Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021

Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA


Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Site inspection was carried out on Hollywood villa on 5 August by EES. The electrical panels and wiring were in a
good condition and very few issue to report.

Only a few points to mention:


1. Lighting system in the public areas and uostairs bed roims was turned off due to fault on the control panel. A
company was notified already and the isdye was being dealt with.
2. A few airckns were found faulty abd out of service.
3. Many areas rust was evident and should be addressed to prevent further rust damaged.
4. Earthing was nit found on the pool lighting control panel.
5. The pool lights cintrol contactor was noisey when testing. This should be replaced

Doc. Id.: 4.1


page 1 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Thu 05 Aug 20:09 2021


Ocean facing 6 bedroom guest
house. Has pool, whirlpool tub and
direct accees to the ocean.

(1)

67.jpeg

Doc. Id.: 4.1


page 2 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(2)

95.jpeg

Created: Fri 06 Aug 13:22 2021


Main electrical meter for the residence, located in the entrance garage

Doc. Id.: 4.1


page 3 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(3)

68.jpeg

Created: Thu 05 Aug 20:10 2021


Main distribution board, 125 A mains breaker 50mm supply cable. TNS, 3 phase configuration.400 volts mains
supply voltage. Voltage between earth and neutral slightly above 1 volt. This is not a concern given the property
is built on a rock getting a clean earth can be a challenge.

Doc. Id.: 4.1


page 4 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Thu 05 Aug 20:11 2021


Single phase voltage 230 volt, 50 hz
supply

(4)

69.jpeg

Doc. Id.: 4.1


page 5 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(5)

71.jpeg

Created: Thu 05 Aug 20:12 2021


3 phase voltage on site

Doc. Id.: 4.1


page 6 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Thu 05 Aug 20:11 2021


PSC test proved succesful. Any fault
current should not exceed the ka
rating of the mains breaker. Here the
test shows 1.15ka rating which is
below the main breaker rating of
25ka. The mains breaker offer
overload and short circuit protection
only, there is not earth leakge
protection on the panels
(6)

70.jpeg

Doc. Id.: 4.1


page 7 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(7)

82.jpeg

Created: Thu 05 Aug 20:20 2021


Mains breaker current draw on blue phase, 89Amps, Blue phase slightly higher than red and yellow phase.

Doc. Id.: 4.1


page 8 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(8)

84.jpeg

Created: Thu 05 Aug 20:20 2021


Yellow phase current draw 82 amp.

Doc. Id.: 4.1


page 9 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(9)

83.jpeg

Created: Thu 05 Aug 20:20 2021


Red phase current draw 73 amp

Doc. Id.: 4.1


page 10 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Thu 05 Aug 20:14 2021


Earth continuity was tested
throughout the building and found to
be satisfactory. All outlets tested
have earth connections. EARTHING
reading to be below 1 ohm.

(10)

74.jpeg

Doc. Id.: 4.1


page 11 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(11)

76.jpeg

Created: Thu 05 Aug 20:16 2021


150lt hotwater storage tank that feeds the premises, pulling 9 amp during operation is correct, the system is a
2.1kw storage vessal and is correctly earthed. There is not dedicated isolation device for this storage system.

Doc. Id.: 4.1


page 12 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(12)

77.jpeg

Created: Thu 05 Aug 20:16 2021


Spec of the hot water storage tank

Doc. Id.: 4.1


page 13 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(13)

78.jpeg

Created: Thu 05 Aug 20:17 2021


Pool lighting could not be tested, the contactor is shuddering when turned on to test, so left switched off. The
is also no grounding of this panel, given its location in the pool pump room directly adjacent the surge tank this
shouldbe rectified

Doc. Id.: 4.1


page 14 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(14)

79.jpeg

Created: Thu 05 Aug 20:18 2021


Pool pump control panel, the pool lighting contactor is faulty and needs replacing, we could not test pool
lighting. Panel showing signs of rusting and can be painted with anti corrosive paint to prevent further
corrosion

Doc. Id.: 4.1


page 15 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(15)

80.jpeg

Created: Thu 05 Aug 20:19 2021


Pool pump, 2HP Hayward pump operating normaly at 8 amps.......filter did not have a pressure gauge to indicate
pressure through the filter

Doc. Id.: 4.1


page 16 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(16)

85.jpeg

Created: Thu 05 Aug 20:22 2021


Several sockets tested and opened on site. All connections and polarity normal. 2.5mm cable on socket
outlets.

Doc. Id.: 4.1


page 17 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(17)

86.jpeg

Created: Thu 05 Aug 20:22 2021


Sockets tested in various locations, polarity tested correctly and safe

Doc. Id.: 4.1


page 18 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(18)

90.jpeg

Created: Fri 06 Aug 13:07 2021


Booster pumps villa water supply, working and cables correctly terminated

Doc. Id.: 4.1


page 19 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Fri 06 Aug 13:07 2021


Working pressure for the prpoerty
around 4 bar

(19)

91.jpeg

Doc. Id.: 4.1


page 20 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(20)

92.jpeg

Created: Fri 06 Aug 13:07 2021


Pressure pump control panel. Earth is continueous throughout property

Doc. Id.: 4.1


page 21 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(21)

93.jpeg

Created: Fri 06 Aug 13:07 2021


Water storage vessel located in water pump room. 100lt. Fed from sump pump control panel. There is not
dedicated isolator for this hot water system.

Doc. Id.: 4.1


page 22 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Fri 06 Aug 13:07 2021


Specs of hot water storage in
booster pump room

(22)

94.jpeg

Doc. Id.: 4.1


page 23 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

(23)

96.jpeg

Created: Fri 06 Aug 13:28 2021


Whirlpool was out of service when testsing was done

Doc. Id.: 4.1


page 24 of 25
Contact: Sean Reynolds Created: Thu 05 Aug 20:01 2021
Company: Engineering Environmental Services Location: CAPE PANWA HOLLYWOOD VILLA
Phone: +66654104428 Title: MEP INSPECTION
Email: eesolutions8@gmail.com No. Items: 24

Created: Fri 06 Aug 13:29 2021


Controls for whirlpool tub where
turned off. Air blower was tested
and works, water pressure from
taps was very low.

(24)

97.jpeg

Doc. Id.: 4.1


page 25 of 25