CALCULATION SHEET FOR PULL OUT PILE LOAD TEST

Pile Dia : mm

Safe Design Load : 0.95 MT

Test Load = 2.5 X Safe LOAD = =0.95 x 1.5 = : 1.43 MT

Increment / Decrement @ 20% of Safe Design Load = =0.2 x 0.95 = : 0.19 MT

2
Ram Area of Jack : 32.97 cm

2
Least Count of Pressure Gauge : 5 kg/cm

Increment Load for each stage : 0.19 MT

2
Equivalent Increment Pressure for Increment Load =0.19 x 1000 / 32.97 : 5.76 kg/cm

No. of division corresponding to Increment Pressure =5.76 / 5 : 1.15 Div

Total No of Division to be applied for each Increment 1.0 Div

Actual Applied load each Stage =1 x 5 x 32.97 / 1000 : 0.16 MT

No. of Increments = 1.43 / 0.16 : 8.64 Nos


Say : 9.0 Nos

Final Test Load =9.0 x 0.16 : 1.48 MT