OPERATION MANUAL
(DC INVERTER SERIES)
(HYBRID INVERTER&EVI SERIES)
User Panel
Defrosting Clock/Timing
Electrical heater
Tank heating mode
Compressor
2. Electrical heater is
5. WIFI function is
Down key
FUNCTIONS
M
M
A. Press Set Key time after time to select shows item to be U07
C. Press Set Key again for 5 seconds to confirm the Temp setting
M
M
4. Set Room Heating Mode (Floor or Radiator) and Desired Return Temp)
A. Press Set Key time after time to select shows item to be U10, set
U10=1, it is radiator mode, the return temp can set to be 55℃, set
U10=0, it is floor mode, the return temp can set to be 45℃.
B. Press Set Key time after time to select shows item to be U05, set
the desired return Temp.
C. Press Set Key again for 5 seconds to confirm the Temp setting
FOSHAN
*Press SHUNDE ENSKey
Up or Down ELECTRIC CO
to adjust LTD
the Temp Value www.ens-energy.com
5. Set Auto Mode ( Tank +Room Heating, Exchange Automatically )
M
M
- In Auto Mode, the unit first to heat storage tank follow item 2 setting, when the set temp is reached,
then automatically change to heat room follow item 4 setting. (Change the water flow direction).
6. Set Temp Difference for Unit Restart in Tank or Room Heating Mode
- When the actual temp of storage tank dropped a certain degrees and meet the set temp difference value:
A. In Auto mode, the unit will back to work at tank heating mode from room heating mode.
B. In Only tank heating mode, the unit will be restarted from standby condition.
- When the actual temp of Room return temp dropped a certain temp and meet the set temp difference value:
A. In Auto mode, the unit will back to work at room heating mode from tank heating mode ( if the set tank temp is
reached)
B. In Only room heating mode, the unit will be restarted from standby condition.
Operation
• Turn off the unit or do not start the unit, make it in standby condition.
• Keep on press “ USER SET KEY” to enter Administrator Mode, need to fill in password (1000), press “UP KEY”
once the first digit shows 1, then press “ USER SET KEY” again to confirm the first digit of password, now the
four digit shows 1000
• Keep on press “ USER SET KEY” to activate Administrator Mode, the screen shows P00
• Press “ USER SET KEY” one by one to change the showing item to be P09 or P10
• Press “DOWN or UP KEY” to change the setting value
• Keep on press “ USER SET KEY” to confirm the setting.
• Press “ON/OFF KEY” once to quit the mode.
A. Press Set Key time after time to select shows item to be U12
M
M C. Press Set Key again for 5 seconds to confirm the setting
B. Press Up or Down Key to adjust value to be 1 to activate WIFI control function, if it is 0, the WIFI function is closed
A. Press Set Key time after time to select shows item to be U14,
Press Up or Down key to change the original value 12, after this,
keep on press Set Key for five seconds to confirm the setting.
M
M B. Do above operation again for other digit of U15-U17.
9. Set Clock
- Display of Clock
Administrator Mode
• Turn off the unit or do not start the unit, make it in standby condition.
• Keep on press “ USER SETTING KEY” to enter Administrator Mode, need to fill in password (1000), press “UP KEY”
once the first digit shows 1, then press “ USER SETTING KEY” again to confirm the first digit of password, now the four
digit shows 1000
• Keep on press “ USER SETTING KEY” to activate Administrator Mode, the screen shows P00
• Press “ USER SETTING KEY” one by one to change the showing item from P01-P98
• Press “Down or UP KEY” to change the setting value
• Keep on press “ USER SETTING KEY” to confirm the setting.
• Press “POWER KEY” once to quit the mode.
P value
P00-P06 Reserved - - -
P08 Set a temp for entry ambient too low -1℃ -25℃ -30℃
protection mode
P12* Set interval time for two defrosting mode 70 minutes 40 minutes 25 minutes
P16 Set max user side inlet water temp in room 45℃ 33℃ 33℃
heating mode
P17 Set max user side inlet temp in tank 58℃ 45℃ 45℃
heating mode
P19-P45 Reserved - - -
P46 Set a tank temp for start extra electrical 60℃ 60℃ 30℃
heater
P47 Reserved - - -
P51 Set interval time for oil return operation in 30 minutes 10 minutes 10 minutes
low compressor speeds
P52 Set running time for oil return operation 2 minutes 1 minute 1 minute
P55-P64 Reserved - - -
P66-P87 Reserved - - -
FAULT CODE
1. If the failure occurs, the related fault code will be displayed on the panel. The unit could be stopped automatically or
cannot be started again to avoid making any danger or personal injury.
⚠ Please call your local service provider or contact the factory telling them the fault code. The fault need to be handled by
professional technicians, The personal injury would be caused by any unqualified operation of maintenance.
Er02 IPM module loading parameters failure Er03 IPM module over current
Er20 IPM module temperature sensor abnormal Er21 IPM module temperature is too high
Er32 IPM module communication failure Er33 Ambient temperature sensor failure
Er34 Storage tank temperature sensor failure Er35 User side inlet temperature sensor failure
Er36 User side outlet temperature sensor failure Er37 Compressor exhaust temperature sensor failure
Er38 Compressor suction temperature sensor failure Er39 Evaporating temperature sensor failure in heating
mode
Er40 Condensing temperature sensor failure in heating Er41 Storage tank inlet temperature sensor failure (Into
mode water tank)
Er42 Storage tank outlet temperature sensor failure Er43 Ground source outlet temperature sensor failure
(Into heat pump) (into heat pump)
Er44 Ground source inlet temperature sensor failure Er45 Before EEV temperature sensor failure
(into ground)
Er46 Coil gas inlet temperature sensor failure Er47 Economizer gas inlet temperature sensor failure
Er48 Economizer gas outlet temperature sensor failure Er49 Temperature sensor failure
Er52 Temperature sensor failure Er53 IPM module temperature is too high
Er54 System exhaust pressure is over load Er55 System suction pressure is too low
Er56 System exhaust temperature is too high Er57 Condensing temperature is too high
Er64 Water flow is not enough (Flow switch is opened) Er65 User side outlet temperature abnormal
Er66 Floor pipe outlet temperature abnormal Er67 Ambient temperature is too low
Er78 User side inlet temperature sensor is fall out Er79 Cooling low temperature abnormal
Er80 Water flow of storage tank abnormal Er81 Water flow of ground source abnormal
Er82 Ground source temperature is too low Er83 Water is overflow in drainage plate