthalpy wheel to
avoid increases in the enthalpy of the supply air due to increases in the cooling coil load. The
AC
target humidity ratio of supply air (𝜔𝑆𝐴 ) should be satisfied by the cooling coil. The sensible
wheel should be activated to reheat the supply air when the temperature of supply air (𝑇𝑆𝐴 )
after the temperature of the cooling coil is lower than the setpoint temperature (e.g., 13 °C).
When the outdoor air condition is in Region 3 or Region 4 (Fig. 3), the enthalpy wheel should
be operated to satisfy the target humidity ratio of the supply air (𝜔𝑆𝐴 ) by adjusting the latent
16
ACCEPTED MANUSCRIPT
effectiveness of the enthalpy wheel (𝜀𝑙𝑎𝑡 ) as expressed by Equation (10). The latent
effectiveness (𝜀𝑙𝑎𝑡 ) of the enthalpy wheel is adjusted by the rotating speed control. When the
required latent effectiveness of the enthalpy wheel is predicted by Equation (10), the adjusted
rotation speed (Spd) is determined by Equations (11) with the driving force ratio (DFR) as
defined by Equation (12) [1]. The sensible effectiveness of the enthalpy wheel (𝜀𝑠𝑒𝑛 ) under
T
IP
𝜔 −𝜔
𝜀𝑙𝑎𝑡 = |𝜔𝑆𝐴,𝑃2 −𝜔𝑂𝐴,𝑃1 | × 100 (10)
CR
𝑅𝐴,𝑃5 𝑂𝐴,𝑃1
𝐷𝐹𝑅 = 2430.6 × 2
𝑅𝐻𝑂𝐴,𝑃1
US
(𝜔𝑅𝐴,𝑃5 ;𝜔𝑂𝐴,𝑃1 )/(𝑇𝑅𝐴,𝑃5 ;𝑇𝑂𝐴,𝑃1 )
(12)
AN
In Regions 1 and 2, the sensible wheel is used to reheat the supply air by claiming waste heat
PT
from the exhaust air when the supply air temperature leaving the cooling coil is lower than
the setpoint temperature (e.g., 13 °C). In Region 4, the outdoor air humidified by the enthalpy
CE
wheel may require additional heating by the sensible wheel when the enthalpy wheel leaving
air temperature is lower than the supply air temperature setpoint. The sensible wheel
AC
effectiveness (𝜀𝑆𝑊 ) required to satisfy the target supply air temperature is determined by
Equation (14). The rotating speed of the sensible wheel at the required sensible wheel
17
ACCEPTED MANUSCRIPT
𝑇𝑆𝐴,𝑃4 −𝑇𝑆𝑊,P3
𝜀𝑆𝑊 = × 100 (14)
𝑇𝑅𝐴,𝑃5 −𝑇𝑆𝑊,𝑃3
The cooling coil load of the DOAS is determined by Equation (15). It is assumed that the
inlet chilled water temperature of cooling coil (𝑇𝐶𝑊𝑆,𝑐𝑐 ) is 8 °C, the temperature difference of
T
the chilled water across the coil is 5 °C, and the chilled water flow rate passing through the
IP
cooling coil (𝑚̇𝑤,𝑐𝑐 ) is controlled by the two-way valve based on the cooling coil load. The
CR
expression is as follows:
US
𝑄̇ 𝑐𝑜𝑜𝑙𝑖𝑛𝑔 𝑐𝑜𝑖𝑙 = 𝑚̇ 𝑆𝐴 (𝐸𝑊,𝑜𝑢𝑡,𝑃2 − 𝑐𝑐,𝑜𝑢𝑡,𝑃3 ) = 𝑚̇ 𝑤,𝑐𝑐 𝐶𝑝,𝑤 (𝑇𝐶𝑊𝑅,𝐶𝐶 − 𝑇𝐶𝑊𝑆,𝐶𝐶 ) (15)
AN
In DOAS, the size of the cooling coil was determined based on the peak load of cooling coil.
It was 1.43 kW, and this is significantly lower than that is the cooling coil in VAV because the
M
DOAS only uses the minimum required ventilation rate of 0.04 kg/s for the supply air flow
ED
rate.
PT
In the DOAS with the CRCP system, the CRCP accommodates the remaining sensible load
(𝑄𝑟𝑒𝑚 ) of the conditioned zone, and this was not satisfied by the DOAS supply air (Eq. 16).
AC
As shown in Figure 2, the chilled water leaving the cooling coil is supplied to the CRCP. The
chilled water flow rate circulating to the radiant panel system is constant, and the panel
follows:
18
ACCEPTED MANUSCRIPT
𝑄̇𝐶𝑅𝐶𝑃 = 𝑄̇𝑟𝑒𝑚 = 𝑄̇𝑠𝑒𝑛 − 𝑚̇𝑆𝐴 (𝑟𝑎,𝑃5 − 𝑠𝑎,𝑃4 ) = 𝑚̇𝑤,𝐶𝑅𝐶𝑃 𝐶𝑝,𝑤 (𝑇𝐶𝑊𝑅,𝐶𝑅𝐶𝑃 − 𝑇𝐶𝑊𝑆,𝐶𝑅𝐶𝑃 ) (16)
The peak cooling loads of the CRCP was 3.43 kW. In the hydraulic CRCP, the manufacturer
generally provides the cooling performance of the CRCP as the cooling capacity per square
meter with respect to the temperature difference between mean water temperature and room
air temperature and room designations. Therefore, the size of CRCP is defined by using the
T
area of panels. Based on the manufacturer cut sheet [22], the CRCP exhibits a cooling
IP
capacity of 136 W/m2 in the simulated condition, and it is necessary to use 25.2 m2 of CRCP
CR
to satisfy the cooling performance. Then, its covered area rate with respect to the ceiling area
The existing TEM model in extant studies [23] was derived as a function of the selected
M
thermophysical properties of the thermoelement used in TEM, such as heat conductivity (κ),
Seebeck coefficient (α), and electric resistivity (ρ) as defined by Equations (17) through (19).
ED
It is assumed that the thermoelements (i.e., p-type and n-type semi-conductors) exhibit
PT
temperature difference between cold and hot side (∆𝑇𝑚𝑎𝑥 ), maximum input current (𝐼𝑚𝑎𝑥 ),
CE
thickness (𝑙), and area of TEM (𝐴𝑇𝐸𝑀 ) were obtained from the TEM manufacture’s cut sheet
AC
[24]. The packing fraction (fp) and the number of thermoelement couples (N) of the selected
TEM were 0.5 and 127, respectively [25]. The expression is as follows:
19
ACCEPTED MANUSCRIPT
lumped TEM, such as Seebeck coefficient (S), electrical resistance (R) and thermal
T
IP
S = 2Nα (20)
4𝑁 2 𝑙
CR
R=𝐴 (21)
𝑇𝐸𝑀 𝑓𝑝 𝜌
𝐴𝑇𝐸𝑀 𝑓𝑝
K=κ (22)
𝑙
US
AN
In the DOAS with TEM-RCP shown in Figure 4, the remaining sensible load (𝑄𝑟𝑒𝑚 ) that was
not satisfied by the DOAS supply air is accommodated by the TEM-RCP. Thus, the cooling
M
load of the TEM-RCP (𝑄𝑐,𝑇𝐸𝑀;𝑅𝐶𝑃 ) should be identical to 𝑄𝑟𝑒𝑚 of conditioned zone with
an assumption for simplicity that the cold-side temperature of the TEMs (𝑇𝑐 ) was maintained
ED
at 15 °C and that the panel surface temperature converged to 16 °C due to the heat resistance
PT
of the aluminum panel. Consequently, the input current (I) to the TEM-RCP is determined by
Equation (23) [26]. The input voltage (V) and electrical power consumption (P) are also
CE
calculated by Equations (24) and (25), respectively. The amount of heat rejection
V = (I × R) + (S × ∆T) (24)
P =n×I×V (25)
20
ACCEPTED MANUSCRIPT
In the proposed TEM-RCP, the released heat from the hot-side of the TEMs were removed by
circulating cooling water produced by the cooling tower through the water blocks attached at
the hot side of TEMs as shown in Figure 4. The approach and the range of the cooling tower
were 2 °C and 10 °C, respectively [27]. The cooling water supply temperature (𝑇𝐶𝑊𝑆,𝐶𝑇 ) is
T
IP
determined by Equation (27). The hot-side temperature of the TEMs (𝑇 ) is expressed by
Equation (28) when the temperature difference between the hot-side of the TEM and the
CR
cooling water supplied (∆𝑇;𝐶𝑊𝑆 ) was known. The determination process is discussed in
US
section 5.1. The cooling water flow rate supplied to the TEM-RCP was modulated by the
two-way control valve based on the amount of released heat (𝑄,𝑇𝐸𝑀 ). The expressions are as
AN
follows:
M
𝑇 = 𝑇𝐶𝑊𝑆,𝐶𝑇 + ∆𝑇;𝐶𝑊𝑆
ED
(28)
PT
Meanwhile, the scavenger air flow rate of the cooling tower is determined by Equation (29)
with a liquid-to-gas ratio (LG ratio) of 1.5 obtained from the manufacturer’s cut sheet [28].
CE
The water flow rate of cooling tower (𝑚̇𝑤,𝐶𝑇 ) is determined by Equation (30) under the
AC
design condition. The design cooling water supply temperature (𝑇𝐶𝑊𝑆,𝐶𝑇,𝑑𝑒𝑠𝑖𝑔𝑛 ) is obtained by
Equation (27) with the design outdoor air wet bulb temperature (𝑇𝑂𝐴,𝑤𝑏,𝑑𝑒𝑠𝑖𝑔𝑛 ). The design
cooling water return temperature (𝑇𝐶𝑊𝑅,𝐶𝑇,𝑑𝑒𝑠𝑖𝑔𝑛 ) is determined by Equation (31) when the
heat exchange effectiveness of the water block (𝜀𝑊𝐵 ) was known (e.g., 0.8). The expressions
are as follows:
21
ACCEPTED MANUSCRIPT
𝑚̇
𝑚̇𝑎,𝐶𝑇 = 𝐿𝐺 𝑤,𝐶𝑇 (29)
𝑟𝑎𝑡𝑖𝑜
𝑄,𝑇𝐸𝑀,𝑚𝑎𝑥
𝑚̇ 𝑤,𝐶𝑇 = (30)
𝐶𝑝,𝑤 (𝑇𝐶𝑊𝑅,𝐶𝑇,𝑑𝑒𝑠𝑖𝑔𝑛 −𝑇𝐶𝑊𝑆,𝐶𝑇,𝑑𝑒𝑠𝑖𝑔𝑛 )
T
Additionally, the number of TEMs directly affects the initial costs of TEM-RCP and the
IP
covered area of radiant panel. As described in section 3.4, the cooling performance of radiant
CR
panel is defined by using the area of the panel because the cooling mechanism of radiant
cooling panel corresponds to convection and radiation heat transfer from the cooled panel.
US
Thus, any radiant panels exhibited identical cooling performance if they exhibited the same
area as that of the panel with identical panel temperature. Therefore, the TEM-RCP with a
AN
25.2 m2 also exhibited cooling performance equal to that of CRCP if both the panels exhibit
M
identical panel temperature. In case of the TEM-RCP, there is no manufacturer cut sheet but
there is a literature that provide the recommended length between TEMs for the radiant panel
ED
in the range of 0.387 m to 0.548 m [29]. The recommendation was derived based on the
dynamic heat transfer modeling for uniform temperature variation on the radiant panel.
PT
Therefore, it was assumed that the distance of 0.387 m between TEMs on the radiant panel
CE
was used, and it implied that a TEM corresponds to 0.15 m2. Thus, it was necessary to use
The air-cooled electric chiller model applied in the DOE-2 building energy simulation
program [30] was used to simulate the chiller energy consumption in each system case. In the
model, three performance curves, namely the available cooling capacity of the chiller
22
ACCEPTED MANUSCRIPT
(CAPFT) (Eq. 32), energy input of the cooling output factor (EIRFT) (Eq. 33), and part-load
efficiency of the chiller (EIRFPLR) (Eq. 34), were required to determine the required power
of the chiller (Eq. 35). The part load ratio (PLR) is defined by Equation (36). In the study, the
temperature of the chilled water supply (𝑇𝐶𝑊𝑆 ) was set as 8 °C. The expressions are as
follows:
T
𝐶𝐴𝑃𝐹𝑇 = 𝑓(𝑇𝐶𝑊𝑆 , 𝑇𝑂𝐴 ) (32)
IP
𝐸𝐼𝑅𝐹𝑇 = 𝑓(𝑇𝐶𝑊𝑆 , 𝑇𝑂𝐴 ) (33)
CR
𝐸𝐼𝑅𝐹𝑃𝐿𝑅 = 𝑓(𝑃𝐿𝑅) (34)
In the VAV system, it was assumed that the heating coil and reheat coil were used [31]. In the
heating mode, the heating load of the zone was accommodated by the parallel heating unit
PT
with an electric heating coil in all three system cases. All the heating coils are assumed to
CE
correspond to electric coils, and the energy consumption is calculated by using Equations (37)
to (39) as follows:
AC
23
ACCEPTED MANUSCRIPT
(a) Fan
There are two fans in DOAS unit in all the simulated cases. In the TEM-RCP, the energy
consumption of a fan in the cooling tower was considered. The power of fan (P𝑓𝑎𝑛 ) is derived
by using a general fan model [30] in Equation (40). The part load ratio of the fan (𝑃𝐿𝑅𝑓𝑎𝑛 ) is
defined in Equation (41). If the fan operates in constant air flow rate, the part load ratio of the
T
IP
fan (𝑃𝐿𝑅𝑓𝑎𝑛 ) is 1. The air flow rates of supply and return ducts in DOAS and cooling tower
were constant. The fan power at the design air flow and for the constant air volume fan is
CR
calculated by using Equation (42). The fan efficiency (𝜂𝑓𝑎𝑛 ) was assumed as 50% [32], and
US
the pressure drop (Δ𝑝𝑓𝑎𝑛 ) of each component applied on the simulation is listed in Table 2.
The pressure drops of the heat sink and direct evaporative cooler were used based on the data
AN
sheet from the manufacturer according to the air velocity. The expressions are as follows:
M
2 3
P𝑓𝑎𝑛 = (0.001 + 0.147 ∙ 𝑃𝐿𝑅𝑓𝑎𝑛 + 0.951 ∙ 𝑃𝐿𝑅𝑓𝑎𝑛 − 0.100 ∙ 𝑃𝐿𝑅𝑓𝑎𝑛 ) ∙ 𝑃𝑓𝑎𝑛,𝑑𝑒𝑠𝑖𝑔𝑛 (40)
ED
𝑉̇𝑎𝑖𝑟,𝑝𝑟𝑒𝑠𝑒𝑛𝑡
𝑃𝐿𝑅𝑓𝑎𝑛 = (41)
𝑉̇𝑎𝑖𝑟,𝑑𝑒𝑠𝑖𝑔𝑛
PT
𝑉̇𝑎𝑖𝑟,𝑑𝑒𝑠𝑖𝑔𝑛 𝛥𝑝𝑓𝑎𝑛
𝑃𝑓𝑎𝑛,𝑑𝑒𝑠𝑖𝑔𝑛 = (42)
𝜂𝑓𝑎𝑛
CE
24
ACCEPTED MANUSCRIPT
(b) Pump
The constant variable pumps were used in all cases by adjusting the inlet water flow rate by
using a two-way valve and by pass pipe. Therefore, the power consumption of pump (𝑃𝑝𝑢𝑚𝑝 )
is estimated by using Equation (43). The efficiency of the pump (𝜂𝑝𝑢𝑚𝑝 ) was assumed as
T
IP
60%, and the total head of components is summarized in Table 3.
CR
𝑉̇𝑓𝑙𝑢𝑖𝑑 ×H×9.8
𝑃𝑝𝑢𝑚𝑝 = (43)
𝜂𝑝𝑢𝑚𝑝
US
AN
Table 3. Total head of system components.
System component Total head (m)
Chilled water pump [37] 20
Ceiling radiant cooling panel [38] 7
M
4. Simulation results
PT
In Figure 5, the operating energy consumption of the components of each system during the
AC
summer were compared. As shown in the VAV system, the chiller and the heating coil for
reheating consumed most of the operating energy to accommodate all the sensible and latent
On the other hand, in both DOAS integrated systems, significant reductions in chiller and
reheating coil energy consumptions were observed due to the energy reclaimed by enthalpy
25
ACCEPTED MANUSCRIPT
wheel and sensible wheel used in the DOAS. Additionally, when the TEM-RCP was used
with the DOAS, the reduction in the chiller energy consumption was more significant than
that for the DOAS with the CRCP system although this benefit in chiller energy consumption
was offset by the energy consumption in TEMs. Consequently, it is concluded that the DOAS
with CRCP and the DOAS with TEM-RCP exhibited 38.6% and 27.3% total operating energy
savings, respectively, when compared with those of the conventional VAV system during the
T
summer. However, the DOAS with the TEM-RCP system exhibited 18.5% more energy
IP
consumption when compared with that of the DOAS with the CRCP system.
CR
US
AN
M
ED
PT
(b) Intermediate season (March, April, May, September, October, and November)
AC
Figure 6 shows a comparison of the operating energy consumptions during the intermediate
season in the three systems. The results indicate more significant heating and reheating coil
energy consumptions for heating the supply air in the VAV system while the chiller energy
consumption of the VAV system was lower than that of the DOAS with the CRCP system
thanks to the air-side economizer operation strategy. As expected, the DOAS with the TEM-
26
ACCEPTED MANUSCRIPT
RCP system exhibited the lowest chiller energy consumption although this advantage was
offset by the TEM energy consumption. Consequently, in the intermediate season operation,
both DOAS with CRCP and DOAS with the TEM-RCP systems exhibited significant total
operating energy savings of 37.3% and 42.3%, respectively, when compared with those of the
T
IP
CR
US
AN
M
In the operation during winter, all three system cases supplied the minimum required
CE
ventilation air to the conditioned zone at the neutral temperature (i.e., 20 °C) and the sensible
heating load in the zone was accommodated by the parallel heating units. Consequently, as
AC
shown in Figure 7, the only difference between the VAV system and two DOAS with radiant
panel systems corresponded to the heating and reheating coil energy consumptions. In the
DOAS with radiant panel systems, the enthalpy wheel and sensible wheel reclaimed the
sensible heat from the exhaust air to satisfy the supply air setpoint temperature, and this
provided energy benefits to the DOAS based systems. Thus, the DOAS with radiant panel
27
ACCEPTED MANUSCRIPT
systems saved 46.6% of operating energy when compared with that of the conventional VAV
system in winter.
T
IP
CR
US
AN
Figure 7. Energy consumptions of studied systems in winter
M
The annual energy consumption of three cases are compared in Figure 8. It is observed that
ED
the VAV system experienced significantly higher energy consumptions in the heating coil and
PT
fan energy due to reheating of the supply air and higher airflow rates to and from the
conditioned zone. Consequently, total annual operating energy savings of 41.3% and 40.7%
CE
were observed in the DOAS with CRCP and the DOAS with TEM-RCP, respectively, when
On the other hand, in the DOAS with TEM-RCP, significant chiller energy reduction was
obtained although this energy benefit was offset by the energy consumed in TEMs. Thus, the
DOAS with the TEM-RCP system consumed only 1.0% more operating energy (i.e., 0.04
28
ACCEPTED MANUSCRIPT
T
IP
CR
Figure 8. Comparison of the annual energy consumption of studied systems
5. Discussion US
AN
5.1. Influence of the weather condition
The studied cases of VAV system, DOAS with CRCP and TEMRCP showed difference
M
The VAV system showed lots of energy consumption in the cold weather because there is no
ED
energy recovery from the exhaust air and it consumed lots of heating coil energy. While, there
PT
were benefits in the intermediate season by air-side economizer operation in VAV system.
As shown in Figure 9, the total energy consumptions of studied systems were compared
CE
according to the month. The numbers labeled according to the month indicates the total
operation times of air-side economizer for each month. When the air side economizer was
AC
operated over about 240 hours, the VAV systems showed the least energy consumptions.
Therefore, even though the VAV system showed the most energy consumption annually in
Seoul, it can show better energy performance in the mild weather similar with the weather in
April, May, Jun, September and October of Seoul. Also, the DOAS with TEM-RCP showed
better performance than DOAS with CRCP except June, July, August and September. That is
29
ACCEPTED MANUSCRIPT
because the TEM-RCP can operate with high COP in the relatively cold and dry weather.
Therefore, the DOAS with TEM-RCP can show better performance in the microthermal and
dry climates. The detail about performance of TEM-RCP is described in section 5.3.
In addition, the characteristics of thermal loads affects to the energy performance of the
HVAC systems. In case of the DOAS, it shows good cooling performance in hot and humid
summer and energy recovery for heating in winter. However, if there is a building which has
T
year-round cooling loads, such as in the data center, the core of larger building, and so on, the
IP
air-economizer operation of VAV can show more energy savings in winter and intermediate
CR
season [41,42].
US
AN
M
ED
PT
CE
5.2. Temperature difference between the hot side of TEM and cooling water
The energy consumption of TEM increases with the temperature difference between hot and
cold sides. In the TEM-RCP, the cold-side temperature of the TEMs should be maintained at
15 °C to obtain the desirable panel surface temperature. Consequently, the hot side
temperature of the TEMs is critical in determining the energy consumption of the TEM-RCP.
30
ACCEPTED MANUSCRIPT
With respect to the hot side temperature of TEM, a trade-off exists between the performance
of TEM and required water flow rate. First, the hot side temperature of TEM should exceed
the cooling fluid for heat rejection (i.e., the cooling water supply). Therefore, the minimum
temperature difference between cold and hot sides of TEM is determined based on the
cooling water temperature. Subsequently, the key factor is the temperature difference between
hot side of TEM and cooling water (∆𝑇𝐶𝑊𝑆; ) in Equation (44), and it is necessary to
T
determine its optimum value. The expression is as follows:
IP
CR
∆𝑇𝐶𝑊𝑆; = 𝑇 − 𝑇𝐶𝑊𝑆,𝐶𝑇 (44)
US
The cooling water supply temperature ( 𝑇𝐶𝑊𝑆,𝐶𝑇 ) depends on the outdoor wet-bulb
AN
temperature (Eq. 27), and thus the hot side temperature of TEM (𝑇 ) is determined based on
the pre-defined temperature difference between the hot side of the TEM and cooling water.
M
If this temperature difference (∆𝑇;𝐶𝑊𝑆 ) is lower, then the energy consumption of TEM
decreases. However, the cooling water requires a large water flow rate (𝑚̇ 𝑤,𝐶𝑇 ) that leads to
ED
high energy consumption of the pump as shown in Equations (30) and (31). The lower hot
PT
side temperature of TEM (𝑇 ) decreases the cooling water return temperature (𝑇𝐶𝑊𝑅,𝐶𝑇 ). The
decreased cooling water return temperature (𝑇𝐶𝑊𝑅,𝐶𝑇 ) increases the cooling water flow rate
CE
(𝑚̇ 𝑤,𝐶𝑇 ). Additionally, the amount of heat rejection at the hot side of the TEM-RCP (𝑄,𝑇𝐸𝑀 ) is
AC
also dependent on the hot side temperature of TEM. Therefore, the optimal temperature
difference between the hot side of the TEM and cooling water supply (∆𝑇;𝐶𝑊𝑆 ) should be
investigated in terms of energy consumption of the TEM, pump, and fan energy from the
cooling tower
As shown in Figure 10, the annual energy consumptions of TEM and distribution equipment
31
ACCEPTED MANUSCRIPT
were investigated based on the temperature difference with an interval of 0.1 °C. Additionally,
the optimal temperature difference that shows the minimum total energy consumption was
determined by using a hill climbing algorithm based on the dichotomous search method [43].
Thus, the optimum temperature difference values between the hot side of the TEM and
T
IP
CR
US
AN
M
Figure 10. Optimization of the temperature difference between the hot side of the TEM and
cooling water
ED
The annual performances of TEM-RCP are shown in Figure 11. There are three main
CE
parameters that determine the performance, namely an input current, the temperature
difference between hot and cold sides of the TEM, and COP for cooling.
AC
In Figure 11(a), the TEM-RCP was operated under the average input current of 0.66 A ±
0.35. Additionally, the temperature difference between the hot and cold sides was 9.62 °C ±
5.31 (Fig. 11(b)). The COP of TEM-RCP exhibited a high value of 8.32 ± 13.52 (Fig. 11(c)).
Specifically, the TEM exhibited very high COP due to the low temperature difference
between hot and cold sides. The only exception was observed during extremely hot and
32
ACCEPTED MANUSCRIPT
humid weather.
From another perspective, the cooling tower supplies cooled water to the radiant panel.
However, the temperature of the water is not sufficient to ensure cooling to the panel
temperature of 16 °C due to the limitation of evaporative cooling (i.e., the high wet-bulb
temperature of outdoor air). Therefore, the TEM supports the cooling by Peltier effects to
ensure cooling to the panel temperature of 16 °C. In that respect, this is the reason the TEM
T
operates in the low temperature difference with high COP, and this achieves energy
IP
consumption similar to that of the vapor compression cycle based chiller.
CR
US
AN
M
ED
(a) Input current (b) Temperature difference (c) COP for cooling
Figure 11. Performance of TEM-RCP
PT
CE
5.4. Figure of merit for the thermoelectric module radiant cooling panel
The performance of TEM is quantified by using the figure of merit (Z) as shown in Equation
AC
𝛼2
Z= (45)
𝜌×𝜅
33
ACCEPTED MANUSCRIPT
The figure of merit is determined based on the characteristics of material and manufacturing
method. The general material for TEM is bismuth telluride (Bi2TE3) with ZT ranging from
0.7 to 0.9 [9]. In the study, we used a TEM with an average ZT value of 0.73, which
corresponds to a normal value. Therefore, the possible ZT value to achieve the energy savings
of TEM-RCP when compared with that of the CRCP was derived by increasing the Seebeck
coefficient to adjust the ZT value of TEM as shown in Figure 12. An increase in the ZT value
T
led to energy savings as observed at the ZT value of 0.75. It exhibited ZT values almost
IP
identical to that of the already commercialized TEM. Additionally, in a very recent study,
CR
thermoelectric materials with a ZT value over 1.5 to 2.5 were developed such as PbTe/PbS,
Pb0.98Tl0.02Te, Pb1+xSbyTe, and PbTe-SrTe [44–47]. If a TEM with a ZT value of 2.5 is applied,
US
then energy savings of 15.0% are achieved when compared to those of a system in which
AN
CRCP is used. Although high ZT value thermoelectric materials are not commercialized to
date, it is expected that TEM-RCP achieves energy savings as opposed to the use of a vapor
M
34
ACCEPTED MANUSCRIPT
Figure 12. Energy savings of TEM-RCP when compared with that of the CRCP based on the
ZT of TEM
6. Conclusions
In the study, the annual energy saving potential of DOAS with TEM-RCP was investigated by
using detailed energy simulations. As conventional systems, VAV and DOAS with CRCP
were also estimated to compare them with those of the DOAS with the TEM-RCP system.
T
The water-cooled TEM-RCP was considered for the heat rejection method. Thus, the TEM-
IP
RCP exhibited very high COP in the intermediate season based on the low temperature
CR
difference between the hot and cold sides of the TEM. However, the COP of TEM decreased
under 1.0 in a hot and humid climate with the temperature difference between cold and hot
US
sides exceeding 15 °C. In conclusion, 40.7% of annual energy savings is achieved by using
AN
DOAS with TEM-RCP when compared with that of the VAV system. Conversely, the TEM-
RCP is unable to achieve significant energy savings when compared with those of the CRCP
M
due to the low ZT of the TEM. However, the TEM-RCP exhibits advantages of the simple
control method since it uses input current and exhibits fast temperature response as well as
ED
accurate and stable control. Interestingly, it is a non-refrigerant system that does not include
PT
GWP and ODP. Additionally, the ZT values that derive energy saving when compared with
that of the CRCP were estimated as only 0.76, and this is similar with those of the latest
CE
commercialized TEM. Therefore, given the development speed of TEM, it is expected that
Acknowledgement
This work was supported by the Korea Agency for Infrastructure Technology Advancement
35
ACCEPTED MANUSCRIPT
References
[1] J.W. Jeong, S.A. Mumma, W.P. Bahnfleth, Energy conservation benefits of a dedicated
outdoor air system with parallel sensible cooling by ceiling radiant panels, ASHRAE Trans.
T
[2] H.J. Kim, S.J. Lee, S.H. Cho, J.W. Jeong, Energy benefit of a dedicated outdoor air
IP
system over a desiccant-enhanced evaporative air conditioner, Appl. Therm. Eng. 108 (2016)
CR
804–815.
[3] J. Niu, J. v. d. Kooi, H. v. d. Ree, Energy saving possibilities with cooled-ceiling systems,
[5] L. Shen, F. Xiao, H. Chen, S. Wang, Investigation of a novel thermoelectric radiant air-
M
ceiling combined with displacement ventilation system, Energy Convers. Manag. 87 (2014)
PT
559–565.
[7] L. Shen, Z. Tu, Q. Hu, C. Tao, H. Chen, The optimization design and parametric study of
CE
thermoelectric radiant cooling and heating panel, Appl. Therm. Eng. 112 (2017) 688–697.
AC
[8] Y. Luo, L. Zhang, J. Wu, Z. Liu, Z. Wu, X. He, Dynamical simulation of building
integrated photovoltaic thermoelectric wall system: Balancing calculation speed and accuracy,
[9] H. Lee, Thermoelectrics: Design and Materials, John Wiley & Sons, Inc, Publication,
2017.
36
ACCEPTED MANUSCRIPT
[11] W. He, G. Zhang, X. Zhang, J. Ji, G. Li, X. Zhao, Recent development and application of
[12] Z. Liu, L. Zhang, G. Gong, H. Li, G. Tang, Review of solar thermoelectric cooling
technologies for use in zero energy buildings, Energy Build. 102 (2015) 207–216.
T
[13] U.S.D. of Energy, Overview of existing and future residential use cases for connected
IP
thermostats, (2016).
CR
[14] K.E. Agency, Regulations for the operation of building energy efficiency rating system,
(2016).
US
[15] ANSI/ASHRAE/IES Standard 90.1-2013: Energy standard for buildings except low-rise
AN
residential buildings (SI edition), (2013).
cooling capacity determination of cooling ceiling radiant panel system, Sci. Technol. Built
[17] Z. Tian, X. Yin, Y. Ding, C. Zhang, Research on the actual cooling performance of
PT
[19] ANSI/ASHRAE Standard 62.1-2013: Ventilation for acceptable indoor air quality,
(2013).
AC
[20] J.W. Jeong, S.A. Mumma, Practical thermal performance correlations for molecular
sieve and silica gel loaded enthalpy wheels, Appl. Therm. Eng. 25 (2005) 719–740.
[22] Technical Data Sheet for radiant cooling panel, STERLING, (2013).
37
ACCEPTED MANUSCRIPT
[23] M. Chen, G.J. Snyder, Analytical and numerical parameter extraction for compact
[24] Hebei I.T. (Shanghai) Co., Ltd., Technical Data Sheet for TEC1-12706.
[25] G. Tan, D. Zhao, Study of a thermoelectric space cooling system integrated with phase
[26] H. Lim, J. Jeong, Energy saving potential of thermoelectric modules integrated into
T
liquid desiccant system for solution heating and cooling, Appl. Therm. Eng. (submitted).
IP
[27] J.W. Mitchell, J.E. Braun, Principles of heating, ventilation, and air conditioning in
CR
buildings, John Wiley & Sons, Inc, Publication, (2013).
US
[29] Y. Luo, L. Zhang, Z. Liu, Y. Wang, J. Wu, X. Wang, Dynamic heat transfer modeling and
AN
parametric study of thermoelectric radiant cooling and heating panel system, Energy Convers.
1–847.
ED
[31] M.H. Kim, Energy performance evaluation of liquid desiccant and evaporative cooling-
PT
assisted 100% outdoor air system (Ph.D. Thesis), Hanyang University, (2016).
[32] S.J. Lee, H.J. Kim, H.W. Dong, J.W. Jeong, Energy saving assessment of a desiccant-
CE
enhanced evaporative cooling system in variable air volume applications, Appl. Therm. Eng.
[33] M.H. Kim, S.W. Ham, J.S. Park, J.W. Jeong, Impact of integrated hot water cooling and
(2014) 384–396.
38
ACCEPTED MANUSCRIPT
[35] S. De Antonellis, M. Intini, C.M. Joppolo, C. Leone, Design optimization of heat wheels
[36] P.M.V Subbarao, Thermal analysis and design of cooling tower, (2011).
[37] H.W. Dong, S.J. Lee, D.S. Yoon, J.Y. Park, J.W. Jeong, Impact of district heat source on
(2017) 432–444.
T
[38] U. Inc., Radiant cooling design manual (1st edition), (2013).
IP
[39] J. Tsao, S. Hu, T. Xu, D.Y.L. Chan, Capturing energy-saving opportunities in make-up
CR
air systems for cleanrooms of high-technology fabrication plant in subtropical climate,
US
[40] PRICETWA, Radiant heating systems, (2009).
AN
[41] J. Siriwardana, S. Jayasekara, S.K. Halgamuge, Potential of air-side economizers for
data center cooling: A case study for key Australian cities, Appl. Energy 104 (2013) 207-219.
M
[42] S.W. Ham, J.S. Park, J.W. Jeong, Optimum supply air temperature ranges of various air-
side economizers in a modular data center, Appl. Therm. Eng. 77(2015) 163-179.
ED
[43] Y. Jaluria, Design and optimization of thermal systems (2nd edition), CRC Pres, (2008).
PT
[44] J. Androulakis, C.H. Lin, H.J. Kong, C. Uher, C.I. Wu, T. Hogan, B.A. Cook, T. Caillat,
K.M. Paraskevopoulos, M.G. Kanatzidis, Spinodal decomposition and nucleation and growth
CE
[45] A.J. Minnich, M.S. Dresselhaus, Z. Ren, G. Chen, Bulk nanostructured thermoelectric
materials: current research and future prospects, Energy Environ. Sci. 2 (2009) 466.
39
ACCEPTED MANUSCRIPT
[47] Y. Kim, L. Zhao, M.G. Kanatzidis, D.N. Seidman, Analysis of nanoprecipitates in a Na-
Doped PbTe − SrTe thermoelectric material with a high figure of merit, ACS Appl. Mater. 9
(2017) 21791–21797.
T
IP
CR
US
AN
M
ED
PT
CE
AC
40